EE ETD DHAMPUR
OFFICE OF THE EXECUTIVE ENGINEER 132 KV SUBSTATION PREMISES NEAR NEW TEHSIL DHAMPUR
Work of repair and overhauling of air compressor system of 145 KV CBs and 33 KV VCBs at 220 KV Substation Nehtaur under ETD, Dhampur.
2022_UPTCL_683592_1
02/ETDD/2022-23
Open Tender
Electrical Works
60 days
Nehtaur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE ETD DHAMPUR
₹2,000
6 May 2022
31 Mar 2022
22 Apr 2022
31 Mar 2022
22 Apr 2022
31 Mar 2022
Amount
Work for complete overhauling of air compressor system of 145 KV breakers at 220 KV Sub station, Nehtaur.
Complete overhauling of air compressor including worn out/defective parts viz. oil seals, piston rings, piston rings kit, valve finger, bearing etc.
Complete arresting of air leakage in air pressure pipe line by providing all necessary sealing agents, repairing of pipe lines, replacement of worn out/leaked socketes etc.
Complete overhauling of electrical auto control system with complete replacement of defective parts viz. power contactor, over load relay and checking & making its complete wiring of the system.
Repair & overhauling work of 33 KV BHEL/CGL make CBs (No. 381, 382 & 2) type PVN-36 at 220 KV S/S, Nehtaur by checking and adjustment of snatch gap, travel of drive insulator rod, tie rod. Dismatling of operating mechanism of 33KV VCB from cubical. Repair of opening and closing mechanism by welding, drilling, matching & filling of material as per requirement. Oiling and greasing of crank gears by opening of lock,circlip etc. Replacement of worn out parts such as bush, rings, lock pins & latch etc. to get the repair work complete. After repair of operating mechanism fitting the mechanism at in its original place in CB cubical.Fitting of tripping and closing coil with open and close mechanism. Now checking and adjustment of snatch gap,travel of drive insulator rod, tie rod. Checking & adjustment of slow closing and operating of breaker. Checking and adjustment of oil dash-pot of breaker for its damping action.Carry out HV test of CB pole and proper adjust-ment of link rod. After successful overhauling, checking of meggar values of breaker poles.Checking of VCB operation mechanically and electrically. Checking and adjustment of spring charge timing. Carrying out contact resistance measurement, and checking tripping of breaker at 80% of DC voltage. Prepare and submit the site overhauling report of each breaker.
OHM ENTERPRISES AND ENGINEERS
Hi-tech power transmission
KARAN SINGH
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid