| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.4 LAccepted-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹20.0 L+₹1.0 L (5.45%)Rejected-Finance 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Being not lowest |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
12 Nov 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Major A R Thakkar
GE (P) Dappar
Repair to flame proof fittings and allied maint works in Technical area at Mil Stn Dappar under GE (P) Dappar
2022_MES_557921_2
GE (P) DPR-26/2022-23
Open Tender
Civil Works
Works
180 days
GE (P) Dappar
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (P) Dappar
₹40,000
Yes
16 Dec 2022
29 Oct 2022
14 Nov 2022
29 Oct 2022
12 Nov 2022
29 Oct 2022
29 Oct 2022 - 29 Oct 2022
Amount
Taking down carefully Copper/aluminium point wiring on wooden batten /pvc conduit /Pvc casing and capping (light/Socket/Power) complete including (Fittings such as switches, ceiling roses, pendants, regulators, sockets electric energy meters, light fittings, etc) making good distrubed surfaces of walls. Floors etc to match with the existing including disconnection of ceiling/exhaust fan connection, complete all as specifed and directed by Engr-in charge.
S & F Flame proof point wiring with single core PVC insulated and unsheathed 1100 volt grade (FRLSH) electric cable with multi stranded copper conductor of size 1.5 Sqmm phase and neutral drawn in and including ERW rigid steel stove enameled black conduit heavy duty ISI marked of size 20mm dia concealed type including all flame proof conduct fittings and accessories such as tees junction boxes, bends duly tested by CMRI Dhanbad suitable for Six light controlled by one flame proof rotary switch SP one way and including drawing continuous earth wire PVC insulated unsheathed 1100V grade cable with stranded copper conductor of size 1.5 Sqmm and connected to earth dolly complete conforming to IS-694 all as specified and directed by Engrs-in-Charge.
S & F Flame proof sub main wiring with two single core 6 sqmm multistandard copper conductor cable (FRLSH), PVC insulated cable 1100 volts grade and 6 Sqmm as continious earthing single core copper continious earthign drawing and including extra including ERW rigid steel stove enameled black conduit heavy duty ISI marked of size 40 mm dia concealed type including all flame proof conduct fittings all as specified and directed by Engrs-in-Charge.
S & F Flame proof point wiring with single core PVC insulated and unsheathed 1100 volt grade (FRLSH) electric cable with multi stranded copper conductor of size 1.5 Sqmm phase and neutral drawn in and including ERW rigid steel stove enameled black conduit heavy duty ISI marked of size 20mm dia concealed type including all flame proof conduct fittings and accessories such as tees junction boxes, bends duly tested by CMRI Dhanbad suitable for two light controlled by one flame proof rotary switch SP one way and including drawing continuous earth wire PVC insulated unsheathed 1100V grade cable with stranded copper conductor of size 1.5 Sqmm and connected to earth dolly complete conforming to IS-694 all as specified and directed by Engrs-in-Charge.
Supply and fixing totally enclosed flame proof/weather proof direct entry type rotary switch single pole on & OFF rotary motion switch in cast aluminum alloy LM-6 enclosure epoxy powder coated single pole 230Volts 16 Amps, AC ON/OFF switch operated externally by Knob having 02 Nos of M-20 cable entries, earthing terminals suitable for mounting on Wall/Steel structure etc duly tested & certified by CMRI-Dhanbad. Make : Shyaam/ Sudhir
Supply and fixing totally enclosed flame proof/weather proof LED fixture 2x20 complete watts 1200mm with aluminium extruded and aluminium heat sink, System Lumen Efficacy ≥100 Lm/W operating Voltage between 140-270Vac , Power Factor more than 0.90%, LED Driving Current < 70% of rated maximum forward current,THD less than 20%, CRI more than 80%, Luminaire intergal driver with 2KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), Driver Certiifcation IEC64347-2-13 IS(15885), Over all electrical efficency more than 90%, Driver electrical efficiency will be > 85%, with 2 year warranty all as specified and directed. Make : Shyaam, Crompton/ Sudhir/ Bajaj
Supply and fixing Flame proof 12 way distribution board for mounting MCBs/RCBO's ELCB etc. as per IS specification and CMRI approved of factory made fabricated out of cast aluminium alloy LM-06 gray appoxy powder coated finish, fitted with DIN Channel neutral link, Earth links and 200 Amps rated bus bar. The DB shall be having with IP-65 protection. The DBs shall also be consisting and including the following:- (a) SPN 230 volts AC 50 Hz 40 Amps - 01 Nos (b) MCB single pole 240 volts AC 50 Hz 10 Amps - 10 Nos. Make:- Sudir, shyaam, Baliga
Supply and Fix flame proof flexible metalic hose conduit 20 mm dia all as specified and directed.
