| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.7 LAccepted-AOC 93 618 A MOHANTA PARA WARD NO 19 PO DIST JALPAIGURI PIN 735101 | JALPAIGURI | WEST BENGAL | 735101 | L1 | Accepted-AOC Being lowest biddr | |
| 2 | L2₹50.8 L+₹9.5 L (22.9%)Rejected-Finance | L2 | Rejected-Finance Being other than lowest bidder | |
| 3 | L3₹52.0 L+₹10.6 L (25.7%)Rejected-Finance | L3 | Rejected-Finance Being other than lowest bidder | |
| 4 | L4₹53.0 L+₹11.7 L (28.2%)Rejected-Finance OPPOSITE GATE NO 2 NORTH BENGAL UNIVERSITY PO N B U DIST DARJEELING WB | DARJEELING | DARJEELING | WEST BENGAL | 734013 | L4 | Rejected-Finance Being other than lowest bidder | |
| 5 | L5₹53.6 L+₹12.3 L (29.7%)Rejected-Finance SAYED MUSTAFA ALI ROAD HAKIMPARA P O SILIGURI 734001 DISTT DARJEELING W B INDEX NO E 139 BENG 2010 | DARJEELING | WEST BENGAL | 734001 | L5 | Rejected-Finance Being other than lowest bidder |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
7 Jun 2021, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Bengdubi
Headquarters Commander Works Engineers Bengdubi, Post - Bengdubi Distt - Darjeeling (WB) PIN- 734424
REPAIR / MAINTENANCE OF CERTAIN HT INSTALLATIONS AT BENGDUBI MIL STATION UNDER GE BENGDUBI
2021_MES_439778_1
8097/B/E8
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
GE BENGDUBI
As per tender documents
8 documents required · 8 mandatory
₹500
GE Bengdubi
₹92,000
6 Jul 2021
3 May 2021
12 Jun 2021
3 May 2021
7 Jun 2021
17 May 2021
60 days
Amount
S & F in repairs Steel Tubular Poles complete with and including cast iron base plate, finial taper plug, bolts , nuts & screws, type 410 SP-55(11 Metre long), also including painting to the external exposed surfaces with 2 coats of aluminium paint over 1 coat of red oxide primer and with 2 coats of black bituminous paint over 1 coat of red oxide primer to the external exposed surfaces of steel poles embedded in the ground / concrete after preparation of the surfaces, numbering to the poles, complete in all respect as specified and as directed, Make: Jindal Steel/ National Tubing Co/ Calcutta Poles & Tubes). Note:- Excavation & Earth Work, concrete for foundation and coping shall only be measured and paid for separately.
S & F in repairs Steel Tubular Poles complete with and including cast iron base plate, finial taper plug, bolts , nuts & screws, type 410 SP-31(9 Metre long), also including painting to the external exposed surfaces with 2 coats of aluminium paint over 1 coat of red oxide primer and with 2 coats of black bituminous paint over 1 coat of red oxide primer to the external exposed surfaces of steel poles embedded in the ground / concrete after preparation of the surfaces, numbering to the poles, complete in all respect as specified and as directed, Make: Jindal Steel/ National Tubing Co/ Calcutta Poles & Tubes). Note:- Excavation & Earth Work, concrete for foundation and coping shall only be measured and paid for separately.
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5m in depth for laying of under ground cables/ pipes and not exceeding 10 Sqm on plan & 1.5 metre in depth for pole etc, complete all as specified and directed.
All as per item No. 3.00 above but depth exceeding 1.50 metre and not exceeding 3.00 metre.
Returning, filling in, including spreading, watering and well ramming in layers not exc 25cm thick in layers, complete all as specified and directed.
Removal of surplus spoil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point, complete all as specified and directed.
M & L for cement concrete (1:3:6) type C-2 (using 40mm graded stone aggrgate) for pole foundation including provision of necessary form work, complete all as specified and directed.
M & L for cement concrete (1:2:4) type B-1 (Using 20mm graded stone aggregates) for coping of pole etc including provison of necessary form work, complete all as specified and directed.
M& L for Sand cushioning in trenches for cushioning of underground cable including spreading, levelling, well ramming in layers not exceeding 25cm in thickness, complete all as specified and directed.
Supplying and laying factory made (Make as approved by the GE) pre cast unreinforced concrete cable cover class HV, type 1, flat, size 300mm x 180 mm x 40 mm for cable protection in trenches, complete all as specified and directed.
Taking down old unserviceable existing XLPE insulated, heavy duty electric cables with aluminium conductor 11000 volts grade including aluminium lugs, pipes from the trenches /duct/ any other location, complete all as specified and as directed. Note:- Excavation and earth work shall be measured and paid for separately.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables (hevy duty) with aluminium conductor 11000 volts grade (Earthed) of size 95 sqmm 3 core (Make Havells/ Gloster/Finolex), complete all as specified and directed. Note:- Excavatioin and earth work, sand cushioning, protection covers, protection pipes and jointing kits Iincluding jointing materials shall be measured and paid for separately.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables (hevy duty) with aluminium conductor 11000 volts grade (Earthed) of size 120 sqmm 3 core (Make Havells/ Gloster/Finolex), complete all as specified and directed. Note:- Excavatioin and earth work, sand cushioning, protection covers, protection pipes and jointing kits Iincluding jointing materials shall be measured and paid for separately.
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables (hevy duty) with aluminium conductor 11000 volts grade (Earthed) of size 185 sqmm 3 core (Make Havells/ Gloster/Finolex), complete all as specified and directed. Note:- Excavatioin and earth work, sand cushioning, protection covers, protection pipes and jointing kits Iincluding jointing materials shall be measured and paid for separately.
Boring/Drilling (horizontally) using ultrasound technique and necessary machine for passing pipe for protection of the cable at approx 1 metre depth in soil below existing road, pavement, hardstanding etc without damaging to the existing surfaces, getting out & disposal of spoil to a distance not exceeding 50 metre from the site of the work, complete all as specified and directed. Note :- Cost of pipes & cable not included in the scope of above item.
Supply and fixing GI tubing, medium grade, 80mm bore for protection of cable under road crossing, across drain, along electric pole or floor /wall etc, complete incliding taking out existing pipe, complete all as specified and directed. Note for Item No. 16 : Excavation & Earthwork and Boring/Drilling shall be measured & paid for separately.
Supply, jointing and testing, in repairs, cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint, complete with and including jointing materials and accessories suitable for 11KV XLPE insulated armoured aluminium conductor cable of size 95 Sqmm 3 core, complete all as specified and as directed. Make: Denson / M Seal / Cab seal.
Supply, jointing and testing, in repairs, cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint, complete with and including jointing materials and accessories suitable for 11KV XLPE insulated armoured aluminium conductor cable of size 120 Sqmm to 185 Sqm, 3 core, complete all as specified and as directed. Make: Denson / M Seal / Cab seal.
Supply, jointing and testing, in repairs, straight through cable jointing kit (Heat shrink type) for 11 KV (Earthed) grade cable complete with and including jointing materials & accessories, suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm and also including provision of aluminium thimbles, all as specified and as directed. Make: Denson / M Seal / Cab Seal.
Supply, jointing and testing, in repairs, straight through cable jointing kit (Heat shrink type) for 11 KV (Earthed) grade cable complete with and including jointing materials & accessories, suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqm and also including provision of aluminium thimbles, all as specified and as directed. Make: Denson / M Seal / Cab Seal.
M&L for earthing complete of advance encapsulated compound based (CPRI tested) maintenance free, pipe-in-pipe technology upgraded (Zinc & Alloy coated). Zinc coated (80-100) microns with pure zinc(99.9%) & alloy coating (200-250) microns. Earthing system shall be conforming to IS-3034, the outer and inner pipe shall be 76.2mm & 41.9mm dia, 3 metre length Zinc coated with additional special alloy coating 300mm on the topside for additional protection of the terminal, annular space between the pipes being filled up with compact fill (CF) (Crystalline conductive compound). The compact fill (CF) mixture shall be machine pressed in the pipes and should not disintegrate or collapse when outer pipe corrodes. The inner pipe shall be extended with terminals for connectivity. The job includes digging the pits of 300mm diameter and refilling the same with 4 bags (25 Kgs/bag) electrodite/ conductolite back fill comopound (Ground Enhancer). The BFC shall be eco friendly, it shall not contain environmentally hazard materials having ROHS certification from NABL accredited lab. The earth pit shall also be provided with earth pit cover for protection and safe guard of terminals. The earth electrode (the main component of the earthing system) which is in direct contact with the ground shall be able to provide a means of releasing or collecting earth leakage current. The materials shall have good electrical conductivity & anti-corrosion property in wide rage of soil condition and testing on completion including replacing the existing soil with black soil for 80cm dia (Black soil shall be filled for total 80cm dia - 30cm dia of earth pit) (for the total depth of pit) around the 300mm dia pit, Make : ASHLOK Model –ASEEL-39 ZC & AC (zinc & Alloy) or equivalent as approved by the GE and also including taking out/ dismantling of the existing earthing, complete all as specified and as directed. Note : Earth results obtained should be minimum 01 Ohm.
Dismantling of existing insulators from poles of any description and any size, complete all as specified and directed.
S&F Pin type, polymer, grey, brown or green insulator including one galvnished mild steel spindle, two galvanised iron washers and one galvanied iron nut for 11 KV grade, complete all as specified and directed. MAKE: BHEL / Jaipuria Brothers / Pactil
S&F Pin type, Polymer, grey, brown or green insulator including one galvnished mild steel spindle, two galvanised iron washers and one galvanied iron nut for 33 KV grade, complete all as specified and directed. MAKE: BHEL / Jaipuria Brothers / Pactil
S&F post type, polymer, grey, brown or green insulator including one galvnished mild steel spindle, two galvanised iron washers and one galvanied iron nut for 11 KV grade, complete all as specified and directed. MAKE: BHEL / Jaipuria Brothers / Pactil
S&F post type, polymer grey, brown or green insulator including one galvnished mild steel spindle, two galvanised iron washers and one galvanied iron nut for 33 KV grade, complete all as specified and directed. MAKE: BHEL / Jaipuria Brothers / Pactil
Dismantling of Over head aluminium conductor steel reinforced, complete all as specifed and directed.
M&L for Over head aluminium conductor steel reinforced of size as ordered, complete all as specifed and directed.
Dismantling of cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, complete all as specified and directed.
M & L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of preparation of exposed surfaces, application of one coat of red oxide primer and thereafter 2 coats of alluminiuam paint, complete all as specified and directed.
S&F in repair, 11 KV, 400 Amps, out door, tilting type, gang operated, air break off load disconnecting switch, triple pole, each consists of galvanized channel base HT insulator,non - ferrous knife and spring loaded contacts, arcing horn of adequate section to break magnetizing current of the transformer, horizontal GI pipe of adequate length for phase separation and for operation from ground level and operating handle, complete with locking arrangement on both ON and OFF position, all ferrous parts shall be hot dipped galvanized and non ferrous parts heavily tinned to withstand weather suitable for vertical mounting and conforming to IS 1818-1961, complete all as specified and as directed. Make - High tension switch gear Ltd / Jaipuria Brothers / SK industries / Pactil .
S&F in repair, lightening arrester, non-linear metal oxide type, complete with and including all fittings, distribution class, discharge capacity 65 Kilo amps suitable for 11 KV, out door typeand also including necessary connection and fittings all as per IS-3070 Part-III and IEC 1994, complete all as specified and as directed. Make: High tension switch gear Ltd / Jaipuria Brothers / SK industries / Pactil.
S&F in repair, lightening qrrestor, non-linear metal oxide type, complete with and incuduing all fittings, transmission class, discharge capacity 65 Kilo amps suitable for 33 KV, out door type and also including necessary connection and fittings all as per IS-3070 Part-III and IEC 1994, complete all as specified and as directed. Make: High tension switch gear Ltd / Jaipuria Brothers / SK industries / Pactil.
S&F in repairs Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with and including M.S.clamps, bolts and nuts of approved size for 33 KV HT, 25x20cm size, complete all as specified and directed.
Supply and fix in replacement D O(Drop out) fuse unit, double stack, channel type, 3 pole, 33 KV, channel mounted, complete all as specified and directed, Make - High tension switch gear Ltd / Jaipuria Brothers / SK industries / Pactil .
Supply and fix in replacement D O(Drop out) fuse unit, double stack, channel type, 3 pole, 11 KV, channel mounted, complete all as specified and directed, Make - High tension switch gear Ltd / Jaipuria Brothers/ SK industries / Pactil .
M&L for carrying out repair to the 11 KV 400 Amps, Outdoor type, Gang Operated, Air Break Switch by replacing unserviceable spares like male , female contact, moving contact, flexible jumper, closing handle, clamps, bolt, nuts etc including necessary cleaning, applying grease and all other relevant works to make the Air Break Switch fully functional, complete all as specified and directed.
M&L for removing and taking out all old stone aggregate of any size, staking properly, carryout surface dressing & cleaning the surfaces of the 33 KV yard, thereafter providing single layer of 100 mm thick PCC (1:3:6), Type C-2 (using 40mm graded stone aggregets), subsequently laying 1 mm thick plastic mat in complete yard, further relaying the removed stone aggregate in the complete yard and lastly spreading thin layer of anti vegetation chemical to prevent abnormal growth of grass/bushes, complete all as specified and directed. Note for item No 38: (i) For the payment purposes, volume of PCC 1:3:6 shall only be considered. (ii) For additional qty of stone aggregate (as required) will be paid under item No 39.
M&L for spreading and levelling evenly in layers not exc 15cm thickness, 40 mm graded stone aggregated at 33KV main receiving station, complete all as specified directed.
M&L for precast RCC 1:11/2:3, type A-0 (using 12.5 mm graded stone aggregates) as in cover slabs etc (including use of Forms, Moulds or Machine Moulds for casting of the slabs etc) over the cable trenches at the 33 KV/11 KV MRS Ward etc, complete all as specified and directed. Note:- Reinforcement shall be measured and paid seperately.
M&L for TMT bars 08 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia, or securing with clips etc, complete all as specified and as directed.
S&F in repairs, highly insulated FRP earth discharge rod 3 section, 15 feet long suitable for working pressure 11 KV, Make :- Jaipuria brothers or of any other equivalent make as approved by the GE, complete all as specified and directed.
S&F in repairs, highly insulated FRP earth discharge rod 3 sections, 15 feet long suitable for working pressure 33 KV, Make :- Jaipuria brothers or of any other equivalent make as approved by the GE, complete all as specified and directed.
Supply and installation in repair ABC type fire extinguisher of capacity 9 litre (ISI marked) with and including all accessories, complete all as specified and directed, Make: Minimax, Firex, Cease Fire, Newage.
Dismainting of existing fire fighting post and PCC foundation including disposing off the rubish off the premises/site, complete all as specifed and directed.
M&L for cement concrete 1:2:4 type B1 (using 20 mm graded stone aggregates) as in foundation and plateform for fire fighting posts etc, including use & waste of necessary formwork, weathering, slightly rounded or chamfered angles and throating, complete all as specified and as directed.
M&L for Preparation of new steel and iron surfaces of any description, over 10 cm in width or girth , not otherwise described and painting with two coats of synthetic enamel paint (red tint) over a coat of red oxide primer, complete all as specified and as directed.
S&F mild steel rolled sections [Fe 410-W (Gde E-250) quality - B] and mild steel sheet as in fire fighting posts etc, , includng welding or riveting etc, complete all as specified and as directed.
M&L for carrying out the Periodical Check and Preventive Maintenance as detailed below (interval between each of the periodical check and preventive maintenace shall not exceed 03 months) for the entire system Comprising of the 27 Nos of existing HT VCB, 11 KV, 630/ 400 Amps, 50 Hz with VCB Panel etc, CG/ Kirloskar make at 33 KV/11 MRS, complete all as specified and as directed :- (i) Checking the closing & opening operation of VCB and functional checks and carrying out Repairs/ Replacement (as directed) of the defective components. (ii) Overhauling and Calibration of relays (secondary injection/Primary injection on each multiple setting of relays). (iii) Setting, coordination and testing through primary injecction of relays. (iv) Checking and recording of IR value of VCB trolley and panel. (v) Checking/repairing/rectification of the power/control wiring. (vi) Replacement of panel heater 80 watt. (vii) Replacement of worn out bushing of PT/Busbar support insulators. (viii) Replacement of unserviceable & Open circuit of CT's, and testing of polarities of CT's. (ix) Checking fibre plates, gaskets, transformer oil and applying multi grease to the mechanical parts & dry graphite conductive sealant to contacts of PT etc. & re-assembling the same and commissioning complete to the entire satisfaction of GE. (x) Testing of Volt Meter & Ammeter. (xi) High voltage testing with high voltage tester of CT & Breaker pole to withstand working pressure of HT 11 KV to ascertain servicieability; spare parts found defective to be replaced for smooth functioning as directed by GE. (xii) Opening the busbar chamber of HT, 11KV, VCB panel board, cleaning the bus bar chamber, inspecting the CT's wiring, spout insulator & bus-bar joints & tightening if required & heating up with hot air blower to remove moisture, meggering, HV testing, applying TRTPPEX(B) to the surfaces of bus bar & commissioning, complete all as specified & directed by GE. (xiii) The servicing, overahauling and testing of 11 KV indoor VCB Panel (including for Breakers), shall be got done by the contractor from the authorised agency/ Rep of OEM (CG/ Kirloskar) or State Electricity Board as approved by the GE.
Notes for Item No 49:- (i) Cost of all the materials, labour, travelling charges, providing Food & Accn to the Rep of OEM and other elements to make the entire system servicable, shall be deemed to be included in the quoted rates and only payment for supply only of the items listed at Ser No 51 to 92 here-in-below, shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items /materials shall be as specified in the item(s) and in case not specified, the same shall be of make C.G/ Kirloskar or as per existing make, suitable to match with the existing VCB system, as approved by the GE. (ii) The periodicity for carrying out the periodic check & preventive maintenance as per the scope included in the above item shall be 03 months. Unit of the payment for carrying out each of the periodic check & maintenance at interval of 03 months shall be considered as “Each Job” for the Entire System. Further, in case, the periodic check & preventive maintenance is required to be carried out, at a interval of less than 03 months, due to development of any defect or due to any reasons, whatsoever may be, as per the direction of the GE, the same shall also be carried out by the contractor, for which, no payment shall be admissible and the cost thereof, shall be deemed to be included in the quoted rate of above item. (iii) After carrying out each of the periodical check and maintenance, the contractor shall submit the Servicability and Recommendetion Certificate from the Rep / Agency of OEM (CG/Kirloskar) or State Electricity Board (as applicable) for further improvement of the system. (iv) Immediately after issue of Work-Order, the Periodic Check & Preventive Maintenance included in the above item & its connected items, shall be commenced by the contractor, simultaneously to the other repairs/ works as directed by the GE.
Supply only LED indicating lamps RED for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only LED indicating lamps YELLOW for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only LED indicating lamps Blue for VCB 11000 Volt, of 630/ 400 Amps,complete all as specified and as directed.
Supply only LED indicating lamps Amber for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only LED indicating lamps white for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only LED indicating lamps green for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only trip circuit push button with NO contacts suitable for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only spring charging motor 230VAC suitable for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only limit switch suitable for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only ZZ, microswitch suitable for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only big gear assembly suitable for VCB 11000 Volt, of 630/400 Amps,complete all as specified and as directed.
Supply only small gear assembly suitable for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only tripping shaft assembly suitable for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only closing shaft assembly suitable for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only segment gear suitable for VCB 11000 Volt, of 630/ 400 Amps, complete all as specified and as directed.
Supply only PT fuse for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only spring charging handle for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only breaker rack in rack out handle for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only CT(Epoxy type) ratio 100/5+5A for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only PT, 3 phase, 110-30 Volt for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only closing coil assembly 30VDC for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only tripping coil assembly 30VDC for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only closing coil assembly 110VDC for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only tripping coil assembly 110VDC for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only plug & sockect for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only 7NO+7NC Auxiliary switch for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only space heater 100W for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only thermostat for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only HRC control fuse 2A,4A,6A,10A for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only terminal block for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only breaker control for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only complete breaker mechanism assembly for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only ON/OFF push button plate assembly for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only breeze rectifier for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only fuse base with carrier for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only test & service switch for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only vaccum interceptor for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only timer for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only hooter for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only power pack unit 230VAC/30VDC for VCB 11000 Volt, of 630/400 Amps, complete all as specified and as directed.
Supply only, 3 phase, Over Current (low/high set) + Earth Fault (low/high set) with inrush current protection, single phasing protection conductor broken, negativve phase sequence, breker failure draw out type relay, front USB port and back RS485 port for existing 11 KV indoor VCB panel with High Set with IDMT and INST characteristics having aux. supply (V) of 18-250V AC/DC, rated volt 250 VAC / 30 or 110 VDC, Make:- CG/ ABB/ Seimens/Schneider as approved by the GE. Note:- Cost of all necessary arrangement for fixing/accomdating new relays in exisitng 11 KV VCB panel including cutting/casing,control wiring etc will be deemed to be included in quoted rate of item No.49.
Supply only, 3 phase, master Relay (for existing 33 KV indoor VCB panel) with contact 3 NO + 2 NC having aux supply of 110 VDC, Make:- CG/ ABB/ Seimens/Schneider as approved by the GE. Note:- Cost of all necessary arrangement for fixing/accomdating new relays in exisitng 33 KV VCB panel including cutting/casing,control wiring etc will be deemed to be included in quoted rate of item No.49.
M&L for carrying out the Periodical check and preventive maintenance, as detailed below (interval between each of the periodic check and preventive maintenance shall not exceed 03 months) for the entire system comprising of the 4 Nos. of existing HT VCB/SF-6 breaker, 33 KV, 1250 Amps, 25 kA with VCB/SF6 Panel etc, CG/Kirloskar make at 33/11 KV MRS, complete all as specified and as directed. :- (a) Servicing (i.e light primary terminals) & carrying out repair/replacement (as directed) of defective components. (b) Functional checks. (c) Mechanisum servicing and lubrication. (d) Gas leak check. (e) Protection checks (Gas density switch operation) (f) Control wiring tightness. (g) Power connection tightness. (h) Insulation measurement of main circuit. (j) Contact resistance of main circuit. (k) Check oil leak of absorber. (l) Checking the operation of VCB/SF6 breaker. (m) Overhauling and Calibration of O/C & E/F relays,Aux relay,Buch ,OTI,WTI. Alarm, Aux relay, Buch, OTI, WTI, trip, Master trip replay (through primary injection/ secondary injection), testing on each multiple setting of relay. (n) Checking and recording of IR value of breaker trolley. (o) Checking/repairing/rectification of the control wiring. (p) Checking &repairing/ replacement (as directed) of the Panel Heater & Space Heater. (q) Replacement of the unserviceable open circuit of CT's. (r) Testing of CT & PT and their circuit. (s) Cleaning the breaker externally and internally thoroughly with lint free cloth, complete all as specified & directed . (t) High voltage testing with high voltage tester of CT & Breaker pole to withstand working pressure HT 33 KV to acertain servicieability; spare parts found defective to be replaced for smooth functioning as directed by GE. (u) The servicing, overahauling and testing of 33 KV outdoor SF 6/VCB panel (including breakers)shall be gote done by the contractor from the authorised Agency /Rep of OEM (CG/Kirloskar) or State Electricity Board as approved by the GE.
Notes for Item No 93:- (i) Cost of all the materials, labour, travel charges, providing of Food & Accn to the Rep of OEM and other elements to make the entire system servicable shall be deemed to be included in the quoted rates and only payment for supply only of the items listed at ser No 95 to 106 here-in-below shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items /materials shall be as specified in the item(s) and in case not specified, the same shall be of make CG/Kirloskar or as per existing make, suitable to match with the existing VCB system as approved by the GE. (ii) The periodicity for carrying out the periodic check & preventive maintenance as per the scope included in the above item shall be 03 months. Unit of the payment for carrying out each of the periodic check & maintenance at interval of 03 months shall be considered as “Each Job” for the Entire System. Further, in case, the periodic check & preventive maintenance is required to be carried out, at a interval of less than 03 months, due to development of any defect or due to any reasons, whatsoever may be, as per the direction of the GE, the same shall also be carried out by the contractor, for which, no payment shall be admissible and the cost thereof, shall be deemed to be included in the quoted rate of above item. (iii) After carrying out each of the periodical check and maintenance, the contractor shall submit the Servicability and Recommendetion Certificate from the Rep / Agency of OEM (CG/Kirloskar) or State Electricity Board as approved by the GE for further improvement of the system. (iv) Immediately after issue of Work-Order, the Periodic Check & Preventive Maintenance included in the above item & its connected items, shall be commenced by the contractor, simultaneously to the other repairs/ works as directed by the GE.
Supply only ratchet wheel assembly for 33KV VCB/SF-6 breaker 1250 Amp, 25 KA, complete all as specified and as directed.
Supply only powell set for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only closing latch assembly for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only tripping latch assembly for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only crank lever with bolt for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only set up 'O' ring for pole for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only SF6 gas pressure gauge for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only DC auxiliary 110V DC contactor for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only motor contactor 110V DC for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only motor cut off limit switch(Cherry type) for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only closing coil assembly 110 V DC for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
Supply only tripping coil assembly 110 V DC for 33KV VCB/SF-6 breaker, 630/400 Amp, 26.3 KA, complete all as specified and as directed.
S&F in repairs Breaker control switch (Trip-Neutral-close), TNC with 2NO + 2NC SPR RTN, Cat part No 72009 of make L&T or of any other equivalent make as approved by the GE, complete all as specified and directed.
S&F in repairs Electric rubber hand gloves suitable for working pressure 11 KV. Make :- Jaipuria brothers or of any other equivalent make as approved by the GE, complete all as specified and directed.
S&F in repairs Electric rubber hand gloves suitable for working pressure 33 KV. Make :- Jaipuria brothers or of any other equivalent make as approved by the GE, complete all as specified and directed.
S&F in repair of telescopic pole, 5.5m with & tree pruning saw for sawing and shearing, complete all as specified and directed.
M&L for earth continuity conductor or main earthing lead of size 32X6 mm galvanized iron strip fixed to wall on batten or recess or chases or burried in ground or drawn in existing conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc including dismantling of existing one, complete all as specified and directed. Note :- Excavation and earth work shall be measured and paid for separately.
Supply, laying, testing PVC insulated, PVC sheathed cable, galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of following size, 1100 Volts grade, in the trenches /ducts/along wall / floor /pole/equipment /on floor etc, including taking out of existing cable, complete all as specified and directed.
12 core 2.5 Sqmm
19 core 2.5 Sqmm
2 core 2.5 Sqmm
4 core 2.5 Sqmm Note:-Excavation and earth work, sand cushioning, protection covers shall be measured and paid for separately.
S & F in replacement of Cell tubular for battery bank, 2 V , 100 AH, making including connection with and including necessary suitable cable or bus bar strip, complete all as specified and directed, Make: - Exide powersafe or equivalent as approved by the GE.
S & F in replacement of seal maintenance free battery for battery bank 12 V , 165 AH, making connection with and including necessary suitable cable or bus bar strip, complete all as specified and directed, Make: - Exide powersafe or equivalent as approved by the GE.
Surface dressing averaging 15cm depth in soft/loose soil for cleaning and cutting/removal of green vegetation, subsequent to above, spreading thin layer of anti vegetation chemical as per the manufacturer’s instructions (make of the chemical shall be as approved by the GE) inside and around the installations premises and removal & disposing off of the soil outside of the installation premises, complete all as specified and directed. Note :- The surface cleaning shall normally be done once in three months for the Sub-Stations as ordered. Payment for each time shall be made for separately as per the actual work done at site.
Carrying out testing of Earth Resistance of existing Earthings as and when required as per IS 3043 (1987) & SSR part-I Para 19.146 using earth resistance testing equipments as directed by the GE and producing the test results duly recorded, complete all as specified and directed:- Notes:- (i) The contractor is required to carry out the Earth Test complete in all respects. (ii) All test results indicating the date of testing duly authinticated/ signed by the JE & Engr-in-Charge on the same day of testing shall be entered in a register properly bound and shall also be submitted by the contractor to the Engr-In-Charge before claiming /releasing of payment. (iii) For the purpose of testing, contractor shall deploy all equipments and apparatus/instruments at his own cost, all as directed by the Engr-In-Charge. (iv) Minimum 75 Nos of Earth testing shall be carried out in every three months. For payment purpose, 75 Nos of tests or more tests as carried out during the period of 3 months as per the direction of GE, shall be considered as "Each Job".
Testing of battery of existing Battery bank and battery charger as and when required using testing equipments including changing of terminals, greasing of terminals and pouring of distilled water (cost of water is also included in the scope) as directed by the GE and producing the test result duly recorded, complete all as specified and directed:- Notes:- (i) The contractor is required to carry out the battery testing complete in all respects. (ii) Testing of all battery in the battery bank shall be measured as 'one unit'. (iii) All test results indicating the date of testing shall be entered in a register properly bound & covered duly authenticated/signed by the JE & Engr-in-Charge on the date of testing itself and shall also be submitted by the contractor to the Engr-In-Charge before claiming/releasing of payment. (iv) For the purpose of testing, contractor shall deploy all equipments and apparatus/instruments at his own cost all as directed by the Engr-in-Charge.
Supply, fixing & testing, in repair, 33 KV, single phase, out door, oil cooled, Current Transformer of ratio 200-100-50/5-5 Amp, class 1.0-5P, 10 burden, 15 VA insulation, 70/170 KV, including first filling of transformer/ insulation oil conforming to IS:335 and of dielectric strength 40 KV as per IS 1866, complete all as specified and as directed.
Supply, fixing & testing, in repairs, 33 KV, 50 HZ, oil immersed, Potential Transformer for metering and protection, single phase, outdoor type, ratio 33000/110/^3 volt, rated burden 200 VA, accuracy class 3, Phase as per IS:3156 for protection with & including first filling of transformer/insulation oil conforming to IS : 335 and of dielectric strength 40 KV as per IS 1866, complete with & including all accessories, mounted with & including provision of new bolts, nuts, check nuts, washers etc on the existing fabricated steel structure and also making connection, complete all as specified and as directed.
Checking of all 3 phase in electric panel phase wise (RYB) and distribution of the load equally balanced, maintaining the record of the above in a Register duly authinticated & signed by the JE, also producing the records to the Engr-in-Charge for his authintication/signatures, complete all as specified and directed.
Disconnection of HT and LT connection of the RMU (Make : Siemens), repairing of locking system, testing and meggering of VCB, testing meters, complete testing of internal wiring, replacement of fault wirings, replacement of unserviceable 11 KV boots, cleaning of bus bars and burnt parts of the RMU complete using Petroleum Jelly and CRC 80 Spray etc and testing of RMU after carrying out the repairs as per above, complete all as specified and directed: Notes:- (i) Cost of all the materials, labour and other elements to make the entire system servicable by the Rep of OEM during the entire contract period shall be deemed to be included in the quoted rates and only payment for supply only of the items listed at ser No 124 here-in-below shall be measured and paid for separately in case these are ordered and provided as directed. The make of the items /materials shall be as specified in the item(s) and in case not specified, the same shall be of make Seneider/CG/Kirloskar or as per existing suitable to match with the existing RMU system as approved by the GE.
Supply only 11 KV boots, complete all as specified and as directed.
M&L for carrying out the under mentioned tests in the transformers of make Schneider/ ALSTOM/ CG, stepdown 33/11 KV, 2 MVA to 3 MVA capacity at existing position on platform at 33/11 KV MRS :- (i) I R Value Test (ii) P I Value Test (iii) Magnetic Core Balance Test. (iv) Magnetising Current Test. (v) Vector group test (vi) Winding Resistance Test (vi) High Voltage Test (vii) BDV, PPM & Acidity, Sludge Test. Notes : (i) The testing shall be got done by the contractor from the Authorised Agency/Rep. of OEM CG/ Schneider/ ALSTOM/ Kirloskar or State Electricity Board as approved by the GE. Cost of deploying all the testing equipments, labour, skilled tradesman, Engineer(s), transportation for testing eqpt, travelling charges, providing Food & Accn to the Rep of OEM during the entire period of the testing shall be deemed to be included in the quoted rates. (ii) After testing, the contractor shall submit the test report of transformer from the auth Rep / agency or State Electricity Board, as applicable. In the test Report, repairs, if any required and all other aspects with complete details for serviceablity & for further improvement of the system, shall also be included.
M&L for carrying out the under mentioned tests in the transformers of make : ALSTOM/ Schneider, step-down 33/11 KV, 2 MVA to 3 MVA capacity at existing position on platform at 33/11 KV MRS :- (i) Partial Discharge test (PD). (ii) Tan-Delta test of HV side and LV side. Notes : - (i) The testing shall be got done by the contractor from the authorised Agency/Rep of OEM CG/Schneider/Alstrom/Kirloskar or State Electricity Board as approved by the GE. Cost of deploying all the testing equipments, labour, skilled tradesman, Engineer (S), transportation for testing eqpt, travelling charges, providing Food & Accn to the Rep of OEM during the entire period of the testing shall be deemed to be included in the quoted rates. (ii) After testing, the contractor shall submit the test report of transformer from the auth Rep/Agency or State Electricity Board, as applicable. In the test Report, repairs, if any required and all other aspects-with complete details for serviceability & for further improvement of the system, shall also be included. (iii) This item shall be operated only in case advised through the test report of item No 125 and as well as if approved by the SEI.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .