| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.3 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹28.3 L+₹85,660 (3.12%)Rejected-Finance 40 VISHNU VIHAR KHERAI SHAMSHABAD ROAD KHERAI AGRA UTTAR PRADESH 282001 | AGRA | UTTAR PRADESH | 282001 | L2 | Rejected-Finance Not Lowest Bidder | |
| 3 | L3₹29.8 L+₹2.3 L (8.35%)Rejected-Finance 202 NEW RAM VIHAR COLONY PINTO PARK MORAR GWALIOR 474005 | GWALIOR | GWALIOR | MP | 474005 | L3 | Rejected-Finance Not Lowest Bidder | |
| 4 | L4₹30.4 L+₹2.9 L (10.5%)Rejected-Finance ATLANTIS A2 1501 PLOT NO 05 SECTOR 11 NEAR CLOUD 36 GHANSOLI NAVI MUMBAI 400 701 E 97 CWE SUBS BHANDUP | THANE | MAHARASHTRA | 400701 | L4 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
25 Dec 2021, 6:00 pmClosed
GE (AF) Jaisalmer
GE (AF) Jaisalmer
Repair/maint/improvement of internal electrification and lighting protection system at Chandan Air Force Station Jaisalmer
2021_MES_491409_1
8794/GE/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (AF) Jaisalmer
As per tender documents
7 documents required · 7 mandatory
₹500
Yes
GE (AF) Jaisalmer
₹40,000
Yes
11 Jan 2022
30 Nov 2021
27 Dec 2021
30 Nov 2021
25 Dec 2021
13 Dec 2021
1 Dec 2021 - 4 Dec 2021
Amount
SCHEDULE 'A' PART-I Taking down carefully existing unserviceable/perished conduit/ batten/ casing caping aluminium/copper point wiring any type for light, fan, bell, socket, power point etc complete including all fixtures and fittings such as batten/ conduit/casing caping, top sheet covers etc and making good the disturbed surfaces of wall/ceiling complete all as specified & directed.
Concealed point wiring for one light point controlled by one, one way switch with 1.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade including 1.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour to common earth and connected to earth dolly laid/drawn into and including non metalic rigid PVC conduit 20mm dia with accessories fixed to cutting chases in walls by cutter and making good the surface in cement and sand mortar 1:3 and to the original specification and PVC conduit on ceiling for steel structure/surfaces conduit with clamps, gutties etc for RCC ceiling with including cast iron/pressed steel/wooden terminal boxes (as per site requirement) including providing new 3 mm thick plastic laminated sheet cover (Hylem) complete all as specified and directed.
All as per serial item No. 2.00 here-in-before but for one fan point controlled by one switch and regulator complete all as specified and directed.
All as per serial item No. 2.00 here-in-before but for one 3 Pin, 6 Amps, socket outlet controlled by one 6 Amps switch on same board complete all as specified and directed.
All as per serial item No. 2.00 here-in-before but for one 3 Pin, 6 Amps, socket outlet controlled by one 6 Amps switch on independent board complete all as specified and directed.
All as per serial item No. 2.00 here-in-before but for One 3 pin 6 Amps socket outlet independent but below the switch board of light points in the same vertical plane complete all as specified and directed.
Concealed Point wiring for one 3 pin, 16 Amps socket outlet controlled by one 16 Amps switch on independent board with 2.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade including 2.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour to common earth and connected to earth dolly laid/drawn into and including non metalic rigid PVC conduit 20mm dia with accessories fixed to cutting chases in walls by cutter and making good the surface in cement and sand mortar 1:3 and to the original specification and PVC conduit on ceiling for steel structure /surfaces conduit with clamps, gutties etc for RCC ceiling with including cast iron/pressed steel/wooden terminal boxes (as per site requirement) including 3mm thick plastic laminated sheet cover (Hylem) complete all as specified and directed.
Point wiring for one light point controlled by one way switch with 1.50 sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade including 1.50 sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour to common earth and connected to earth dolly laid/drawn into and including PVC casing & caping with accessories fixed on surface of walls/ceiling by means of PVC sleeves/dash fasteners with cadmium plated screws, all as per IS, terminated including suitable size module boxes for housing of modular switches, sockets, regulators complete all as specified & directed. Note : (i) Unit rates quoted by contractor shall be deemed to included for cutting chases in walls, ceilings and making good surfaces in cement and sand mortar (1:3) and finishing the surfaces to match with existing surfaces. (Make : Hylem/Anchor/Formica including machine screws and washer etc for fixing switches sockets etc and 1.5 sqmm copper conductor, standard (green colour earth), PVC insulated unsheathed earth wire to commen earth and connected to earth dolly as specified and directed.
All as per serial item No. 8.00 here-in-before but for one fan point controlled by one switch and regulator complete all as specified and directed.
All as per serial item No. 8.00 here-in-before but for one light point controlled by two way switch complete all as specified and directed.
All as per serial item No. 8.00 here-in-before but for one 3 pin 6 Amp socket outlet controlled by one 6 Amp switch on same board complete all as specified and directed.
All as per serial item No. 8.00 here-in-before but for one 3 pin 6 Amp socket outlet controlled by one 6 Amp switch on independent board complete all as specified and directed.
All as per serial item No. 8.00 here-in-before but for One 3 pin 6 amps socket outlet independent but below the switch board of light points in the same vertical plane complete all as specified and directed.
Point wiring for one 3 Pin, 16 Amps socket outlet controlled by one 16 Amps switch on independent board with 2.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 volt grade including 2.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour to common earth and connected to earth dolly laid/drawn into and including PVC casing & caping with accessories fixed on surface of walls/ceiling by means of PVC sleeves/dash fasteners with cadmium plated screws, all as per IS, terminated including suitable size module boxes for housing of modular switches, sockets, regulators complete all as specified and directed. Note : (i) Unit rates quoted by contractor shall be deemed to included for cutting chases in walls, ceilings and making good surfaces in cement and sand mortar (1:3) and finishing the surfaces to match with existing surfaces. (Make : Hylem/Anchor/Formica including machine screws and washer etc for fixing switches sockets etc and 2.5 sqmm copper conductor, standard (green colour earth), PVC insulated unsheathed earth wire to commen earth and connected to earth dolly as specified and directed.
Switch piano, flush type, Single Pole, one way, 6 Amp, 240 Volts (ISI Marked) fixed as in repair complete all as specified and directed.
Switch piano, flush type, Single Pole, one way, 16 Amp, 240 Volts (ISI Marked) fixed as in repair complete all as specified and directed.
Switch piano, flush type, Single Pole, two way, 6 Amp, 240 volt (ISI Marked) fixed as in repair complete all as specified and directed.
Socket outlet 2 in 1, 5 pin, 16 Amps, flush type, 240 Volts (ISI Marked) fixed as in repair complete all as specified and directed.
Socket outlet, 2 in 1, 3 pin, 6 Amp, flush type, 240 Volts (ISI Marked) fixed as in repair complete all as specified and directed.
Ceiling rose surface bakelite with two or three terminal PVC/Polycarbonate, isolated body (ISI Marked), 240 volts in repair complete all as specified and directed.
Lamp holder, PVC / Polycarbonate type with cord grip cap suitable for pendant fittings B-22 base fittings fixed as in repair complete all as specified and directed.
Stepped type electronic fan regulator, flush type and connecting up, 120 watt, 230 volt (ISI marked) complete all as specified and directed.
Modular switch 6 Amps, 250 Volt, AC, one way, one module (ISI Marked) fixed as in repair complete all as specified and directed.
Modular switch 20 Amps, 250 Volt, Single Pole, AC, one way with indicator one module (ISI Marked) fixed as in repair complete all as specified and directed.
Modular Socket shuttered, 6 Amps, 250 volts, 2/3 Pin combined, Single Pole, two module (ISI Marked) fixed as in repair complete all as specified and directed.
Modular Socket shuttered, 6/16 Amps, 250 volts, 3 Pin combined, Single Pole, two module (ISI Marked) fixed as in repair complete all as specified and directed.
Modular Fan Regulator, step type, 120 Watt, 2 module, 250 volts grade, (ISI Marked) fixed as in repair complete all as specified and directed.
Modular Metal flush mounting box of 1/2 Module fixed as in repair complete all as specified and directed.
Modular Metal flush mounting box of 3 Module fixed as in repair complete all as specified and directed.
Modular Metal flush mounting box of 4 Module fixed as in repair complete all as specified and directed.
Modular Metal flush mounting box of 6 Module fixed as in repair complete all as specified and directed.
Modular Metal flush mounting box of 8 Module fixed as in repair complete all as specified and directed.
Modular Metal flush mounting box of 12/16 Module fixed as in repair complete all as specified and directed.
White colour modular blanking plate, one module blank fixed as in repair complete all as specified and directed.
White colour plates with frame for modular switch of 1 module fixed as in repair complete all as specified and as directed.
White colour plates with frame for modular switch of 2 module fixed as in repair complete all as specified and as directed.
White colour plates with frame for modular switch of 3 module fixed as in repair complete all as specified and as directed.
White colour plates with frame for modular switch of 4 module fixed as in repair complete all as specified and as directed.
White colour plates with frame for modular switch of 6 module fixed as in repair complete all as specified and as directed.
White colour plates with frame for modular switch of 8 module fixed as in repair complete all as specified and as directed.
White colour plates with frame for modular switch of 2 x 6 module fixed as in repair complete all as specified and as directed.
Single Pole and neutral enclosure with a two pin and earth plug and MCB Protected Socket (Modular AC Box, Metal clad box) Two Module, with one Single Pole, 20 Amps, repturing capacity 10 kA including taking down old unserviceable complete all as specified and directed.
Surface and wall mounted 10 watt LED bulk head fitting in engineering plastic housing with clear prismatic diffuser complete with all accessories and connecting up complete with 3 core flexible cable white of size 23/0.0076 including taking down old unserviceble LED fittings complete all as specified and directed.
Decorative ultra slim round profile LED tube light fittings of capacity 9 watt LED 6000 K, basic all purpose surface and wall mounted LED batten with extruded polycarbonate housing & integrated electronic driver including taking down old unserviceble LED fittings complete all as specified and directed.
Decorative ultra slim square profile LED tube light fittings of capacity 18 watt LED 6500 K, basic all purpose surface and wall mounted LED batten with extruded polycarbonate housing & integrated electronic driver including taking down old unserviceble LED fittings complete all as specified and directed.
Decorative ultra slim square profile LED tube light fittings of capacity 20 watt LED 6500 K, basic all purpose surface and wall mounted LED batten with extruded polycarbonate housing & integrated electronic driver including taking down old unserviceble LED fittings complete all as specified and directed.
Sub main wiring with 2.50 sqmm, Single Core, PVC insulated unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 volts grade conforming to IS 694 including 2.50 Sqmm Single Core PVC insulated unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour drawn through in existing PVC casing caping conduit including taking down old unserviceable submain wiring complete all as specified and directed. Note : Two run of 2.50 sqmm cable and one run of 2.50 sqmm cable as earth wire continuity conductor shall be measured & paid as one unit.
Sub main wiring with 4.00 sqmm, Single Core, PVC insulated unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 volts grade conforming to IS 694 including 4.00 Sqmm Single Core PVC insulated unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour drawn through in existing PVC casing caping including taking down old unserviceable submain wiring complete all as specified and directed. Note : Two run of 4.00 sqmm cable and one run of 4.00 sqmm cable as earth wire continuity conductor shall be measured & paid as one unit.
Sub main wiring with 6.00 sqmm, Single Core, PVC insulated unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 volts grade conforming to IS 694 including 6.00 Sqmm Single Core PVC insulated unsheathed multistranded copper conductor Flame Retardant Low Smoke & Halogen (FRLSH) cable 1100 Volt grade as continuous earth wire in green colour drawn through in existing PVC casing caping including taking down old unserviceable submain wiring complete all as specified and directed. Note : Two run of 6.00 sqmm cable and one run of 6.00 sqmm cable as earth wire continuity conductor shall be measured & paid as one unit.
MCCB, 4 Pole, 100 Amps rating, rupturing capacity 16 kA, 415 Volt grade, AC supply, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
MCB, Single Pole, 6 to 32 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles including taking down old unserviceable MCB, complete all as specified & directed.
MCB, SPN, 32 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles, fixed as in repair complete, all as specified & directed.
MCB, SPN, 40 to 63 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles, including disconnecting & taking down old unserviceable MCB, complete, all as specified & directed.
MCB, TPN, 40 to 100 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 415 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles, including disconnecting & taking down old unserviceable MCB, complete all as specified & directed.
Sheet metal enclosure powder coated single phase DB SPN 8 ways and neutral 240 Volts, AC supply, 50 Hz, with 200 Amps rated bus bar Double Door (IP-43 IK 09 with metal door) suitable for fixing of MCBs including fixing of lugs in main incomming and outgoing line and fixing of cable glands of suitable size including grouting flush in the wall by means of nuts, bolts, angle iron and making good disturbed surfaces including taking down old unserviceable DB complete all as specified and directed.
Sheet metal enclosure powder coated single phase DB SPN 12 ways and neutral 240 Volts, AC supply, 50 Hz, with 200 Amps rated bus bar Double Door (IP-43 IK 09 with metal door) suitable for fixing of MCBs including fixing of lugs in main incomming and outgoing line and fixing of cable glands of suitable size including grouting flush in the wall by means of nuts, bolts, angle iron and making good disturbed surfaces including taking down old unserviceable DB complete all as specified and directed.
Sheet metal enclosure powder coated single phase DB TPN 4 ways and neutral 415 Volts, AC supply, 50 Hz, with 200 Amps rated bus bar Double Door (IP-43 IK 09 with metal door) suitable for fixing of MCBs including fixing of lugs in main incomming and outgoing line and fixing of cable glands of suitable size including grouting flush in the wall by means of nuts, bolts, angle iron and making good disturbed surfaces including taking down old unserviceable DB complete all as specified and directed.
Sheet metal enclosure powder coated single phase DB VTPN 4 ways and neutral 415 Volts, AC, 50 Hz, with 200 Amps rated bus bar Double Door (IP-43) suitable for fixing of MCBs including fixing of lugs in main incomming and outgoing line and fixing of cable glands of suitable size including grouting flush in the wall by means of nuts, bolts, angle iron and making good disturbed surfaces complete all as specified and directed.
LED Panel 36 watt with slim panel 595X595mm with super bright recess mounting LED Slim ceiling light with white powder coated extruded aluminium housing and highly efficient light smoothing optics to deliver superior illumination including LED driver and fixing in recess ceiling suitable size of aluminium strip size as required for fixing of LED fitting complete with all accessories prewired fixed on ceiling and connecting up complete with 3 core flexible cable of size 23/0.0076 including taking down old unserviceable fittings complete all as specified and directed.
Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth wire 4mm dia by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No. 3 of SSR Part-I and connection to main switch board/Test point/ panel/ equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exceeding 50 metre, charcoal and salt in alternate layer 15cm thick all around the earth plate electrode, Mild Steel Funnel with wire mesh, 20mm bore, GI pipe medium grade, 1.50 metre long for watering and 15mm bore, GI pipe light grade, 7.50 metre long for earth wire protection fixed with poles with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:2:4) type B-1, using 20mm graded stone aggregate with angle iron 40x40x5mm frame 60mm thick RCC cover with 6mm steel bars 100mm centre to centre both ways etc including dismantling & taking out old existing unserviceable earthing complete all as specified & as directed. Note : (i) PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) If earth resistance of earthing is not found satisfactory it will be redone by the contractor on his risk and cost.
Earthing complete with galvanished earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5 deep below normal ground level and connected to galvanished iron earth lead strip 32mmx6mm upto 7.50 metre, by means of GI nuts, bolt, check nuts, washers, thimbles, etc as shown in electrical plate No. 5 SSR Part-I and connection to main switch board or panel and testing on completion including excavation and earth work in any type to soil, returning fitting in and removal of surface spoil to a distance not exceeding 50 metre, PCC chamber (1:3:6) type C-2, charcoal and salt mixed layer 15cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe light grade 20mm bore for watering and 50mm bore GI pipe light grade for earth wire protection fixed with poles with two clamps, made from earth lead strip 32mm x 6mm, bolts, nuts and washers, 80mm thick pre cast RCC cover 1:2:4, type B-1, reinforced with hard drawn steel wire fabric wieghing not less than 4 Kg/Sqm in lieu of CI cover etc including taking down old earth complete all as specified and directed. Note : (i) The unit rate shall be deemed to included for Test point, 32mmx6mm GI strip from top of the earth plate upto 7.50m above ground level. In case, GI protection pipe required is less than 7.50m, no price adjustment shall be made. (ii) PCC pit shall be provided at least 500mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fittings, junctions, elbow etc shall be deemed to be included in the unit rate quoted by the tenderer.
Cable jointing kit for 1100 Volts grade LT cable for straight through heat shrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 25 sqmm 3.5/4 core to 95 sqmm 3.5 core including dismantling & taking out old unserviceable jointing kit complete all as specified and directed
Cable jointing kit for 1100 Volts grade LT cable for straight through heat shrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 95 sqmm 3.5 core to 120 sqmm 3.5 core including dismantling & taking out old unserviceable jointing kit complete all as specified and directed
Excavation in trenches, in any type of soil and getting and not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation etc. or for laying of cables, pipes, erection of poles, structs/stays etc. or for shafts, manholes, pier holes, etc not exceeding 10 sqm on plan complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft/loose soil complete all as specified.
Removal of excavated soil/ material to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point complete all as specified.
Stone patti 40 to 50mm thick rough dressed Jodhpur stone slab cover in trenches for protection of cable 25 to 35cm wide and not less than 80cm in length laid dry abutting each other with gap between adjacent slab not exceeding 10mm over sand cushioning complete all as specified and directed.
Dry tibba sand cushioning to underground cable provided with a layer of 8cm deep before laying cable and 15cm after laying of cable and punned to 18cm after laying of cable and cover for protection of underground cable complete all as specified and directed. Notes :- (i) Approved dry sand free from vegetation, grass and other deleterious substances shall be used. (ii) For the purpose of payment only punned thickness shall be measured for payment.
Supply, laying, jointing and testing XLPE insulated armoured heavy duty LT under ground electric cable (ISI marked) with aluminium stranded conductor 1100 Volt grade cross sectional area 35 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/along poles including taking down old unserviceable cable complete all as specified and directed.
Supply, laying, jointing and testing XLPE insulated armoured heavy duty LT under ground electric cable (ISI marked) with aluminium stranded conductor 1100 Volt grade cross sectional area 50 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/along poles including taking down old unserviceable cable complete all as specified and directed.
Taking out the old unserviceable LT under ground cable after disconnecting from over head line and panel rated voltage of 1100 volts from trenches, pole etc and relaying the same after jointing or necessary repair work and testing XLPE insulated PVC outer seathed and PVC inner sheath, galvanised steel strips armoured and reconnecting the cable from over head line and panel suitable for rated voltage of 1100 volts grade Earthed system of size 25-95 sqmm 4/3.5 core and laid in treches/ducts/pipe or on road/pole complete all as specified and directed. Note: excavation and earth work joints will be measured and paid seprately.
Galvanized steel water tubing light grade of 40mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable steel water tubing and connections of 40mm bore, complete all as specified and directed.
Galvanized steel water tubing light grade of 50mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable steel water tubing and connections of 50mm bore, complete all as specified and directed.
Boring Hole/Drilling (Horizontally) under the road / pavement / hard standing with the help of trenchless and necessary machine for inserting Galvanised steel pipe of size 100/80mm not less than one metre below ground level complete all as specified and directed. Note : GI pipe shall be measured and paid for seperately in respective items.
Galvanised strip 32x6mm buried in ground and connected with aluminium strip by means of brazing or fixing on wall including taking down old unserviceable complete all as specified and directed. Note : Nut, bolt and other items included in quoted rate by the tenderer.)
Copper strip 20x3mm with saddles and fixing screws etc for roof conductors and down condoctors above ground including taking down old unserviceable complete all as specified and directed.
Air termination, Single Pointed, copper rod 12mm dia and 300mm long and fixing to GI pipe with clamps, nuts, bolts and washers including taking down old unserviceable complete all as specified and directed.
Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 Nos, 8mm dia, 25mm long hexaguanal head screw including taking down old unserviceable complete all as directed and directed.
Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.00 mtr long) including painting of poles with two coats of aluminium paint over one coat of red oxide primer with and embedded portion shall be painted with two coat of black paint including dismantling of old unserviceable steel tubular poles complete all as specified and directed in IS including the following:- (i) Excavation in post holes in any type of soil, return filling, well ramming and disposal of surplus soil to a distance not exceeding 50mtr from the starting point. (ii) PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as in foundation upto ground level complete all as specified and directed. (iii) PCC 1:3:6 type C2 (using 40mm graded stone aggregate) as in coping including necessary formwork as required. (iv) PCC 1:2:4 type B1 (using 20mm graded stone aggregate) as in coping including necessary formwork as required complete all as specified and directed (v) Writing letters of figures (Block, Roman, Itallicor Indian) with thick enamel paint pait of approved shade not exceeding 5cm height in numbering of Each Pole.
Exhaust Fan, steel body, 300mm sweep, heavy duty, ISI Marked with mounted in suitable opening arrangement with louvers shutters suitable for operation on 230 volts, single phase, 50 cycle per second, AC supply and connecting up including three core PVC insulated PVC sheathed copper conductor flexible cable 24/0.2 mm drawn in flexible PVC conduit from ceiling rose or connector to exhaust fan including marking of MES number and making holes into wall and fixed to wall by using 4 Nos, bolts, nuts and washers and grouted in wall in CM 1:3 including taking down of old unserviceable fan and deposition of the same in MES store yard at Air Force Jaisalmer complete all as specified and directed.
Pedestal fan, sprint Hi speed, stand along unit with base and stand AC supply, single Phase, 230 volt of size 400mm sweep with blades, frame and protection arrangement including taking down of old unserviceable fan and deposition of the same in MES store yard at Air Force Jaisalmer complete all as specified and directed.
Supply, laying, jointing and testing 1100 volts grade heavy duty cable PVC insulated aluminium solid conductor cable 10 sqmm, twin core, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4mm suspension wire including taking down old unserviceable cable complete all as specified and directed.
LED Adore 10 watt base capacity B22, STAR Lamp lumen output 950, color temp 6500K fixed as in repair complete all as specified and directed.
LED Adore 15 watt base capacity B22, STAR ball Lamp lumen output 1425, color temp 6500K fixed as in repair complete all as specified and directed.
PVC insulation tap 25mm wide complete all as specified and directed.
Supply, installation, tower Air conditioning of capacity 2.00 Ton, moisture removal 2.6 litre per hour, high air circulation 1110, 50 Hz, noise level shall not be more than 50 dB (A) including taking down of old Air Conditioning and deposition of the same at MES store yard Air Force Jaisalmer complete all as specified & directed.
Supply, installation, voltage stabilizer for automatic operation single phase naturally air cooled indoor type copper wound and designed for input variation between 140 volts to 280 volts with output voltage stabilized at 200-240 volts with accuracy of ± 2.5% of capacity 5 KVA with mounting bracket with time delay relay complete all as specified and directed.
Sheet metal enclosures with socket plug top Single Pole and neutral encolsure with a two pin and earth plug with socket complete with one Single Pole with neutral MCB, 32 Amps rupturing capacity 10 kA, 415 volt grade, AC supply, 50 Hz, including disconnecting & taking down old unserviceable as existing complete all as specified & directed.
Wooden board for mounting of switches/sockets or other switches of sizes 190x240mm, thickness of wood wall shall not be less than 13mm thick, the board shall be enclosed from all sides and back fixed as in repair complete all as specifed and directed
Wooden board for mounting of switches/sockets or other switches of sizes 300x300mm, thickness of wood wall shall not be less than 13mm thick, the board shall be enclosed from all sides and back fixed as in repair complete all as specifed and directed
Acrelic sheet, electric grade for fixing of switches /sockets or other similer nature items of sizes 190x240mm, 3mm thick, dully cutting for mounting of switches/sockets as required in and including necessary screws for fixing on wooden board fixed as in repair complete all as specifed and directed
Acrelic sheet, electric grade for fixing of switches /sockets or other similer nature items of sizes 300x300mm, 3mm thick, dully cutting for mounting of switches/sockets as required in and including necessary screws for fixing on wooden board fixed as in repair complete all as specifed and directed
Elastomer insulated, round or flat, sheathed, multicore, industrial flexible cable with bright annealed copper conductor, 1100 volts grade cable of size 1.5 sqmm, 3 core, confirming to IS 694-2010 including taking out old unserviceable cable from pole all as specified and directed.
Elastomer insulated, round or flat, sheathed, multicore, industrial flexible cable with bright annealed copper conductor, 1100 volts grade cable of size 2.5 sqmm, 3 core, confirming to IS 694-2010 including taking out old unserviceable cable from pole all as specified and directed.
Earthing complete with CPRI tested 50mm dia copper cladded (250 micron) earth electrode 3000mm in length with NABL tested RoHS complaint earth enhancement compound 30 Kg in each bore hole in tripod configuration with copper strip of 25x3mm inter connected by means of exothermic brazing & protected by GI pipe light grade 32mm bore upto the test point i.e 7.50mtr in length and PCC 1:3:6 type C-1 earth chamber & cast iron earth pit cover 300x300x3mm connecting to test point & testing on ground complete including excavation, earth work, boring in any type of soil strata & cleaning of site complete all as specified and directed. Make: JMV earthing/Daksh Power Solutions/Ashlok Note: (i) Copper strip of size 20x3mm required to connected to the electrode upto test point is deemed to be included in quoted rate by the tenderer. (ii) The boring will take place for 3mtr depth & 350mm dia. Earth enhancement compound to be filled around the earth electrode in 100mm dia in 3 layers of 1mtr each by means of PVC pipe of 100mm dia as casing/form work. The ramaning valume of bore shall be filled with clay soil (available from vicinity) in 3 layers of 1mtr each. The PVC pipe to be removed simultaneously. The cost of all this is deemed to be included in the quoted rates. (iii) Cost of excavation, earth work, boring, PCC earth pit, CI cover including testing & commissioning etc is deemed to be included in the quoted rates by the tenderers. (iv) Marking & painting of earth pit with iron, plate of suitable size is deemed to be included in the quoted rates. (v) Minimum distance between each earthing is not less than 3 RM (vi) Testing of earthing shall be conducted and result should be less than 1.00 Ohm.
SCHEDULE 'A' PART-II Re-winding the electric motor of capacity 5 HP by dismantling and removing the burnt out copper winding cleaning the slot of stator thoroughly and rewinding the stator with super enamelled copper winding wire superior quality of approved make, size & number of wire as per existing including insulation material, minor spares and replacement of unserviceable spare parts and reassembling the parts of the motor, reinstallation in same position complete and testing and comissioning complete all as specified.
Re-winding the electric motor of capacity 3 HP by dismantling and removing the burnt out copper winding cleaning the slot of stator thoroughly and rewinding the stator with super enamelled copper winding wire superior quality of approved make, size & number of wire as per existing including insulation material, minor spares and replacement of unserviceable spare parts and reassembling the parts of the motor, reinstallation in same position complete and testing and comissioning complete all as specified.
Power Contactor 3 phase, 32 Amps with AC coil voltage 415 volts, 50 Hz fixed in existing panel including disconnecting & taking down old existing unserviceable contactor. MAKE : Siemens Cat Part No. 3TF3400-0A/ Legrand/ ABB.
Power Contactor 3 phase, 40 Amps with AC coil voltage 415 volts, 50 Hz fixed in existing panel including disconnecting & taking down old existing unserviceable contactor. MAKE : Siemens Cat Part No. 3TF3500-0A..ZT00 / Legrand/ ABB.
MCCB, 4 Pole, 100 Amps rating, rupturing capacity 25 kA, 415 Volt grade, AC, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
MCCB, 4 Pole, 400 Amps rating, rupturing capacity 36 kA, 415 Volt grade, AC, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
MCCB, 3 Pole, 250 Amps rating, rupturing capacity 36 kA, 415 Volt grade, AC, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
MCCB, 3 Pole, 125 Amps rating, rupturing capacity 25 kA, 415 Volt grade, AC, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
MCCB, 3 Pole, 63 Amps rating, rupturing capacity 50 kA, 415 Volt grade, AC, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
MCB, TP, 32 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles, fixed as in repair complete, all as specified & directed.
MCB, TP, 40 Amps rating, with over load and short circuit protection 'B' curve and rupturing capacity 10 kA, 415 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles, fixed as in repair complete all as specified & directed.
Supply and filling in refrigerant Gas R-407c for charging complete all as specified and directed.
Finding out the leakage and pressure test of the condensor and cooling coil of Chiller Package type Water cooled AC Plant of 11/12.5 TR Capacity and dismantling the same for repair the leakage point by brazing/soldering including taking down/refixing the unit and testing the AC unit.
Dismantling, opening and reassembling after replacement of unserviceable spare parts of Monoblock pump set (Horizontal type) capacity 3 HP to 5 HP, 415 volts including dismantling the pump, replacement of mechanical water seal as bearing and lock etc as required, reconnection, re-fixing in same position, transportation to workshop and back and refixing at site and testing complete all as specified and directed. Notes :- Unit rates quoted by the tenderer shall be deemed to include for all minor spares/extras. The decision of Accepting officer regarding minor spares/extras shall be final, conclusive and binding.
Descalling of Condenser unit complete with Descaling chemical (Scale2/ 38249022) including Descaling of Cooling Tower complete all as specified and directed.
Solenoid valve as per sample fixed as in repair complete all as specified and directed.
Drier filter fixed as in repair complete all as specified and directed.
Opening and refixing of monoblock pump and including replacing of gland, sills, packing, and all necessary items like nut and bolts and washer complete all as specified and directed.
Cooling Tower fins of suitable size as per existing complete all as specified and directed.
AHU Belt of suitable size as per ssmple fixed as in repair complete all as specified and directed. Make : Finner or equivalent.
Cooling tower Sprinkler as per sample fixed as in repair complete all as specified and directed.
AHU filters 90%upto 5 Micron of suitable size fixed as in repair complete all as specified and directed.
Complete control wiring with complete interlocking of chillers units, condensers, Chillers Pump, Cooling Pump and AHU with Panels and including disconnecting & taking down old unserviceable complete all as specified and directed.
PVC insulated Flame Retardant Low Smoke & Halogen (FRLSH) multistranded copper conductor cables, 1100 volts grade conforming to IS 694 including and Single core, 6.00 Sqmm including replacement of all lugs/thimbles with new copper lugs/thimbles and including taking down old unserviceable wiring complete all as specified and directed.
Electronic type Single Phasing Preventer in existing panel boards (max 600V & min 380V) three phase 415 Volts variation voltage 4% tripping time 2-5 second maximum including disconnecting & taking down old unserviceable Single Phasing Preventor, complete all as specified & directed. Make: Minilec/L&T/Siemens/ ABB/BCH/Havells
Phase indicator lamp as per sample fixed as in repair complete all as specified and directed.
Cooling tower Strainer filter as per sample fixed as in repair complete all as specified and directed.
Pressure Gauge 4" dial 0-21 Kgs rating as per sample fixed as in repair complete all as specified and directed.
Blower motor pulley, as per sample fixed as in repair complete all as specified and directed.
Supply, installation, commissioning and testing of Compressor scroll type Copper wound working on R-407c, Capacity 11 TR and compressor shall be equipped with sunction and discharge stop valves, sunctions, strainer, oil pump with oil strainer, high pressures switch and safety valves and gauges oil measuring the sunction and discharge pressure and the coil pressure shall be provied.Compressor shall be provided with unloading starting device and crank case heater system shall be provided including taking down old unserviceable compressor complete all as specified and directed. Make : Danfoss Model Number SZ185S4RC or equivalent.
5000 Litre capacity Rotational moulded polyethylene water storage tanks triple layered (cylindrical vertical with closed top) ISI marked, hoisted & fixed in position & making necessary arrangements for fixing inlet, outlet & over flow pipe & provision of wash out pipe etc. including dismentling & taking down old unserviceable water tank complete as specified in SSR Part-I.
MPD of current range 5-30 Amp, Aux. Supply 0-11 VAC, 0-13 VAC Volt, 5 Sec Curve MPD fixed as in repair complete all as specified and directed. Make:- Softhard Automation Model -SCR 33 TR (MPD) or equivalent.
PLC Controller for 33 TR Chillar unit fixed as in repair complete all as specified and directed. Make :- Softhard Automation Model No-33 TR/ HMI (5-30 A) / Ser No-02/2K13-50 or equivalent.
500 Litre capacity Rotational moulded polyethylene water storage tanks triple layered (cylindrical vertical with closed top) ISI marked, hoisted & fixed in position & making necessary arrangements for fixing inlet, outlet & over flow pipe & provision of wash out pipe etc. including dismentling & taking down old unserviceable water tank capacity 500 litre complete as specified in SSR Part-I.
Heating rod of capacity 2KW to 3 KW as per existing for Dehumidifier/ Humidifier complete all as specified and directed .
Supply, install, connecting & testing electric driven centrifugal monoblock pump set of capacity 5.0 HP / 3.7 KW, Three Phase, 50 Hz, 415 Volts, head range 18 metre with class 'B' insulation of suction and delivery size 80x80mm including necessary fixing arrangement and inlcuding taking down old unserviceable pump complete all as directed. Make : Kirlosker Model KDS 520+ or equivalent/CG/Havells
S.D. And Company
AUTOMATION AND SWITCHGEAR CONTROL
M/s Shree Construction Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .