Provision of Air-Conditioning at 100 Location / Stations / Cabins of Panel Interlocking Station over HWH".
EL-HWH-25-21-3634
EL-HWH-25-21-3634
Open
180 Days
Unknown (Unspecified Location)
₹0
₹7.7 L
19 Jun 2026
19 Jun 2026
26 Jun 2026
A-Provision of Air-Conditioning at 100 Location / Stations / Cabins of
Wiring of AC Machine ( Window / Split ) / Water Cooler point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4 sq.mm, 1100V grade for phase 1 and neutral in PVC conduit / casing along with 1 no. single core, HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) and each switch board comprising with one power unit which includes one double pole MCB, one single phase starter and one 6/16A 3 pin socket and plug with indicating light and all other associated work ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) Above/
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) Above/
Wiring of Mainline by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 3 conductor cable of size 6.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) Above/
Wiring of Mainline by 4 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 10 sq.mm, 1100V grade for 03 phases and 01 neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 5 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) Above/
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition Above/
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition Above/
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) Above/
Supply of SPN DB ( Metal Enclosure with Metal Door ), 10 way, 1Ph, 240V, 50Hz, complete with 6 nos. SP MCB of current rating from 6A to 32A,10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of MCB DP, 40A, 1Ph, 240V, 50 Hz, 10kA with polycarbonate distribution box enclosure (IP-65) with polycarbonate transparent openable window including fixing, connection, testing and commissioning. ( Make of MCB - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) ( Make of Enclosure - Grasp / OBO Bettermann / ABB / Schneider ) Above/
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut-bolts and commissioning of cable ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting with covering of cable through suitabe dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN-10 or higher) along with refilling the trench and make good of surface as its original condition ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable under ground by soil cutting through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN-10 or higher) alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching, laying under road / track through 100 mm dia GI pipe ( medium gauge ) including supply of GI pipe and commi- ssioning of cable including back filling of trench with excavated soil after laying of cable ( Cable will be supplied by Railway ) Above/
Laying of cable underground through 100 mm diameter HDPE pipe by Micro Tunneling cable laying method including supply and jointing of HDPE pipe (PE-100 grade, PN-10 or higher). ( Cable will be supplied by Railway ) Above/
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) Above/
Supply of Maintenance Free Copper Bonded Solid Earthing Rods with 25 kg Earth Enhance Compound with below specifications : a) Certified by CPRI and NABL Accredaited Lab b) 20 ROHS certified c) Low Carbon High Tensile Rod d) Length of Electrode 3000 mm (3 Meter) e) Rod dia 17.2 mm f) Molecular Copper Plating thickness 254 microns as per UL 467 g) Connection terminal size 32 mm x 6 mm with 10 mm hole along with nut bolt and washer including installation, testing and commissioning as per RDSO spec. no. RDSO/SPN/197 ver. 1.0 or latest and conforming to RDSO Drg. No. SDO/RDSO/E&B/001 or latest. ( Make : ABB / VTR / Raychem / Veraizen Earthing / Ennob / True Power Ltd. / OBO Bettermann ) Above/
Supply of Heavy Duty Fiber Reinforced Polymers Pit Cover with below specifications : a) Weight Carrying Capacity 5 Ton b) Lockable arrangement c) Top Dia 162 mm d) Bottom Dia 242 mm e) Height 230 mm f) As per IEC 62561-5 g) M5 Nut Bolts HDG 4.6, 30 mm length with 2 nos. of plain washer h) Tested by NABL Accrediated LAB including installation, testing and commissioning. ( Make : ABB / VTR / Raychem / Veraizen Earthing / Ennob / True Power Ltd. / OBO Bettermann ) Above/
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed ) Above/
Installation, testing and commissioning of 2 TR Split AC machine including outdoor unit with MS angle stand along with necessary power cable and all other accessories. ( Split AC machine will be supplied by Railway ) Above/
Installation, testing and commissioning of 1.5 TR Split AC machine including outdoor unit with MS angle stand along with necessary power cable and all other accessories. ( Split AC machine will be supplied by Railway ) Above/
Supply of Refrigerant Copper Pipe line of required size and length with nitrile rubber insulation and all other accessories including fixing, testing and commissioning of above pipe line for above Split AC units. Above/
Supply of Drainage system for each above Split / Window AC machine for discharge of condensate water with all accessories by 1.5 inch dia PVC pipe and drain line of each machine connected by 0.5 inch cotton braided PVC flexible pipe with all other accesso- ries along with fitment and commissioning. Above/
Supply of Copper Flexible 4C x 4.0 sq. mm.control cabe and cabling between outdoor and indoor units as per OEM specification bundled properly and neatly aligned with the refrigerant piping with well supported at specific intervals with fasteners including erection, testing and commissioning . ( Make of Copper cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab ) Above/
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 63-160 ) Amp, 4 Pole - 1 no. b) Power Contactor, 4 Pole, 28 100A, 415V, 50Hz - 2 nos. c) Astronomical Timer Switch, 2 module - 2 nos. d) Tinned Copper Busbar ( 4 Bar ) each of capacity 200 Amps., 415V, 50 Hz - 1 set e) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. f) CT of suitable ratio for MFM - 3 nos. g) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 12 nos. h) Petty Store for cable gland, socket, fuse etc. - 1 job complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) Above/
Fixing, connection, testing and commissioning of above panel including all incoming 29 and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Above/ 5845641.0
Goods & Services Tax ( at present @ 18% )
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderBooklet.pdf
ATTACHMENT
GCC_April-2022.pdf
ATTACHMENT
TenderFormandAnnexuresnew.pdf Tender form and annexure
ATTACHMENT
HTLTstandardspecification.pdf
ATTACHMENT
3634Clause.pdf
ATTACHMENT
AnnexureVIB.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
Advancecorrectionslips.pdf
ATTACHMENT
TenderFormandAnnexuresnew.pdf
ATTACHMENT
Download all tender documents and submit your bid