Executive Engineer PHE Mech. Div. South Awantipora
Executive Engineer PHE Mech. Div. South Awantipora
Repairing of 3 phase, 63 KVA, 11/0.440 KV H.T Transformer at water supply scheme Awantipora Quarry.
2021_PHE_134299_3
JSD/PHE/MDSA/ e-NIT No. 26 of 2021-22
Open Tender
Repair and Maintenance Works
Item Rate
5 days
Awantipora
Please refer Tender documents.
2 documents required · 2 mandatory
₹50
Executive Engineer PHE Mech. Div. South Awantipora
Exempted
13 Sept 2021
12 Aug 2021
25 Aug 2021
12 Aug 2021
24 Aug 2021
12 Aug 2021
Amount
Disassembling of pole mounted outdoor type 3phase, 63 KVA , 11/0.440 KV H.T Transformer from the two pole structure and H.T Circuit, loading into tata mobile then shifting it to workshop for conducting repairs, unloading the transformer by using channels and skillid/ semi- skilled labours and then back to the site of work by TATA Mobile. The job includes installation of H.T Transformer on transformer bed on channels of two pole structure . The job also includes testing of H.T Transformer at full load.
Disassembling of transformer for assessing the nature of fault and damages. the job includes opening of top cover and removal of damaged coils.
Complete rewinding of H.T Coils as per norms and required specification. (coils prefabricated as per relevant IE- Specification). The job further includes cost on account of old /scrap winding material
Extraction of moisture from the core by way of heat treatment of the same in electric oven at least for 24 hrs.
Re- tapping of all connection leads and P/F of sleeves to H.T/L.T connections
Fabrication , P/F of top lid gasket to the transformer including replacement of nuts and bolts- 1 kg and fitting of whole assembly into the transformer tank.
Filtration of existing T- oil upto desired strength and specifications.
Providing and filling of fresh T- Oil of appropriate strength and specifications.
Rayees Electric Engineering Works
tech_eval.pdf
fin_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .