Executive Engineer Electrical Division No-1 HPPWD
Executive Engineer Electrical Division No-1 HPPWD Shimla-9
Providing AA to existing wiring in Old industries Building at Bamloe Now occupied by H.P High Court at Shimla1 SH Providing 2 No. 20 KVA UPS thereof
2023_PWD_70779_1
Electrical Division-I dated 09.03.2023
Open Tender
Electrical Works
Item Rate
180 days
SHIMLA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
EE ELECTRICAL
₹31,000
18 Jun 2023
15 Mar 2023
22 Mar 2023
15 Mar 2023
21 Mar 2023
15 Mar 2023
Amount
TECHNICAL SPECIFICATION of Online20 kva UPS With 15-20 Mins Backup
SITC of 20KVA Online UPS : 3 Phase Input & 3 Phase Output-Autosensing, True Online UPS with Full Digital Signal Processing (DSP )Technologies with Touch Screen LCD /LED Display Panel & Pure Sine Wave O/P with high frequency. UPS unit shall operate in double conversion mode, it shall be a VFI-type UPS (as per stanard IEC 62040-3) with Inbuilt /external Galvanic ISOLATION Transformer of same OEM make only. UPS should be with 3 level IGBT Based Rectifier & 3 Level IGBT Based Inverter Technology. UPS should have minimum 15-20 minutes backup on SMF Batteries Bank with Minimum VAH = 30200 VAH along with following features/specifications
INPUT FEATURE :
Input Voltage window380 VAC - 450 VAC 3 Phase
Input Frequency window 45-65 Hz .
Nominal Frequency 50 Hz
Total Harmonic Current Distortion (THDI ) should be less than 5 % at full rated load
Input power factor (PF) greater than or equal to 0.99
OUTPUT FEATURE :
Output Power Factor should be unity.
Output Power Capacity in watts (KW) 20kva
Output Voltage - 430/440 Volts rms, adjustable via the user interface.
Total Harmonic Distortion : < 2% for linear load & < 5% for 100% non-linear load
Output Frequency : a. Rated Frequency:- 50 or 60 HZ. B Variations - +_ 0.01% ( Adjustable from frunt pannel )
Communications & Management :-
Interfact ports : optional SNMP , USB/ RS 232.
Touch Screen LCD /LED Display and Multicolour LED Bar highly visible even from a distance
Alarms : Audible Alarm required for Mains failure, Low Battery, Inverter Trip, Over Temperature, Over Load
Internal Backfeed Protection as standard
Noise level at 1meter (dBA) should be < 60dBA
Emergency Power Off (EPO) Should be available as standard
Regulatory Approvals :- EN/IEC 62040-2, EN/IEC 62040-3 Compliance & CE/UE certified product
EFFICIENCY :- Min. 95% ( AC to AC i.e Online Mode) and 98% ( Eco Mode ) without Isolation TX.
Overload Capacity: A) 10 minutes at a load representing 125% of the rated load 40 Deg. C continous. B) 1 Minutes at a load representing 150% of the rated load at 40 Deg. C continous
Parallel option upto 6-8 Units should be available
UPS Should Be built in Manual and automatic Bypass with EPO feature
Warranty Terms :- 2 Years on UPS & 2 years on Batteries with onsite service Support
supplying & installation complete with connection , testing etc. of 20 KVA on line UPS HAVING SPECIFICATION DETAILED ABOVE (1.01 to 1.06 )OFany of FOLLOWING Approved Make : APC- Schneider / Vertiv -Emerson/ Legrand-Numeric /Mitsubishi /GE Only .
DC Battery Breaker : For safe maintenance on the battery of UPS unit, the system shall include a circuit breaker to isolate the battery from the corresponding rectifier /charger and inverter. When the battery is isolated from the system, the UPS shall continue to supply the load without interrup-tion or disturbance, except in the event of a normal AC source outage.
supply ,installation and connection of min VAH i.e. 12V 75 Ah battery of following Make : Quanta / Exide/Panasonic make only
D.S Ranta Electrical Contractor
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .