SE ETC I MORADABAD
220 KV S/S CAMPUS MAJHOLA MORADABAD
REPLACEMENT OF 132KV AND 33 KV MAIN BUS BAR FROM ACSR SINGLE TARANTULA CONDUCTOR TO ACSR TWIN MOOSE CONDUCTOR AT 220KV SS CHANDAUSI UNDER ETD SAMBHAL
2020_UPTCL_484194_1
E-T-49/ ETCM/2020-21
Open Tender
Electrical Works
Fixed-rate
60 days
SAMBHAL
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
SE ETC MORADABAD
₹19,000
24 Jul 2020
17 Jun 2020
14 Jul 2020
17 Jun 2020
14 Jul 2020
17 Jun 2020
Amount
(ANNEXURE-A, FOR WORK)
Cutting/Opening of single Tarantula conductor cross jumper among the Two sections of each phase of existing 132 KV main bus and shifting of the recovered material from site to store.
Cutting/Opening of single Zebra Conductor jumper of each phase of existing 132 KV main bus to bus isolator, shifting of material from site to store.
Dismantling of existing single Tarantula conductor of each phase of 132 KV main bus & shifting of the recovered material from site to store. There are 03 Nos. sections having 03 Nos. conductores in each sections.
Stringing of Twin Moose conductor of each phase of 132 KV main bus with the help of single tension twin Moose fitting alongwith spacers, hoisting of Disc insulators and other hardware at both ends of span & proper sagging including cutting, bending of conductor to & for shifting of the material from store to site. Each bus has 03 spans having 03 Nos. of twin Moose conductors.Total nos. of section conductors. 3x3=9
Reconnection of Single Moose jumper between each phase of 132 KV main bus and bus isolator including cutting bending of conductor alongwith spacers to & for shifting of material from store to site.
To connect twin Moose cross jumpers with spacers, P.G. clamps etc. among three sections of newly stringed 132 KV main bus including cutting, bending of conductor, shifting of material from store to site. There are 02 sections having cross jumpers at Two places. Total No. of corss jumpers =3x2=6
Cutting/Opening of Twin Panther Conductor jumper of each phase of existing 33 KV main bus to bus isolator, shifting of material from site to store.
Dismantling of existing single Tarantula conductor of each phase of 33 KV main bus & shifting of the recovered material from site to store. There are 03 Nos. sections having 03 Nos. conductores in each sections.
Stringing of Twin Moose conductor of each phase of 33 KV main bus with the help of single tension twin Moose fitting alongwith spacers, hoisting of Disc insulators and other hardware at both ends of span & proper sagging including cutting, bending of conductor to & for shifting of the material from store to site. Each bus has 03 spans having 03 Nos. of twin Moose conductors.Total nos. of section conductors. 3x3=9
Reconnection of Twin Panther jumper between each phase of 33 KV main bus and bus isolator including cutting bending of conductor alongwith spacers to & for shifting of material from store to site.
Reconnection of Twin Moose jumper between Section Isolator including cutting bending of conductor alongwith spacers to & for shifting of material from store to site.
(ANNEXURE-B, FOR SUPPLY) B) Following supply of material are required to carry out the augmentation work of 132 KV&33 KV Main bus bar at 220 KV S/S Chandausi.
Bolted type Single tension fitting for twin Moose conductor without turnbuckle.
Spacer for twin Moose conductor with 250 mm spacing.
Spacer for twin Panther conductor with 100 mm spacing.
Spacer for twin Moose conductor with 100 mm spacing
Four Bolted type P.G Clamp suitable for Moose to Moose conductor.
Four Bolted type P.G suitable for Moose to Panther conductor.
Three Bolted type P.G Clamp suitable for Panther to Panther conductor.
Supply of Isolator clamp for twin Panther conductor.
Supply of Isolator clamp for twin Moose conductor.
Supply of bimetallic for 145 KV CT Clamp for Single Moose conductor.
Supply of bimetallic for 145 KV CT Clamp for Single Panther conductor.
Supply of Isolator clamp for Single Moose conductor G.Nandy Make
P&H Engineering
ASHUTOSH ENTERPRISES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .