Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.7 LAccepted-AOC | L1 | Accepted-AOC Being L1 accepted | |
| 2 | L2₹22.5 L+₹18,199 (0.82%)Rejected-Finance 164 197 NEWAJPUR DASAULI KURSI ROAD LUCKNOW UTTAR PRADESH 226026 | LUCKNOW | UTTAR PRADESH | 226026 | L2 | Rejected-Finance In order but L2 | |
| 3 | L3₹24.7 L+₹2.4 L (10.7%)Rejected-Finance | L3 | Rejected-Finance In order but L3 | |
| 4 | L4₹26.3 L+₹4.0 L (18.1%)Rejected-Finance | L4 | Rejected-Finance In order but L4 | |
| 5 | L5₹28.8 L+₹6.6 L (29.5%)Rejected-Finance 289 KASERU KHERA MAWANA ROAD MEERUT 250001 U P | MEERUT | UTTAR PRADESH | 250001 | L5 | Rejected-Finance In order but L5 |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
27 Apr 2024, 6:00 pmClosed
GE (U) Meerut Cantt
Roorkee road Meerut Cantt
REPAIR / MAINT OF VT SUBMERCIBLE PUMPS AND MOTORS, PANELS AND CONNECTED WORK AT VARIOUS WATER SUPPLY INSTALLATIONS (NORTH AREA) UNDER AGE E/M (WS) UNDER GE (U) E/M MEERUT CANTT
2024_MES_647707_1
8576/E8
Open Tender
Civil Works - Water Works
Item Rate
180 days
Meerut
Please refer Tender documents.
11 documents required · 11 mandatory
₹500
GE (U) Meerut Cantt
₹80,000
Yes
6 Jul 2024
23 Mar 2024
29 Apr 2024
23 Mar 2024
27 Apr 2024
13 Apr 2024
Amount
Supplying, laying or fixing, jointing and testing LT PVC insulated and PVC sheathed Three core flat cable , ISI-1554 marked , with copper conductor , heavy duty 1100 Volts grade of 25 sqmm ,complete including taking down of existing unserviceable cable all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc.complete all as specified and directed.
Supply and fixing in repair MCCB, 4 pole, 160 Amps, Icu=35KA, 415 volts, 50 hz, AC , with fixed thermal and magnetic release duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, for 50 HP motor complete with taking down old unserviceable all as specified and directed.
Supply and fixing in repair MCCB, 4 pole, 200 Amps, Icu=35KA, 415 volts, 50 hz, AC , with fixed thermal magnetic release duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, for 75 HP motor complete with taking down old unserviceable all as specified and directed.
S&F in repair to replacement of Aluminium thimble suitable for cable of size 50 Sqmm, 3.5 core complete all as spercified and directed.
S&F in repairs Copper thimble suitable for cable of size upto 35 Sqmm, 3.5 core complete all as spercified and directed.
Supplying, fixing and testing off load changeover switch with sheet metal enclosure of capacity 100 Amps, 415V, 4 pole, side handle operated , 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers including making connections and testing including taking out old unsv complete all as specified and directed .
Supplying, fixing and testing off load changeover switch with sheet metal enclosure of capacity 200 Amps, 415V, 4 pole, side handle operated , 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers including making connections and testing including taking out old unsv complete all as specified and directed .
Supplying, fixing and testing off load changeover switch with sheet metal enclosure of capacity 300 Amps, 415V, 4 pole, side handle operated , 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers including making connections and testing including taking out old unsv complete all as specified and directed .
Dismantiling electric motor carefully from foundation after disconnecting the electric connections from panel board manually or mechanically and transporting both way to work shop and back, installation, refixing, reconnecting at site where directed after necessary repairs carried out and testing complete as directed by Engr-in-Charge for Electric motor 22.5 HP, 3 phase, 400/ 415 volts, 50 Hz of any make / type. Note:- Repairs and Parts Renewed shall be measured and paid for separately.Quoted rates deemed to include transportation charges including loading and unloading and labour charges for dismantling and refixing complete.
Dismantiling electric motor carefully from foundation after disconnecting the electric connections from panel board manually or mechanically and transporting both way to work shop and back, installation, refixing, reconnecting at site where directed after necessary repairs carried out and testing complete as directed by Engr-in-Charge for Electric motor 50 HP, 3 phase, 400/ 415 volts, 50 Hz of any make / type. Note:- Repairs and Parts Renewed shall be measured and paid for separately.Quoted rates deemed to include transportation charges including loading and unloading and labour charges for dismantling and refixing complete.
Dismantiling electric motor carefully from foundation after disconnecting the electric connections from panel board manually or mechanically and transporting both way to work shop and back, installation, refixing, reconnecting at site where directed after necessary repairs carried out and testing complete as directed by Engr-in-Charge for Electric motor 75 HP, 3 phase, 400/ 415 volts, 50 Hz of any make / type. Note:- Repairs and Parts Renewed shall be measured and paid for separately.Quoted rates deemed to include transportation charges including loading and unloading and labour charges for dismantling and refixing complete.
Assessing the repairs to be carried out to the motors after dismantling and carrying out the neccessary repairs to motors by opening the electric motor carefully removing all burnt/wornout coils cleaning the slots and rewinding with super enamelled copper wire of existing size including varnishing two coats, drying and reassembling the electric motor at site and testing the smooth running of the motor on full load for 08 hours continuously for Electric motor of capacity 75 HP 3 phase, 400/ 415 volts, 50 Hz of any size /shape and make. Note: Payment of bearing shall be measured and paid separatly under relevant items .
Assessing the repairs to be carried out to the motors after dismantling and carrying out the neccessary repairs to motors by opening the electric motor carefully removing all burnt/wornout coils cleaning the slots and rewinding with super enamelled copper wire of existing size including varnishing two coats, drying and reassembling the electric motor at site and testing the smooth running of the motor on full load for 08 hours continuously for Electric motor of capacity 50 to 60 HP 3 phase, 400/ 415 volts, 50 Hz of any size /shape and make. Note: Payment of bearing shall be measured and paid separatly under relevant items .
Assessing the repairs to be carried out to the motors after dismantling and carrying out the neccessary repairs to motors by opening the electric motor carefully removing all burnt/wornout coils cleaning the slots and rewinding with super enamelled copper wire of existing size including varnishing two coats, drying and reassembling the electric motor at site and testing the smooth running of the motor on full load for 08 hours continuously for Electric motor of capacity 20 to 22.5 HP 3 phase, 400/ 415 volts, 50 Hz of any size /shape and make. Note: Payment of bearing shall be measured and paid separatly under relevant items .
Lifting of electric motor 22.5 HP to 75 HP capacity from existing position after disconnection of all electrical connection for renewal of U/S bearing and applying grease after removal of old grease and re-installing at site where directed after refilling new grease and reconnecting all electrical connection and testing complete. Note : (a) Necessary payment for bearing shall be measured and paid separately under relevant items if required at site. (b) Quoted rate deemed to include cost of grease as required at site. (c) The contractor shall lift the motors as directed by the dept for normal servicing even if no repairs are reqd for the motor.
Supply only Thrust bearing No. 7220 motor capacity 50 HP complete all as specified and directed
Supply only Thrust bearing No. 7316 motor capacity 75 HP complete all as specified and directed
Supply only Thrust bearing No. 9324 motor capacity 75 HP complete all as specified and directed
Supply only Thrust bearing No. 6312 motor capacity 22.5 HP complete all as specified and directed
Supply only Thrust bearing No. 6316 motor capacity 50 HP complete all as specified and directed
Supply only Thrust bearing No. 6311 motor capacity 50 HP complete all as specified and directed
Supply only Thrust bearing No. 6313 motor capacity 22.5 HP complete all as specified and directed
Supply only Thrust bearing No. 6309 motor capacity 22.5 HP complete all as specified and directed
Renewal of ball bearing sheet suitable for motor of capacity 22.5 HP to 75 HP motor including lathe work as required at site complete all as specified and directed.
Lifting/Dismantling carefully turbine pump set bowl assembly of any make, capacity upto 50000 GPH and size complete with out damaging any parts of the pump and setting aside in pump house for ascertaining the serviceability of existing parts with the following :- (a) Through dismantling and cleaning of complete bowl assembly items such as CI bowls, impeller, lock collets, bowl bush, suction and discharge case with GM bush including pump shaft. (b) Cleaning of all rotary and stationary parts of pump bowl assembly and making them for their satisfactory run. (c) Re-assembling the complete bowl assembly pump with all existing serviceable parts and renew the worn out unserviceable parts including S & F gasket ,lathe work and balancing of assembly others small nature of indispensable items as required for repairing. Note :- Parts renewed shall be measured and paid for separately under respective item of Schedule 'A'/BoQ at supplied only rates. Cost of labour for fixing of new parts shall be deemed to include in the rate quoted by tenderer.
Replacement of old damaged CI centrifugally cast bowl assembly complete with gun metal bush ( make as per original manufacturer) for pump of capacity up to 50000 GPH of vertical turbine pump .
Replacement of old damaged GM impeller ( make as per original manufacturer) for vertical turbine pump of capacity up to 50000 GPH of any type.
Replacement of old damagedStainless steel non magnetic pump shaft 25 to 32 mm ( make as per original manufacturer) dia suitable for 6 to 9 stage pumps (Bowl assembly) as directed .
Replacement of old damaged M.S. line shaft (bright) steel 25 to 32 mm dia 10 Ft long with MS coupling and non magnetic stainless steel sleeve ( make as per original manufacturer) all as specified and directed.
Replacement of old damaged Shaft coupling / sleeve of high carbon steel for 25 mm to 32 mm dia lineshaft (make as per original manufacturer) all aspecified and directed.
Replacement of old damaged GM Bush for suction case of VT pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged CI guide spider heavy duty with rubber bush and check nut suitable for 25 to 32 mm dia lineshaft of 150 mm bore pipe ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged CI guide spider heavy duty with rubber bush and check nut suitable for 25 to 32 mm dia lineshaft of 200 mm bore pipe ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Rubber packing for discharge head upto 200 mm bore complete all as specified ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Rubber bush for guide spider for 25 to 32 mm dia lineshaft ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Stainless Steel top shaft not exceeding 32 mm dia and 3 mtr long, duly threaded both ends and made suitable slot for fixing the stainless steel key adjusting nut & lock washer ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged CI Centrifugally cast suction case with GM Bush (make as per original manufacturer) all aspecified and directed.
Replacement of old damaged CI Centrifugally cast discharge case with GM Bush ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Mild steel cold drawn ERW column pipe 3.00 M long, wall thickness not less than 7.2 mm thick, 150 mm bore, both ends flanged with Mild steel column coupling 12 mm thick including welding, flanged joint on both ends complete all as specified and directed by Engr-in-Charge
Replacement of old damaged Mild steel cold drawn ERW column pipe 3.00 M long, wall thickness not less than 7.2 mm thick, 200 mm bore, both ends flanged with Mild steel column coupling 12 mm thick including welding, flanged joint on both ends complete all as specified and directed by Engr-in-Charge
Replacement of old damaged ratchet assembly complete with ratchet plate, ratchet balls hexagonal bolts etc suitable for up to 75 HP electric motor and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Ratchet plate suitable upto 75 HP VT motor and vertical turbine pump ( make as per original manufacturer) all aspecified and directed..
Replacement of old damagedGM neck ring suitable for 100mm/150mm/200m dia VT pump and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged PVC rubber Gasket 3 mm thick suitable upto 200 mm bore flanged joints .
Replacement of old damaged Rubber bowl bush suitable for VT pump set and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Intermediate bowl bush GM suitable for VT pump set and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged GM Impeller lock collect suitable for VT pump set and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged CI fitting box (Gland box) of suitable type & shape for VT Pump and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Replacement of old damaged Mild steel full threaded bolts of suitable size having hexagonal head with one 3 mm thick washer and nut suitable for jointing 100/150/200 mm bore flanged joints complete all as specified.
Replacement of old damaged Gun Metal split gland of any size & shape with G I clamp suitable for gland box of VT pump and vertical turbine pump ( make as per original manufacturer) all aspecified and directed.
Lowering of turbine pump set any type and capacity upto 50000 GPH re-assembling of all accessories and column pipe after cleaning manually including fixing of motor in existing position making all Electrical & water supply connections and adjustment of pump load etc and testing of pump and motor after installation all as directed by Engr-in-Charge.
Cutting, facing of existing mild steel cold drawn ERW column pipe upto 200 mm dia to desired length and re-threading up to 80 mm run to suit existing coupling complete all as directed. Note :- Rate quoted by tenderer shall be deemed to include all transportation charges from site to work shop and back incl loading/unloading.
Cutting, facing of existing mild steel lineshaft up to 32 mm dia to desired length and re-threading up to 80 mm run as directed. Note :- Rate quoted by tenderer shall be deemed to include all transportation charges from site to work shop and back incl loading/unloading.
Cutting existing MS/BS/SS top shaft of size upto 32 mm dia making slot for key and rethreading both ends for required length to suit the coupling and load adjusting shaft nut all as directed by EIC.
Taking out rusted pump foundation MS bolt from cement concrete foundation base and fixing by providing new mild steel full threaded bolt of 20 mm dia not exc.300 mm long with proper cement concrete foundation (1:2:4) type B-1 using 20mm graded crushed stone aggregate and makeing the surface smooth to match with existing surface complete all as directed.
Renewal of Heavy duty terminal plate made of bakelite suitable for electric motor of capacity 30/40/50/75 HP with brass nuts of suitable size best quality as approved by GE complete all as specified and directed.
Renewal of Terminal plate cover made of CI for fixing over the terminal plate with cover for 30/40/50/ HP electric motor best quality as approved by GE complete all as specified and directed.
Labour for lifting of submersible pump along with flanged column pipe, submersible cable, safety rope etc from the existing bore well by using suitable T&P etc after disconnecting submersible cable from starter making necessary repairs by opening and renewal of parts as required including transportation to market and back for repair complete all as specified & directed for 22.5HP to 41 HP capacity pumpset. Note: Parts Renewed and rewinding of motor shall be measured and paid separately.
Labour for lifting of submersible pump along with flanged column pipe, submersible cable, safety rope etc from the existing bore well by using suitable T&P etc after disconnecting submersible cable from starter making necessary repairs by opening and renewal of parts as required including transportation complete all as specified & directed for 2HP to 7.5 HP capacity pumpset. Note: Parts Renewed and rewinding of motor shall be measured and paid separately at supplied only rates under appropriate item(s) .
Supply only Gunmetal impellers suitable for 22.5 to 41 HP Submersible pump
Supply only Gunmetal bush suitable for 22.5 to 41 HP Submersible pump
Supply only stainless steel sleeve suitable for 22.5 to 41 HP Submersible pump
Supply only 'C' type bushes for impellers suitable for 22.5 to 41 HP Submersible pump
Supply only Bowel case suitable for 22.5 to 41 HP Submersible pump
Supply only stainless steel shaft of standard size complete in all respect suitable for 22.5 to 41 HP Submersible pump
Supply only Gunmetal impellers suitable for 2 to 7.5 HP Submersible pump
Supply only Gunmetal bush suitable for 2 to 7.5 HP Submersible pump
Supply only stain less steel sleeve suitable for 2 to 7.5 HP Submersible pump
Supply only 'C' type bushes for impellers suitable for 2 to 7.5 HP Submersible pump
Supply only Bowel case suitable for 2 to 7.5 HP Submersible pump
Supply only stainless steel shaft of standard size complete in all respect suitable for 2 to 7.5 HP Submersible pump
Lowering down of submersible pump set along with connected items such as column pipes ,submersible cable by using suitable T&P and reconnecting all electrical connections,commissioning & testing complete all as specified & directed for 22.5 HP to 41 HP capacity pumpset.
Lowering down of submersible pump set along with connected items such as column pipes ,submersible cable by using suitable T&P and reconnecting all electrical connections,commissioning & testing complete all as specified & directed for 2 HP to 7.5 HP capacity pumpset.
Lifting out and Rewinding of submersible motor electric driven , AC supply with PVC insulated copper wire (ISI marked) as per existing gauge ,including connected works for rewinding .The scope of works includes dismantaling ,removal of old winding wire ,cleaning of slots & rewinding ,reassembling,testing complete all as specified & as directed for 22.5 HP to 41 HP capacity of pump motors. Note: Other parts required for repair will be measued and paid for separately under respective sch item.
Supply only Gunmetal bush for submersible motor suitable for 22.5 to41 HP
Supply only Thurst bearing for submersible motor suitable for 22.5 to 41 HP
Rewinding of submersible motor electric driven , AC supply with PVC insulated copper wire (ISI marked) as per existing gauge ,including connected works for rewinding .The scope of works includes dismantaling ,removal of old wiring wire ,cleaning of slots & rewinding ,reassembling,testing complete all as specified & as directed for 02 HP to 7.5 HP capacity of pump motors. Note: Other parts required for repair will be measued and paid for separately under respective sch item.
Supply only Gunmetal bush for submersible motor suitable for 2 to 7.5 HP
Supply only Thurst bearing for submersible motor suitable for 2 to 7.5 HP
S & F (in repair) Submersible cable flat ,water proof,PVC insulated,PVC sheathed,3 core,16 sqmm,1100 volts grade ,multistranded copper conductor including making water proof cable joint with submersible motor and normal connections through lugs/thimbles into starter panel complete all as specified and directed.
Supply & fix Single/reverse phase preventor for motor protection with by pass arrangements to run the motor in case of emergency with low/high voltage cut off and time delay/relay of 1 to 3 sec.including dismantling/taking out of unserviceable phase preventor of any make and type complete all as specified and directed.
Taking down and S&F Thermal Over load relay of range 65 to 110 Amps (for 3 phase,415 V motor of 75 HP) complete all as specified.
Taking down and S&F Over load relay of range 45 to 75 Amps (for 3 phase,415 V motor of 50 HP) complete all as specified.
Taking down and S&F Thermal Over load relay of range 28 to 36 Amps (for 3 phase,415 V motor of 22.5 HP) complete all as specified.
Supply & Fixing of Power contactor 3 pole above 50 HP upto 75 HP with 415 V/220 V , AC Coil including repair/replacement of wiring complete all as specified.
Supply Power contactor 3 pole upto 50 HP with 415 V/220V , AC Coil including repair/replacement of wiring complete all as specified.
Supply Power contactor 3 pole upto 25 HP with 415 V/220V , AC Coil including repair/replacement of wiring complete all as specified.
Supply only Thermal timer type GT 200, including wiring operating voltage 230/250 Volts, 400/440 Volts, 50 Hz fun 5-18 seconds range complete all as specified.
S&F (in repair) phase sequence changer of any type /make capacity 22.5 HP to 75 HP including renewal of U/S parts and wiring as required to made the sequencer serviceable condition.
Taking down of RYB phase indicator and repair/renewal of RYB phase indicator of any size and type on LT Panel as specified and directed.
Supply of high torque butterfly torque valve of size 150mm dia bore, line pressure up to 15kg/ cmsq with gears and adoptors self lubricating type, wheter proof with manual operated arrangement to open/close the valve complete all as specified and directed.
Repair/replacement of motor gland leakage including replacement of studs, plate, and other assessories/ items all as directed by Engr-in-Charge.
S&F in repair of fully automatic ,3 phase Star delta starter with enclosure suitable for motor upto 50HP capacity including connector & cables required all as directed by Engr-in-Charge.
S&F in repair of fully automatic ,3 phase Star delta starter with enclosure suitable for motor above 50HP upto 75HP capacity including connector & cables required all as directed by Engr-in-Charge.
Repair to phase sequence changer of any type /make capacity 22.5 HP to 75 HP including renewal of U/S parts and wiring as required to made the sequencer serviceable condition.
S&F in repir of Electronic Energy Meter digital type 3 Phase 415V 50 Hz at various pump Houses and direct connected 5/20Amp CT, 10/60Amp CT operated direct reading type meter with indication LCD having accuracy wide voltage fluctuation from -40% to +20% and should give accurate reading under rapid current fluctuation and accurate for balance as well as unbalance load including anti tamper feature complete all as specified and directed.
SIYA ASSOCIATES
CHAUDHARY FURNITURE HOUSE
NITHYA INFRATECH
Shikha Enterprises
M/S JPS Electrical Engineer & Contractor
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .