Electrical work in connection with provision of Power supply arrangement for New mechanized Laundary at ASH & GTNR, power supply arrangement work for SETC of PERC Dry cleaning machine , SETC of Tumbler Dryer , SETC of Rotary screw electric driven Air compressor , SETC of washer extractor , SETC of folder machine with stacker and SITC of feeder machine at linen center at GKP.
SRDEE-LJN-15-2026
SRDEE-LJN-15-2026
Open
6 Months
Unknown (Unspecified Location)
₹0
₹5.7 L
5 Jun 2026
5 Jun 2026
22 Jun 2026
A-Electrical work in connection with provision of Power supply
Supply and recessing/fixing of PVC Conduit pipe 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories, junction box, etc including making chase, plastering/ clamping etc as per technical specifications.
Supply and fixing of PVC Conduit pipe on surface 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories, junction box, etc including clamping etc as per required.
Wiring for circuit / sub main wiring along with earth wire with the following sizes of 3 FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 10sq. mm+ 1 x 10 sq. mm earth wire.The material shall be inspected at manufacturer's premises by RITES and inspection charges shall be borne by the firm.
Carting of Material from Railway site supervisor's depot to site (Only for the material supplied by Railway and returning of Released material from site to store depot of Supervisor)
Supply and recessing/fixing on surface of 6 SWG GI wire conforming to IS: 280/2006 5 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule. 4969453.0
"Supply, Installation, Testing and Commissioning of 1 x 500 KVA 11/0.415 KV, 500 KVA dry type Transformer (OFTC) Compact Substation outdoor duty, plinth mounted type complete with HT Section Comprising of 1 No. 11KV , 21KA 3-way RMU ( 2 No. LBS + 1 No. VCB). LT section- Incommer - ACB 800 A FP Electrical Draw out type 50KA - 1 No, Incomer Change over switch 800 6 Amp, Bus Coupler- ACB 800A FP Electrical Draw out ACB 50KA - 1 No, Outgoing - MCCB 400A-2 No., MCCB 250A FP Manual Fixed Type -3 No, MCCB 160A FP Manual Fixed MCCB - 2 No and MCCB 63A FP Manual Fixed MCCB - 2No, CSS enclosure should be duly type tested for internal Arc Test by CPRI (21 KA for 1 Sec.) and as per CEE/NER Spec No. CEE/CSS/17/June - 2017 with latest Amendment. Details of switchgears and equipment's are mentioned in the attached Explanatory Note. Note :- CSS (excluding foundation) shall be inspected at manufacturer's premises by the RITES. Cost for the inspection shall be borne by the contractor."
Supply, Installation, Testing and Commissioning of Earthing with pipe 4.5 meter long 7 and 40 mm dia with masonry enclosure on the top with RCC Cover including earth connection to equipment with 4 mm dia G.I. wire in 15 mm dia G.I. pipe and using salt and charcoal for pipe earth electrode as per drawing L/16/STD/86 as enclosed as per IS 3043/1987 (latest Version).
SSupply and installation of Maintenance free chemical Gel Earthing with copper 8 bonded steel Rod of 3 Meter Long 17 mm dia copper bonding thickness 250 microns along with SS Clamp and 50 Kg of TERRAGRIP grounding Minerals with Polyplastic earth pit chamber size top dia 254 mm. Bottom dia 330 mm and 260 mm height.
Laying of L. T. Cable of required size in open/air/along wall/ along pole with clamping arrangement conforming to IS:1255/1983 (Latest Version). (Cable will be supplied by Railway)
Laying of 1 No. XLPE insulated and PVC sheathed power cable of grade 1.1 KV size 3½/4 core size exceeding 25 sq mm but not exceeding 400/120 Sq mm Alluminium conductor cable direct in ground including excavation, sand cushioning, protective covering and refilling the trench 10 etc. as required. Cable laying should be as per IS-1255/1983 with latest ammendments. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Laying and Fixing of one No. Additional PVC/XLPE Insulated PVC sheathed aluminium conductor L.T. power cable 3½/4 core of grade 1.1 KV of size exceeding 25 sq mm but not exceeding 400/120 Sq. mm in ground in the same trench in one tier horizontal formation including 11 excavation, sand cushioning, protective covering and refilling the trench etc. as required. Cable laying should be as per IS-1255/1983 with latest ammendments. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second- class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Supply, Installation, Testing and Commissioning of Busbar Chamber System 100 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout 12 stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Supply, installation, testing and commissioning of Gang operating air break off load diconnecting switch (GOS) 11 KV 400 Ampere complete with drop out fuses, 03 insulator triple pole each pole consist of galvanized steel base HT insulator as per BIS non ferous knife and spring loaded 13 contact arcing horn of adequate section to break magnatisening current of the transformer, horizental GI shaft/pipe of adequate length for phase seperator, adequate length for operation from ground level and operating handle complete with locking arrangement in both OFF & ON position. All ferous part heavily tinned to with stand weather. Fuse shall be conforming to IS - 9385 part I/1979, GOS shall be conforming to IS - 9921 Part - I/1981 & 9921 Part - III/1982.
Supply, fixing and commissioning of H.T. Pin insulator for the use on 11 KV HT overhead line complete with G.I. Spindle and fixing nut confirming to IS : 731/1973 (latest version)
Supply, Installation, Testing and Commissioning of Earthing with 600x600x3 mm thick copper plate earth electrode as per IS: 3043/1987 (Latest version), to achieve earth resistance less than one ohm, including construction of masonry enclosure with RCC cover on top, watering pipe, connections from earth plate to top with 40x6 mm copper strip in 50 mm dia GI pipe class "B", provision of earth plate as per drawing and technical specification.
Supply and making outdoor end termination with heat shrinkable jointing kit 16 conforming to IS: 13573/1992 (Latest version) complete with all accessories including aluminium lugs suitable for 3 core 120 Sq. mm HT XLPE aluminium conductor cable of 11 KV (Earthed) grade complete in all respect as required.
Supply and making indoor end termination with heat shrinkable jointing kit 17 conforming to IS: 13573/1992 (Latest version) complete with all accessories including aluminium lugs suitable for 3 core 120 Sq. mm HT XLPE aluminium conductor cable of 11 KV (Earthed) grade complete in all respect as required.
Supply, installation, testing and commissioning of metal oxide lightning arrestor 18 without gaps type conforming to IS - 3070 : Part - III/ 1993 suitable for protecting 11 KV installation including connection with earth pit by 25 mm x 6 mm GI strip and with overhead by ACSR conductor.
Laying of 1 No. 11 KV (E) XLPE insulated armoured Aluminium conductor 3 core 120 Sq. mm cable conforming to IS:7098 (Pt.II) (Latest version) in ground in single trench in one tier hirizontal formation at depth of not less than 1 meter below ground level including excavation, sand 19 cushioning of 80 mm thick all-round etc. protective covering with bricks on side & top, refilling the trench as per technical specification including testing and commissioning. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Laying of 1 No. additional 11 KV (E) XLPE insulated armoured Aluminium conductor 3 core 120 Sq. mm cable conforming to IS:7098 (Pt.II) (Latest version) in ground in the same above trench in one tier hirizontal formation at depth of not less than 1 meter below ground level including 20 excavation, sand cushioning of 80 mm thick all-round etc. protective covering with bricks on side & top, refilling the trench as per technical specification including testing and commissioning. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Supply and Fabrication and Erection of MS Channel different size like 100 x 50 x 6 mm/ 75 x 40 x 6/50x50x6 mm conforming to IS: 808 / 1989 (Latest Version) with clamp, nut bolt etc. complete in all respect as required at site.
Supply, Fabrication and Erection of angle iron 35 x 35 x 5 mm / 40 x 40 x 6 mm / 50x 22 50 x 6 mm conforming to IS: 808/1989 (Latest Version)/M.S. Plate for making structure/ bracket as supporting arrangement for any equiment complete with clamp, nut bolt etc. complete in all respect as per site requirement.
Supplying, fabrication, installing, fixing of MS sheet junction box (outdoor type) size 450x450x200 mm made of 1.6 mm thick M.S. sheet having lockable cover duly painted with gray 23 paint over red oxide primer duly naming 240/415 volts with red paint complete with 3 phase aluminium bus-bar one for neutral with Al. strips 40x10 mm fixed with bus-bar insulators including suitable size of cable gland in bottom side for incoming & outgoing cable and including double earthing stud complete in all respect.
Cutting of CC work of Platform/Road for laying of cable and supply of Cement and sand for repairing of the CC work of platform/Road as per the directive of site in charge complete in all respect.
Supply & Laying of Hot Dip Galvanized Iron Strip of size 25x6 mm /40x6 mm in ground below 0.30 Mtr./ in floor below 0.05 Mtr. from pit to equipment and connection as required and as per direction of site in-charge.
Supply and Laying of G.I. Pipe 100 mm dia. class B ISI marked under road/rail clamping with erected pole or wall as per technical specification for passing cable of different size.
Supply & Laying of 100 mm dia C. I. Pipe (Spun pipe) conforming to IS 1536/2001 with latest amendment class LA & ISI Marked
Cement Concrete Foundation, ratio 1:2:4 with 20 mm and down graded stone aggregate and coarse sand as per site requirement.
Supply of barbed wire GI 12/12 and making anti climbing device on bracing on pole etc. up to suitable height of safety complete in all respect.
Supply and provision of rubberized matting of size 2 Meter x 1 Meter x ¼ inches conforming to IS:15652/2006 for insulation purpose in front of HT/LT Panel.
Supply and Fixing of fire bucket (filled with sand) fitted in proper stand with shed cover, hook and locking arrangement at suitable place decided by site in charge.
Manufacturing, Supply, Erection, Testing and Commissioning of Feeder Pillar equipped with three phase & Neutral bus bar aluminium capable for 400 Amp capacity for each 32 phase and neutral. Feeder panel box shall be made with 1.6 mm CRCA sheet duly painted size 1000 mm height x 600 mm width x 350 mm depth with both side hinged door along with locking arrangement and feeder pillar to be grouted on ground with help of four No. mounting angle of size 50x50x6 mm of length 500 mm above ground the cost should also be include the cost of end cable termination with proper size cable lugs & cable glands.
Excavation of trenchless track by horizontal direct drilling (HDD) method under 33 Railway track/busy road etc. at a depth of minimum 120 CM below ground level as per direction of site engineer incharge along with Supply and Laying of HDPE Pipe of 150/160 mm inner dia confirming to relevant IS in HDD portion. (HDPE Pipe shall be supplied by Contractor)
Supply and Fixing of Hot Dip galvanized ladder type cable tray 300 mm width and 100 mm height made with 12 SWG Sheet.
Supply and Fixing of Coupler plate with hardware for 100 mm Height Hot Dip galvanized/powder coated type trays.
Supply, Installation, Testing and Commissioning of 100 KVAr rated capacity Automatic Power Factor Correction Panel conforming to IS: 8623 - 1993, IEC: 61921/IS: 16636-2017, Rated 36 Voltage 415 VAC, 3 phase, 50 Hz, Delta Connection and housed in elegant structure with IP 42 degree of protection, fabricated from minimum 1.6 mm thick CRCA sheet with anti-corrosive coating and including making suitable plinth for above APFC Panel. The material shall be inspected at manufacturer's premises by RITES and inspection charges shall be borne by the firm.
Supply, Installation, Testing and Commissioning of 7 Mt. High Hot dip galvanized octagonal pole with longitudinal seam weld throughout the length with bottom 130 mm across face, 37 Top 70 mm across face made of 3 mm thick High Tensile plate and 220 mm x 220 mm x 12 mm base plate complete with one arm of 500 mm for fitting installation and 04 No. M20 (EN 8 Gr) x 700 mm long J type foundation bolt set complete in all respect with RCC foundation as per attached drawing.
Supply of Electrician Fitter tool Kit comprising of Double open end spanner set 6x7 to 30x32 mm - 12 No., Bihexagon deep offset ring spanner set 6x7 to 30x32 mm - 12 No., Adhustable Wrenches 66s-150, 66s-200, 66s-250 mm - 03 No., Water Pump Plier 55-10 - 1 No., Stillson pipe wrench 115-10 - 1 No., Grip Plier 266-10 - 1 No., 12.5 mm square drive, reversible ratchet - speed brace sliding handle extension bars 75, 250 mm iniversal joint -Swivel handle-L-Handle - 09 No., Torque wrench 50 lbs ft - 01 No., Set of allen key 2 mm to 12 mm - 01 No., Engineer's Screw driver 5x100, 6x125, 8x150, 8x200, 10x200 - 5 No., Electrician Screw drivers 4x100, 5x125, 5x200 mm - 03 No., Philips screw drivers tip dimension 1-5x75, 2-6x100 - 02 No., C-clamp 55 mm - 01 No., Combination Plier 351a-6 - 01 No., Diagonal cutting plier 346-160 mm - 01 No., Hacksaw frame 300 mm - 01 No., Cold Chisel 100-150-200 mm - 03 No., Round File II cut 250 mm - 01 No., Half Round File II cut 250 mm - 01 No., Mill file II cut 250 mm - 01 No., Pincer 200 mm - 01 No., Ball pein hammers 250-500 gms - 02 No., Centre punch 100 mm - 01 No. Set feeler gauge 10 blade (in mm) - 01 No., Stainless scale 150 mm - 01 No., Measuring tape 2 mtrs Steel - 01 No., Wire brush - 01 No., 38 Oil can - 01 No. & Tool Chest - 01 No.
Supply and Erection of swaged steel tubular pole conforming to IS: 2713 Part I to 39 III/1980 (Latest Version) complete with base plate, earthing bolt, digging of pit in ground, making foundation up to 300 mm above ground level as per Drawing, Erection of pole vertically, earthing, painting as per Technical Specification of size 11.0 Mtr. With Bottom 5.60 Mt., Middle & Top 2.70 Mt. Approximate weight 227 Kg. (Designation 410 - SP 55)
Supply of Double wall corrugated (DWC) pipes for under ground power cable 40 protection with IS:14930 Part - II mark on duly printed at every one meter interval along with the socket coupler with IP 67 protecting for coupling where ever required. The DWC pipe shall be rodent proof and fire resistant and size of outer dia 90 mm and inner dia 76 mm.
Excavation of cable trench of 110 Cm Depth and 30 Cm wide in all kinds of soil and its refilling with the same excavated soft soil.
Laying of DWC pipe (90/76 mm) with socket coupler in trenches as per requirement.
Supply and Fixing of Hot Dip galvanized perforated type cable tray 100 mm width and 50 mm height made with 14 SWG Sheet.
Supply and fixing of Hot Dip galvanized type cover plate for 100 mm width cable tray with 18 SWG Sheet.
Supply and Fixing of Coupler plate with hardware for 50 mm Height Hot Dip galvanized/powder coated type trays
SITC of End termination of 4 core 70 -150sq mm XLPE Insulated 11 KV ( E) aluminium conductor cable with heat sink able type indoor/outdoor cable box confirming to relevant IS (latest version ) as per technical specification with supply of material including testing & commissioning.
SITC of End termination of 4 core 185 -300sq mm XLPE Insulated 11 KV ( E) 47 aluminium conductor cable with heat sink able type indoor/outdoor cable box confirming to relevant IS (latest version ) as per technical specification with supply of material including testing & commissioning.
SITC of End termination of 4 core 400sq mm XLPE Insulated 11 KV ( E) aluminium conductor cable with heat sink able type indoor/outdoor cable box confirming to relevant IS (latest version ) as per technical specification with supply of material including testing & commissioning.
Supply, Installation, Testing and Commissioning of Straight Through Joint with heat 49 shrinkable staight through jointing kit conforming to IS: 13573-1/2011 (Latest version) complete with all accessories including alluminium lugs suitable for 4 core 70 - 150 Sq. mm L T XLPE alluminium conductor cable of 1.1 KV grade complete in all respect as required.
Supply, Installation, Testing and Commissioning of Straight Through Joint with heat 50 shrinkable straight through jointing kit conforming to IS: 13573-1/2011 (Latest version) complete with all accessories including alluminium lugs suitable for 4 core 185 - 300 Sq. mm L T XLPE alluminium conductor cable of 1.1 KV grade complete in all respect as required.
Supply, Installation, Testing and Commissioning of Straight Through Joint with heat shrinkable staight through jointing kit conforming to IS: 13573-1/2011 (Latest version) complete with all accessories including alluminium lugs suitable for 4 core 400 Sq. mm L T XLPE alluminium conductor cable of 1.1 KV grade complete in all respect as required.
Supply, Installation, Testing & Commissioning of MCCB 32/63 Amps, 4 pole breaking 52 capacity 25 KA at 415 V,50 Hz, thermal release range 25-32A/50-63 A, Ics = 100% Icu including hard wares and insulators as required along with sheet steel enclosure duly painted complete in all respect.
Supply and fixing of 1.6 mm thick mild steel sheet Danger plate 11000 Volts AC supply of Size 200 mm x 250 mm confirming to IS:2551/1982 with latest version comlete in all respect.
Supply, Installation, Testing and Commissioning of Busbar Chamber System 400 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout 54 stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Supply installation testing & commissioning of MCCB 400 Amps , 4 pole breaking 55 capacity 35/36 KA at 415 V,50 Hz, thermal release range 320-400 A, Adjustable short circuit setting 6-10, Ics = 100% Icu including hard wares and insulators as required as per CEE'S Specification No. CEE/Spec./LT-Panel with 400Amp. ACB/06 December - 2008 or latest.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC-APRIL-2022.pdf
ATTACHMENT
BGFormat-NEW_merged.pdf
ATTACHMENT
ACS 1 10
ATTACHMENT
GCCACS11_compressed.pdf
ATTACHMENT
EARTHING.pdf
ATTACHMENT
LTPanel.pdf
ATTACHMENT
POLE_1.pdf