Supply and fixing Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth complete all as shown as specified and directed.
M&L earthing complete with and including galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 m deep below ground level with top edge of earth plate at a depth of not less than 1.5 m below ground level, connected to galvanised iton steel earth lead wire 4 mm dia by means of nuts, bolts, checknuts and washers made out of galvanised iron, 15 mm bore (light grade) GI pipe for protection of earthing lead, 20 mm bore (light grade) GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thick RCC M-25(Design mix) reinforced with XPM (weight not less than 3 kg/sq m) pit cover, C.I frame, charcoal and comman salt filling in alternate layers, complete all as shown and specified in electrical plate No. 5 of SI Part-I.
M&L earthing complete with and including but using copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 m deep below ground level with top edge of earth plate at a depth of not less than 1.5 m below ground level, connected to copper earth lead wire 4 mm dia by means of nuts, bolts, checknuts and washers made out of galvanised iron, 15 mm bore (light grade) GI pipe for protection of earthing lead, 20 mm bore (light grade) GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thick RCC M-25(Design mix) reinforced with XPM (weight not less than 3 kg/sq m) pit cover, C.I frame, charcoal and comman salt filling in alternate layers, complete all as shown and specified in electrical plate No. 5 of SI Part-I.
S & F in replacement of 100W LED flame Proof Flood Light with System Lumen Efficacy≥100 Lm/W operating Voltage between 140-270Vac, Driver will have cut off at > 300 Vac, Power Factor more than 0.95%, LED CCT 5665±355K as per ANSI BIN, LED Driving Current < 70% of rated maximum forward current, Luminaire intergal driver with 5KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), Driver Certiifcation IEC64347-2-13 IS(15885), Driver should be concealed under IP66,Over all electrical efficency more than 90%, Driver electrical efficiency will be > 85% connecting with PVC copper cable of size 3x1 sqmm as per IS 10322 at Least 2 Year on site warranty without any condition including taking down of old light fitting safely and removing from site complete all as specified and directed. Make : Philips, Crompton/ Sudhir/ Bajaj
M&L in replacement of HPMV lamp 250 watt for existing flame proof light fitting of existing size fitted at a hight of 30 feet and above complete all as specified and directed.
M&L in replacement of copper balast, 220-240V for existing HPMV/MH light fitting, fitted at a hight of 30 feet and above complete all as specified and directed.
M&L for ignitor, 220-240V for existing HPMV/MH light fitting, fitted at a hight of 30 feet and above complete all as specified and directed.
M&L for Spiral base type LED Bullb 14W, 220-240 V (E-27), 1300 Lumen, white above complete all as specified and directed.
M&L for flame proof rotary switch top as sample above complete all as specified and directed.
Supply and fixing of static Discharge Handles made out of 20mm dia, 500mm length electrolytic copper solid rod fixed on wall with Dough moulding compound (DMC) insulator, brass spacers and connected to the static discharge conductor/ 20x 3 mm copper strip with brazing all as specified and directed.
S&F copper earth strip of size 25 x 3 mm buried in ground or fixed on wall connecting at ends, nuts and bults, jointing alongwith suitable size PVC insulators as sample etc complete all as specified and directed.
Demolition and taking out old damaged earth pit PCC chamber with cover and M& L for preparation of new PCC chamber in cement concrete 1:2:4 type B1 cover duly reinforced with XPM (weight not less than 4 Kg/sqm and CI frame and other provisions all as shown electrical plate No-3 of SSR-2009 Part-I complete all as specified and directed.
S&F GI strip of size 32x 6 mm buried in ground or fixed on wall connecting at ends, jointing alongwith suitable size PVC insulator etc complete all as specified and directed.
Repair to existing earthing and earth strip of any size includig replacement of existing nuts, bolts, checknuts and washers with new items as specified and directed
M/S Sonu Traders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .