TECHNICAL
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of [V/N or 'V' whichever is less; where V = Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The tenderer must submit a valid Electrical Contractor license as per Indian Electricity Rules for the respective category of works issued by the Government Electrical License Board on or before the closing date of the tender. A copy of which should be submitted along with the tender offer; otherwise, the tender will be summarily rejected.
The Similar nature of works for this instant tender shall be "Supply, installation, testing and commissioning of any LT/HT electrical work." The tenderer should have executed the similar nature of works in Central /State Government department or PSUs of Central /State Government."
51 conditions · 4 needing a document upload
Whether the cost of earnest money deposited
Whether cost of tender document deposited.
Migration to GST regime - Special Tender Conditions: The rates should clearly indicate the rate of applicable duties and taxes included in the prices quoted by them. Any variation in tax structure/ rate due to introduction of GST, shall be dealt with under Statutory Variation Clause. It should be ensure that bidders/tenderers are GST compliant and quoted tax structure/rates are as per GST Law.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Contractor should submit the GSTIN number and same should be mentioned in the bills along with a copy of GSTIN registration certificate while submitting the bills to accounts for audit and payment, As GST is scheduled to implemented wef 01.07.2017. Without GSTN, no bill will be accepted w.e.f. 01.07.2017
From 01.07.2017 GST has been implemented but the detail guideline is still not clear. Hence, new tax structure on materials and labour will be applicable to both Railway & contractor after getting proper notification
Payment of Earnest Money deposit (EMD) , in respect of e- tendering,should be accepted through net banking or online payment gateway only
At GHY: Electrical work for extension of Running room(Electrical portion) & Construction of additional 60 bedded RCC Building Loco Running Room at LMG. (Electrical portion)
EL-LM-25-26-39~NFR
EL-LM-25-26-39
Open
Works - General
120 Days
Hojai, Assam
₹0
₹1.7 L
16 Mar 2026
17 Feb 2026
2 Mar 2026
210 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 45,35,462.07 | ||
| — | 1.00 | — | — | ||
| Supply, Installation, testing and commissioning of Outdoor Cast Resin Oil Type11KV/433V 500 KVA transformer, (BIS Level-1 as per Amendment 4 ) 3Phase,50Hz, Dyn11, copper wound, Class A insulation associated with winding temperature indicator / controller, having cable termination on the HV & LV sidesand all accessories and conforming to IS 2026 part 11. Technical specification as per technical specification attached in tender document. | — | — | — | 10,23,060 | |
| — | 1.00 | — | — | ||
| Construction of 4 pole structure by supply, erection, fixing of the following GI channel and angle clamp with pole by 50 x 5mm GI flat with 50 x 16 mm diameter bolt and nut including making of hole by drill as per requirement with anti climbing device shall be provided by GI Barbed wire along with 33 KV danger board of size 8 x6 showing the voltage grade ,skull symbol etc. (i)GI Channel(100 x 50 x 50 x 6 x2200)mm=4 nos. conductor bracket (ii) GI Angle50x50x6x2200mm=8 nos.bracing (iii) GI Channel (75 x40 x 40 x 6 x 2200mm=2 nos.guard wire (iv) GI Angle50x50x6x3200mm=8 nos.cross bracing. All materials shall be hot dip galvanized as per relevant IS standards. Fabrication and erection shall be carried out as per approved drawing and direction of Engineer-in-Charge. All fasteners shall be galvanized. Work shall include all labour, tools, tackles and incidental charges required for completion. | — | — | — | 16,140.6 | |
| — | 4.00 | — | — | ||
| Supply, erection and commissioning of 12 metre long GI Tubular Pole, Type 410 SP- 63, conforming to IS: 2713 - 1980 (latest amendment), complete with base plate and top cap.Pole Details-Overall Length: 12 Metres,Sectional Length: 5.8 m + 3.1 m + 3.1 m,Outside Diameter (Bottom to Top):193.7 mm,165.1 mm,139.7 mm,Sectional Thickness:4.85 mm,4.50 mm,4.50 mm. Material: Hot dip galvanized steel. Complete with suitable size base plate and top cap.Erection & Foundation:Excavation of pit to a depth equal to 1/5th of the total pole height (i.e., approx. 2.4 m).Providing and laying Cement Concrete (CC) foundation in ratio 1:2:4 (1 Cement : 2 Sand : 4 graded stone aggregate of 19 mm and down size).The CC block shall be 30 cm x 30 cm in cross- section, extending:From bottom of pole foundation Up to 30 cm above Ground Level (GL).Proper alignment, ramming, curing and finishing shall be done.Backfilling and compaction shall be carried out properly as per direction of Engineer-in-Charge | — | — | — | 97,945.12 | |
| — | 4.00 | — | — | ||
| Erection of rail/tubular pole to 1/5 th of its height with a CC foundation from base block (30 cm x 30 cm x 15 cm), including digging & refilling of earth to a height of 30 cm above ground level in ratio 1:3:6 by cement sand & Chips 19 mm & down including excavation of earth . | — | — | — | 5,498.72 | |
| — | 1.00 | — | — | ||
| Supply, installation , testing and commissioning of Triple pole Air- break Gang Operating air break off load disconnecting switch (GOS) 11 KV 400 Amp. complete with drop out fuses, 3 insulator triple pole each pole consists of galvanize steel base HT insulator as per BIS non ferrous knife and spring loaded contact arcing horn of adequate section to break magnetizing current of the transformer horizontal GI shaft/ pipe of adequate length for phase separator, adequate length for operation from ground level and operation handle complete with locking arrangement in both OFF & ON position. All ferrous parts shall be hot dip galvanized and suitable for outdoor service conditions. Fuse shall be conforming to IS:9385 part-I/1979, GOS shall be conforming to IS: 9921 Part-I/1981&9921 Part III/1982.complete with operating rod , drop out fuse and locking arrangement etc. conforming to IS: 1811 1992 or latest including provision of mounting arrangement for GOS as req. The work includes supply, loading, unloading, erection on pole/structure, alignment, connection, testing and commissioning complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 8,802.23 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of lightning arrestor thyrite type conforming to IS: 3070 - Part III/1993 (Latest Version) suitable for protecting 11 KV installation including connection with earth pit by 25 mm x 6 mm GI strip and with overhead by ACSR conductor. The lightning arrestor shall be complete with suitable mounting arrangement for pole/structure installation. The item shall include connection to earth pit using 25 mm x 6 mm GI strip and connection to overhead line using suitable size ACSR conductor, including all necessary clamps, nuts, bolts and accessories required for complete installation.All ferrous parts shall be hot dip galvanized and suitable for outdoor service conditions.The scope includes supply, loading, unloading, erection, connection, testing and commissioning complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 7,196.49 | |
| — | 30.00 | — | — | ||
| Supply and erection of CC foundation in ratio 1:2:4 cement,sand and good quality chips of size 19 mm and down size at site, including mixing, laying, compacting, curing and finishing complete as required.The work shall include all labour, materials, tools, tackles, centering/shuttering (if required), curing and incidental charges necessary for completion of foundation work. The concrete shall be laid to required size, shape and level as per site condition and as directed by the Engineer-in-Charge of Railway.Complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 48,683.7 | |
| — | 50.00 | — | — | ||
| Provision of Horizontal Directional Drilling (HDD) / Horizontal boring using suitable HDD machine for crossing of road/Railway track embankment, at a minimum distance of 6 metres from embankment Ground Level (GL) and at a depth of not less than 2 metres below Ground Level, as required.The work shall include preparation of site, setting out, drilling of 200 mm diameter bore, insertion/placing of protective pipe for electric cable through contractor's own arrangement, alignment, pulling and necessary precautions to avoid damage to road/track structure.The item includes all labour, machinery, fuel, consumables, equipment, supervision and incidental charges required for completion of work, complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 1,77,696.5 | |
| — | 50.00 | — | — | ||
| Supply, laying, fitting and fixing of 200 mm diameter heavy duty Cast Iron (CI) pipe conforming to IS: 1536 (latest amendment)for protection of cable under track crossing/under road crossing, including cutting, jointing, alignment and fixing in position.The work shall include all necessary accessories such as collars, sockets, lead/jute yarn or rubber gasket (as applicable), excavation (if required), backfilling, alignment and proper positioning of pipe for safe cable protection.The pipe shall be of approved quality and suitable for underground installation.Complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 62,810 | |
| — | 250.00 | — | — | ||
| Excavation of cable trench of size 1.0 metre depth x 0.5 metre width below Ground Level (GL) in all types of soil, including dressing, leveling and preparation of trench bottom.The work shall include laying of armoured cable in the trench, providing sand cushioning, brick protection on top of cable, and refilling the trench with excavated soil in layers with proper ramming and compaction .The item also includes supply and fixing of suitable size crimping lugs for termination of armoured cable, proper jointing/termination, connection, testing and commissioning complete in all respects. All materials such as sand, bricks, lugs and other consumables shall be supplied by the contractor .Complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 30,447.5 | |
| — | 50.00 | — | — | ||
| Supply erection of reinforced cement concrete Cable Trench made of Cement Bricks with Cement plaster and the RCC Cover. The Cable trench should be in ratio 1:3:6 by cement,Sand and Ships of size 19 mm.including digging of pit to 500mm and MS rod of Suitable size. The item includes supply of all materials, labour, reinforcement steel, shuttering, curing and all incidental works required for completion of cable trench.Complete in all respects as per direction of Engineer- in-Charge at site. | — | — | — | 50,193.5 | |
| — | 250.00 | — | — | ||
| Supply, laying, fitting and commissioning of 110 mm (OD) diameter Double Wall Corrugated (DWC) HDPE pipe, PN-6.0 kg/cm², conforming to IS: 14930 (Part-II) - latest amendment, suitable for cable protection, laid partly over ground and partly underground.The work shall include supply of pipe with all necessary accessories such as sockets, bends, couplers, end caps, reducers (if required), cutting, jointing, alignment and proper fixing in position.For underground portion, excavation (if required), laying at required depth, backfilling and compaction shall be carried out. For over ground portion, proper clamping/support arrangement shall be provided.The item includes all labour, materials, tools, tackles and incidental charges required for complete installation and commissioning. Complete in all respects as per direction of Engineer-in-Charge at site. | — | — | — | 68,662.5 | |
| — | 1000.00 | — | — | ||
| Supply and wiring of sub-main line with 2 x 2.5 sq.mm PVC insulated, unsheathed, multi-stranded FRLS copper conductor cable, conforming to IS: 694 (latest amendment), laid through suitable size PVC concealed rigid conduit pipe.The work shall include providing and drawing of 1 x 1.0 sq.mm unsheathed copper conductor as earth continuity wire along with phase and neutral conductors.All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 62,670 | |
| — | 800.00 | — | — | ||
| Supply and wiring of sub-main line with 2 x 4 sq.mm PVC insulated, unsheathed, multi-stranded FRLS copper conductor cable, conforming to IS: 694/1990 (latest amendment), laid through suitable size PVC concealed rigid conduit pipe.The work shall include providing and drawing of 1 x 1.0 sq.mm unsheathed copper conductor as earth continuity wire along with phase and neutral conductors.All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 61,616 | |
| — | 500.00 | — | — | ||
| Supply and wiring of sub-main line with 2 x 6 sq.mm PVC insulated, unsheathed, multi-stranded FRLS copper conductor cable, conforming to IS: 694/1990 (latest amendment), laid through suitable size PVC concealed rigid conduit pipe.The work shall include providing and drawing of 1 x 1.0 sq.mm unsheathed copper conductor as earth continuity wire along with phase and neutral conductors.All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 49,840 | |
| — | 2500.00 | — | — | ||
| Supply, laying, testing and commissioning of 10 sq mm single core copper conductor PVC insulated, FR/FRLS grade cable, 1100V grade, conforming to IS 694, drawn through concealed rigid PVC conduit in wall/ceiling including all accessories. All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 3,57,125 | |
| — | 180.00 | — | — | ||
| Supply of materials and wiring of light point through concealed wiring by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch(with indicator type) to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes.(i.e thickness of mounting boxes of 3 mm and inside width of box should be 50 mm). All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. Make - Cable- Finolex, Havells, KEI, Polycab Casing & Capping/Conduit - Diamond, Presto Plast, Richa C/Rose & Switch - Crabtree, Anchor, Legrand.All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 76,743 | |
| — | 40.00 | — | — | ||
| Supply of materials and wiring of fan point through concealed wiring by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sqmm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch(with fan marking) and module type step fan regulator of 100 W to beprovided on good quality modular plate and frame ofsuitable sizes and mounting box of proper sizes.(i.ethickness of mounting boxes of 3 mm and inside width of boxshould be 50 mm). All othernecessary accessories i.e PVCTee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface.All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 20,071.2 | |
| — | 10.00 | — | — | ||
| Supply, Wiring of concealed exhaust fan point by PVC insulated unsheathed and multi stranded FRLS Copper Cable 1.5sq.mm S/C confirming to IS - 694/1990 through suitable size (19 mm) of PVC Concealed rigid Conduit pipe of wall thickness 2mm including ceiling rose and 10 AX one way modular switch in 1/2 M concealed unbreakable GI modular box, 2 M cover plate etc. with 1sq. mm unsheathed copper cable as earth continuity wire. All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 3,129 | |
| — | 70.00 | — | — | ||
| Supply of materials and wiring of 6 amps plug point through concealed wiring by 1.5 sqmm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single corePVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch (with indicator type) and 2 modular 6Amps 5 Pin universal socket to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes.(i.e thickness of mounting boxes of 3mm and inside width of box should be 50mm). All other necessary accessories i.e PVCTee, Bend etc will be supplied by contractor.After concealed if needed than the concealed portion will be painted by contractor as persite colour of the surface. All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 22,135.4 | |
| — | 15.00 | — | — | ||
| "Supply of materials and wiring of 16 amps plug point through concealed wiring by 4 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 16 amps controlling switch(with indicator type) and 3 modular 16 Amps 6 Pin universal socket to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes. (i.e thickness of mounting boxes of 3 mm and inside width of box should be 50 mm). All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. All work shall be carried out as per direction of Engineer-in-Charge at site. | — | — | — | 6,239.85 | |
| — | 10.00 | — | — | ||
| Supply, fitting, fixing, connection & commissioning of 300 mm sweep heavy duty exhaust fan. All consumables regarding fixing arrangement will be supplied by the contractor as per the direction of engineer in charge at site. | — | — | — | 13,071.5 | |
| — | 10.00 | — | — | ||
| Supply; Wiring of concealed exhaust/wall bracket fan point by PVC insulated unsheathed and multi stranded FRLS Copper Cable 1.5sq.mm S/C confirming to IS - 694/1990 through suitable size (19 mm) of PVC Concealed rigid Conduit pipe of wall thickness 2mm including ceiling rose and 10 AX one way modular switch in 1/2 M concealed unbreakable GI modular box, 2 M cover plate etc. with 1sq. mm unsheathed copper cable as earth continuity wire. | — | — | — | 3,129 | |
| — | 50.00 | — | — | ||
| Supply of materials and wiring of modular type mobile charging through concealed/surface wiring with mobile keeping tray by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealedrigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch 3 no and 6/10 amp 5 pin modular socket 3 nos to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper size (i.e. thickness of mounting boxes of 3 mm and inside width of box should be 50 mm).All other accessories i.e. PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site color of the surface. | — | — | — | 36,756.5 | |
| — | 50.00 | — | — | ||
| Supply, installation, testing and commissioning of 36 Watt LED recess mounting 2'x2' flat panel luminaire, suitable for installation in false ceiling and operation on 230V, 50Hz AC supply, complete with electronic constant current driver, high transmission diffuser, CRCA powder-coated housing/frame, heat sink, flexible copper conductor connecting cable, ceiling rose and all mounting accessories, including connection to existing wiring and testing complete as required at site. Technical Parameters: (i) Rated Wattage: 36 W (ii) Luminous Flux: Minimum 3600 lumens (iii) Luminous Efficacy: 100 lm/W (iv) Power Factor: 0.95 (v) THD: 10% (vi) CRI: 80 (vii) CCT: 4000K / 6500K (as specified) (viii) Input Voltage: 140-270V AC (ix) Surge Protection: 2.5 kV (x) LED Life: Minimum 50,000 hours (L70) (xi) IP Rating: IP20 (indoor) (xii) Warranty: Minimum 2-3 years | — | — | — | 1,05,932 | |
| — | 50.00 | — | — | ||
| Supply, fitting, fixing, connection and commissioning of 18/20 Watt LED indoor batten fitting, complete set with LED tube, electronic driver, housing, end caps and all accessories, suitable for operation on 230V, 50Hz AC supply. The fitting shall be connected with 1.5 sq.mm FR PVC insulated flexible copper conductor wire drawn through PVC pipe/casing & capping as required at site, including connection to existing wiring, testing and commissioning complete as required. | — | — | — | 15,710 | |
| — | 16.00 | — | — | ||
| Supply, erection, testing and commissioning of heavy-duty 400 mm sweep wall bracket fan, suitable for operation on single phase 230V, 50Hz AC supply, complete with motor, blades, mounting bracket, guard, regulator (electronic step type), necessary clamps, nuts, bolts, foundation fasteners and allied minor engineering works including drilling, grouting and connection to existing wiring, complete as directed by Site Engineer. Technical Parameters: (i) Sweep: 400 mm (ii) Rated Voltage: 230V AC, Single Phase, 50 Hz (iii) Power Consumption: 75-90 Watts (iv) Speed: Minimum 1300 RPM (v) Air Delivery: Minimum 70-80 CMM (vi) Motor: Copper wound motor with thermal overload protection (vii) Bearing: Double ball bearing (viii) Body: Powder-coated metal body with heavy-duty mounting bracket (ix) Duty: Continuous rating (x) Warranty: Minimum 2 years | — | — | — | 20,884.8 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing and commissioning of 3 kW, 25 litres capacity, 5-Star rated storage type water heater (Geyser) suitable for operation on 230V, single phase, 50Hz AC supply, complete with inner tank, heating element, thermostat, safety valve, mounting bracket, inlet & outlet connections, necessary fasteners, connection to existing water line and electrical wiring including earthing, testing and commissioning complete as directed by Site Engineer. Technical Parameters: 1.Capacity: 25 Litres 2.Rated Power: 3 kW 3.Voltage: 230V ±10%, Single Phase, 50 Hz 4.Energy Rating: 5 Star (as per BEE latest notification) 5.Inner Tank: Glass-lined / Porcelain enamel coated with corrosion protection 6.Heating Element: Copper / Incoloy heating element 7.Thermostat: Adjustable thermostat with automatic thermal cut-out 8.Safety: oMultifunction safety valve (pressure relief) oOverheat protection oDry heating protection 9.Working Pressure: Minimum 8 bar (suitable for multi-storey buildings) 10.Insulation: High density PUF insulation 11.IP Rating: Minimum IPX4 12.Warranty: •Inner Tank: Minimum 5 years •Heating Element: Minimum 2-3 years •Product: Minimum 2 years. | — | — | — | 1,64,900 | |
| — | 10.00 | — | — | ||
| Supply and wiring of geyser point complete with 15/16 Amp socket outlet, 16 Amp DP MCB for overload and short circuit protection, suitable for 230V, single phase, 50Hz AC supply. The point shall be wired with 4 sq.mm single core PVC insulated FRLSH copper conductor flexible industrial unsheathed cable for phase and neutral, drawn through heavy duty PVC rigid concealed conduit pipe including necessary accessories such as PVC bends, tees, junction boxes, saddles etc. The earth continuity conductor shall be 1 sq.mm single core PVC insulated unsheathed flexible copper wire drawn along with the circuit wiring. The work includes making necessary wall chases, fixing conduit, box, accessories, proper termination, connection to existing distribution board, testing and commissioning complete. The concealed portion after wiring shall be properly plastered and finished; if required, the surface shall be painted by the contractor to match the existing surface colour, complete as directed by Site Engineer. | — | — | — | 4,689.3 | |
| — | 26.00 | — | — | ||
| Supply & wiring of RAC (Room Air Conditioner) point through suitable size (minimum 19 mm dia) heavy duty PVC concealed rigid conduit pipe, complete with wiring by 2 x 4 sq.mm PVC insulated, unsheathed, multi-stranded FRLS copper conductor cable for phase and neutral, drawn through conduit on wall, including 1 x 1 sq.mm PVC insulated unsheathed copper conductor as earth continuity wire. The point shall be complete with 1 No. 25A motor starter switch, 1 No. 32A SP Miniature Circuit Breaker (MCB), C-curve, minimum 3kA breaking capacity, and 1 No. heavy duty 3- pin shuttered socket outlet (6-16A type as specified), housed in concealed unbreakable GI modular box with modular plate/cover, including all accessories such as bends, tees, junction boxes, saddles, fasteners etc. | — | — | — | 23,218.78 | |
| — | 50.00 | — | — | ||
| Supply, fitting and fixing of 3 Watt concealed LED reading lamp, suitable for operation on 230V, 50Hz AC supply, complete with LED module, in-built driver, flexible neck (where applicable), housing, mounting box, necessary fasteners and accessories, including connection to existing wiring, testing and commissioning complete as required at site. •Rated Wattage: 3 Watts •Input Voltage: 140-270V AC •Luminous Flux: Minimum 180-250 lumens •Luminous Efficacy: 80-100 lm/W •Power Factor: 0.90 •THD: 20% •CRI: 80 •CCT: 3000K (Warm White) / 4000K (Neutral White) as specified •Beam Angle: 30°-60° focused beam •Body: Powder-coated aluminium / die-cast housing •LED Life: Minimum 30,000-50,000 burning hours •IP Rating: IP20 (indoor use) •Warranty: Minimum 2 years | — | — | — | 65,100 | |
| — | 40.00 | — | — | ||
| Supply, installation, testing and commissioning of 1200/1400 mm sweep decorative ceiling fan (as specified), BEE 5-Star rated, conforming to IS: 374 (latest amendment), complete with Brush Less Direct Current (BLDC) motor, suitable for operation on 230V, 50Hz, single phase AC supply, including 3 nos. aerodynamically designed blades, 30 cm down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, remote control/electronic regulator unit for speed control, safety pin, nuts, bolts, washers, earthing and all accessories, complete as required at site. Technical Specifications: 1.Sweep: 1200 mm / 1400 mm (as specified) 2.Standard: IS: 374 (latest amendment) & ISI marked 3.Energy Rating: BEE 5-Star rated 4.Motor Type: BLDC Motor 5.Input Voltage: 230V ±10%, 50 Hz, Single Phase 6.Power Factor: 0.90 7.Service Value: Minimum 6.00 (CM/M/W) 8.Air Delivery: Minimum 210 m³/min 9.Speed: Approx. 350 RPM (tolerance as per IS 374) 10.THD: 10% 11.Insulation Class: Class B 12.Temperature Rise: Maximum 75°C 13.Insulation Resistance: 2 Mega Ohm 14.Down Rod Length: 30 cm 15.Accessories: Shackle assembly, safety rope, canopy, remote/electronic regulator, complete fixing hardware 16.Warranty: Minimum 2-3 years | — | — | — | 1,09,200 | |
| — | 2.00 | — | — | ||
| Supply and erection of copper plate earthing station comprising of 600 mm x 600 mm x 6 mm thick copper earth plate buried in ground at a minimum depth of 3.0 metres below ground level (or as per site condition), including construction of earth pit chamber with brick masonry, RCC/Precast concrete cover with CI frame and cover, watering arrangement with GI pipe and funnel with wire mesh, alternate layers of charcoal/coke and common salt, complete as required. The earthing arrangement shall include 40 mm x 5 mm copper flat of 15 metre length for earth continuity conductor, securely connected to the earth plate with brass/copper nuts, bolts, washers etc., and extended up to the required equipment. The earthing terminal shall be connected to the neutral terminal of transformer and integrated with the system earthing network, complete as directed by Site Engineer. Technical Specifications Earth Plate: Copper plate 600 x 600 x 6 mm Depth of Burial: Minimum 3.0 m below ground level Earth Continuity Conductor: 40 x 5 mm copper flat, 15 m length Hardware: Brass/Copper nuts, bolts & washers Earth Pit Construction: Brick masonry chamber RCC/Precast concrete cover with CI frame Watering pipe with funnel & mesh Backfill Material: Charcoal/coke and salt in alternate layers Earth Resistance: Achieved value preferably 1 Ohm (or as specified) Testing: Earth resistance measurement using approved earth tester | — | — | — | 19,517.28 | |
| — | 20.00 | — | — | ||
| Supply and erection of earthing by 50 mm GI pipe, 4 mtr long 3.6 mm thickness including construction of earth pit, RCC earth cover slab with filling/mixing of salt, charcoal etc of required quantity and earth continuity by 25x3mm GI strip with GI nuts bolts washer etc. including welding, earth resistance flag etc. as per Drg. No. DRG No. PCEE-ELG-DRG-2024-1-Rev-1 Dt. 28.07.2025. The GI Strip ( should be welded with the earth pipe. The pipe is provided with at tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value. The connecting conductor from earth electrode to the distribution panel board should not be thinner than8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be pre casted RCC and The values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. | — | — | — | 32,196 | |
| — | 50.00 | — | — | ||
| SUPPLY OF MATERIAL, INSTALLATION, TESTING & COMMISSIONING OF MULTICOLOR LED BASE NAME BOARD :(Technical specification / salient features for LED name board ) :- 1. Power supply System:- It should be as under. Input: 230 Volt single phase A.C ± 5% Output : 12 Volt D.C. 2. a) Letters for name board shall be made in three languages i.e. English, Hindi & Assamese . b) Substrate material used for the front portion of channel letter shall be 3 mm thick Acrylic sheet frosted or milk white (0/40). c) letter size should be as per board area and width of letter should be in proportionate to the height d) Depth of each letter should not be less than 3"" e) Back of letter should be of sunpack sheet or 28 SWG powder coated sheet. f) Front & Back of letters should be assembled in such a fashion that it remains water tight, Dust proof. g) Front & Back of letters should be jointed / tighten with steel screw and washers, so that it may be opened in case of failure or for maintenance. h) All letters of each location should be fitted suitably on 3mm thick ALUMINUM PANEL Sheet and background shall be dark blue, if Required and this sheet to be fixed suitably on above M.S. Structure. i) Complete name board should be fixed on a M.S. Iron frame structure suitable size to withstand the atmospheric weather wind pressure etc. j)M.S. Structure should be grouted well with appropriated cement, concrete mixture at given Location. (Note1- LED Signage board are to be erected at various stations as per requirement and N.F.Railway will be also add in each borad at lower side, Location may be add or change as per instruction of competent authority )" | — | — | — | 57,032 | |
| — | 1.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of 10 kVA Online UPS, complete with necessary internal batteries (if specified), input-output MCBs, bypass arrangement, interconnecting cables, earthing, installation, testing and commissioning, complete in all respects and as directed by Engineer-in-Charge at site. Technical Specifications •Capacity: 10 kVA •Type: Online UPS (Double Conversion) •Input Supply: 230V AC Single Phase / 415V AC Three Phase (as required) •Output: 230V AC, 50Hz, Pure Sine Wave •Efficiency: 90% •Power Factor: 0.9 •Waveform: True Online Double Conversion •Static Bypass: Inbuilt automatic & manual bypass •Display: LCD / LED display for parameters •Protections: oOverload oShort circuit oBattery low oOver temperature oInput over/under voltage | — | — | — | 1,06,490 | |
| — | 20.00 | — | — | ||
| Supply, fitting and fixing of 12V, 75Ah VRLA (Valve Regulated Lead Acid) battery for UPS, conforming to IS 16046, complete with interconnecting leads, terminal covers, necessary hardware, testing and commissioning, including two years onsite warranty, complete as required and as directed by Engineer-in-Charge. Technical Specifications •Type: VRLA (SMF - Sealed Maintenance Free) •Rated Voltage: 12 Volts •Capacity: 75 Ah @ C10/C20 rate (as applicable) •Standard: IS 16046 •Design Life: Minimum 3-5 years •Container: ABS body, leak proof •Terminal Type: Heavy duty threaded terminal •Application: Suitable for UPS duty (High discharge rate) •Warranty: Minimum 2 years onsite replacement warranty | — | — | — | 1,60,000 | |
| — | 29.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of 3 Watt LED concealed foot light fitting, complete with inbuilt LED lamp, driver, mounting accessories, internal wiring and all necessary hardware, suitable for operation on 230V AC supply, complete as required and as directed by Engineer-in-Charge. | — | — | — | 16,820 | |
| — | 26.00 | — | — | ||
| Supply and installation of Single Phase Automatic Voltage Stabilizer suitable for 1.5 Ton Air Conditioner, with input voltage range 120V-280V and output voltage range 195V-245V (Single Phase Sine Wave), conforming to IS: 8448:1989 (latest amendment), complete with mounting arrangement, input-output wiring, testing and commissioning as required and as directed by Engineer-in-Charge. | — | — | — | 52,201.5 | |
| — | 26.00 | — | — | ||
| Supply and fixing of MS Iron Angle base frame for outdoor AC unit, fabricated from suitable size MS angle (minimum 40mm x 40mm x 5mm or as required), duly welded, drilled and painted with one coat of red oxide primer and two coats of synthetic enamel paint, including necessary anchor fasteners, foundation bolts, rubber pads, grouting and all fixing accessories, complete as required and as directed by Engineer-in-Charge at site. | — | — | — | 31,200 | |
| — | 1.00 | — | — | ||
| Design, fabrication, supply, installation, testing and commissioning of LT Control Panel, outdoor type, double door, rear access, FORM-3b construction, suitable for 415V, 3 Phase, 4 Wire, 50Hz system, complete with MCCBs, changeover switch, busbar system, metering, protection, cable alley, internal wiring and all accessories as specified, complete in all respects. Technical Specifications 1. Standards & Compliance IEC 60439-1 / IS 8623 Part-1 IEC 60947-2 (for MCCBs) IS 694 (Control wiring) CPRI type tested & ISI / ISO approved manufacturer Short circuit withstand capacity: 100 kA for 1 second Temperature rise test at 6300A as per IS 8623 Part-1 2. Panel Construction •Outdoor type, rear access, FORM-3b •Protection: IP54 / IP55 •Colour: RAL 7035 structured finish •CRCA steel enclosure oLoad bearing parts: 2.0 mm thick oNon-load bearing parts: 1.6 mm thick •Gland plate: 3 mm thick GI •Neoprene gasketed doors •Cable entry: Incoming - Bottom / Outgoing - Bottom •Separate cable alley provided •Built & inspected at OEM factory in presence of Railway representative •Approved drawings to be submitted before fabrication 3.Busbar System •Horizontal busbar at top throughout panel •TPN electrolytic grade copper busbar •Size: 50 mm x 6 mm (R, Y, B & N) •Heat shrinkable colour coded PVC sleeves •Mounted on porcelain insulators with adequate clearance •Incoming switches connected to busbar through crimped sockets •Separate earth busbar provided 4. Incomer & Outgoing Configuration (i) Incomer •630A, 4 Pole MCCB, 50kA, adjustable thermal magnetic - 1 No. •800A, 4 Pole On-Load Changeover Switch (Manual Transfer Switch) - 1 No. (ii) Outgoings •400A, 4 Pole MCCB, 50kA - 4 Nos. •250A, 4 Pole MCCB, 36kA, Ics = 100% Icu - 2 Nos. •100A, 4 Pole MCCB, 25kA, Ics = 100% Icu - 2 Nos. All MCCBs shall conform to IEC 60947-2 with adjustable thermal magnetic settings. 5. Metering & Accessories •Multifunction meter (Digital) •CTs of suitable ratio •LED indicating lamps (RYB) •Auxiliary contactors •Selector switches / Cam switches •6A Control MCB •1.1 kV grade flexible copper control wiring •Terminal blocks with ferruling | — | — | — | 5,75,080 | |
| — | 1.00 | — | — | ||
| Design, fabrication, supply, erection, testing and commissioning of floor mounted, outdoor type, double door LT Main Control Panel (8 Way MCCB Panel) complete with MCCBs, copper busbar, metering, protection, internal wiring and all accessories, conforming to IEC 60947-2, suitable for 415V, 50Hz, 3 phase, 4 wire AC supply, complete as required and as directed at site. Confirm outdoor IP rating (IP54/IP55 preferable). Ensure proper earthing & earth continuity bar. Conduct IR test, functional test & primary injection test before commissioning. Panel Configuration Incomer 400A, 4 Pole MCCB, 50kA Ics, Ics = 100% Icu, adjustable thermal-magnetic type - 01 No. Outgoings 250A, 4 Pole MCCB, 36kA Ics, Ics = 100% Icu - 03 Nos. 100A, 4 Pole MCCB, 25kA Ics, Ics = 100% Icu - 04 Nos. All MCCBs shall conform to IEC 60947-2. Technical Specifications Panel Construction •Floor mounted, outdoor type, double door •Fabricated from 2 mm thick CRCA sheet steel •Powder coated finish •Dust & vermin proof construction (minimum IP54 recommended for outdoor) •Gland plate at bottom •Removable side covers •Adequate ventilation •Built & inspected at OEM factory in presence of Railway representative •Approved drawings to be submitted before fabrication Busbar •630A rated copper busbar •Electrolytic grade copper •Size: 50 mm x 6 mm (for R, Y, B & Neutral) •Proper colour coding & heat shrink sleeves •Suitable earth busbar Metering & Indications •Digital / analog Ammeter with selector switch •Voltmeter with selector switch •LED indication lamps (RYB) •6A SP control MCB •CTs of suitable ratio for ammeter & protection •Reverse current relay (if specified for DG/parallel application) Accessories Included •MCCB door interlocks •Auxiliary contacts •Spreader links •Terminal blocks (adequate size & quantity) •Ferruled internal wiring with PVC insulated copper wire conforming to IS 694 •Proper earthing terminals Standards •IEC 60947-2 - MCCB •IS 694 - PVC insulated copper wiring •Panel to be manufactured by CPRI approved panel manufacturer | — | — | — | 3,64,925 | |
| — | 4.00 | — | — | ||
| Supply, fixing, testing and commissioning of 8 Way TPN Distribution Board (8+8+8 outgoing modules), conforming to IS 8623 (Part-1 & 3) / IEC 61439 (Part-1 & 3), fabricated out of CRCA sheet steel, RAL 9003 powder coated finish, single door, IK-08 mechanical protection, IP43 protection class, complete with busbar, neutral link, earth bar, DIN rail mounting, internal wiring and all accessories, suitable for 415V, 50Hz, 3 phase, 4 wire AC supply, complete as required at site. Components Included The TPN DB shall be complete with the following MCBs (C-curve, 10kA breaking capacity or as specified): 63A, 4P MCB, C-curve - 2 Nos. 32A, DP MCB, C-curve - 2 Nos. 16A, DP MCB, C-curve - 4 Nos. 10A, SP MCB, C-curve - 4 Nos. Technical Specifications Enclosure: CRCA sheet steel, powder coated RAL 9003 Ingress Protection: IP43 Mechanical Protection: IK08 Busbar: Tinned copper busbar of suitable rating Neutral Link: Copper neutral bar with adequate terminals Earth Bar: Copper earth bar with suitable terminals Mounting: Surface/flush mounting (as specified) Internal Wiring: FRLS copper wiring with proper ferruling Standards: IS 8623 / IEC 61439 | — | — | — | 77,620 | |
| — | 15.00 | — | — | ||
| Supply, fixing, testing and commissioning of HT heat shrinkable type outdoor cable end termination kit, suitable for single core 11 kV grade, 120 sq.mm XLPE insulated, armoured aluminium conductor cable, complete with all accessories for terminating 11 kV cable to overhead line through suitable PG clamp, complete as required and as directed by Site Engineer. Technical Specifications Voltage Grade: 11 kV (12 kV class) Cable Type: Single core, 120 sq.mm, XLPE insulated, armoured aluminium conductor Termination Type: Heat shrinkable, outdoor type Standard: Conforming to relevant IS/IEC standards for 11 kV cable accessories Kit Contents: Heat shrinkable stress control tubing Anti-tracking outdoor insulation tube Breakout boots Lugs (aluminium/compression type) Earthing accessories for armour Mastic tape, sealants and insulating materials PG Clamp: Suitable size for conductor and overhead connection Installation: Including stripping, crimping with hydraulic crimping tool, armour earthing, heat shrinking and proper dressing Testing: IR test and HV test (if required) after termination | — | — | — | 59,976 | |
| — | 50.00 | — | — | ||
| Supply and laying of 50 mm dia medium class GI pipe, conforming to relevant IS specification, laid in ground/on surface/wall (as specified), including cutting, threading, jointing with sockets, bends, tees, unions, necessary fittings, clamps, supports, excavation (if laid underground), refilling, testing and commissioning complete as directed by Site Engineer. | — | — | — | 20,600 | |
| — | 1000.00 | — | — | ||
| Laying, installation, testing and commissioning of LT/HT XLPE insulated, armoured aluminium conductor power cable of different sizes, partly laid along pole/structure and partly laid underground through excavated cable trench, complete as required at site. The work includes loading, unloading and carrying of Railway-supplied cable to actual work site by contractor's own arrangement, straightening, dressing, clamping on pole with suitable saddles/clamps, laying in trench, sand cushioning, protective covering with bricks/tiles, backfilling, compaction, route marking, and testing before and after laying, complete as directed by Engineer-in-Charge. | — | — | — | 40,930 | |
| — | 6.00 | — | — | ||
| Supply of 6 metre long single longitudinal welded, single dip hot-dip galvanized octagonal pole (Type: BOP-6030) having 70 mm top diameter, 130 mm bottom diameter and 3 mm steel thickness, manufactured under ISO 9001 & ISO 14001 certified facility, complete with base plate of size 220 mm x 220 mm x 12 mm thick, pole cap on top, and all necessary accessories. The work includes design, supply and construction of CC foundation, including excavation, PCC/RCC foundation as per design, backfilling and compaction; providing and fixing 4 Nos. anchor foundation bolts of 20 mm dia and 600 mm length (one set) embedded in CC foundation; provision of 6A SP MCB inside pole base compartment; fixing of Bakelite sheet terminals; and wiring with 2 x 1.5 sq.mm copper conductor cable from MCB to street light luminaire, complete as directed by Site Engineer. Technical Specifications Pole Type: Octagonal, single longitudinal welded Height: 6 metres above ground level Top Dia: 70 mm Bottom Dia: 130 mm Thickness: 3 mm Galvanization: Single dip hot-dip galvanized (minimum 70-80 microns coating) Base Plate: 220 x 220 x 12 mm Anchor Bolts: 4 Nos., 20 mm dia x 600 mm length with nuts & washers Foundation: CC foundation (size as per soil condition, typically 1:2:4 mix or as designed) MCB: 6A SP MCB inside pole box Internal Wiring: 2 x 1.5 sq.mm copper conductor cable Terminal Plate: Bakelite sheet with suitable connectors Includes: Excavation, concreting, curing, backfilling and erection | — | — | — | 70,994.94 | |
| — | 6.00 | — | — | ||
| — | 6.00 | — | — | ||
| — | — | — | 23,014.98 | ||
| — | 30.00 | — | — | ||
| Supply and fitting of 0.5 Watt LED bulb, suitable for operation on 230V, 50Hz AC supply, complete with LED lamp, inbuilt driver, B22/E27 cap (as specified), and connection to existing holder, including testing and commissioning complete as required at site. | — | — | — | 1,350 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .