SE R and B Division No I Berhampur
SE R and B Division No I Berhampur
S/R to EI to SITC of panel and distribution of power to OPD ward, Integrated lab, OT ward, Drug warehouse, BPMU and meeting hall and BPHU room at CHC Kukudakhandi building
2026_EICCL_126738_1
SE R and B Divn NoI Bam 65/2025-26
Open Tender
Electrical Works
Percentage
30 days
Ganjam
2 documents required · 2 mandatory
₹4,000
₹9,000
Yes
20 May 2026
27 Feb 2026
7 Mar 2026
27 Feb 2026
6 Mar 2026
27 Feb 2026
27 Feb 2026 - 6 Mar 2026
S/I/T&Commissioning of LT indoor 200AMP floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing. (FOR ALL MAIN CONNECTED LOAD) BUILDING POWER)as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 5 years & compelete test certificate must be submitted along with panel board including component list.Type 2 SPD 3P,N 40KA ,10KV shall be installed in the incomer. Separate Aluminium Earth bus bar should be installed. 01 number of 200 Amps 4P MCCB 25KA ( Make-LEGRAND/ Siemens/ Schneider). Onload type Changeover-01 number of 200 Amps 4P ( Make-LEGRAND/ Siemens/ Schneider) Busbar- 04 numbers of 200Amps 50kA Electrolytic copper busbar duly sleeved by color coaded PVC sleeve & supported by suitable size DMC insulator. Out going- (i) 5 no's 100-125 AMP 25KA MCCB ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9) Out going- (ii) 04 nos 40A 4P MCB FOR LIGHT BDB , 63A 4P MCB, ( Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9) Instrument- (i) 3 numbers phase indicating lamp with 2A SP MCB,C,10KA. (ii) 01 set of MFM with RS-485 & CTS.(DIGITAL)(Sicure/L&T,CT-KAPPA or equievalant make & model) providing with Floor Rubber mat 3'X2'X6 mm
2 X 1.5sq.mm +1 X 1.5sqmm
Supply and fixing of copper plate earthing( 600 X 600 X 3.15mm )with running copper flat 25 X 5mm from copper plate to funnel of 40mm dia G.I pipe including all accessories
Supplying and laying 25 mm x 5 mm copper strip on surface or in recess for connection etc as required.
Providing and fixing 8 SWG (4 mm) dia copper wire on surface or in recess for loop earthing as required
12way, Double door
63Amp TPN bus bar -300 X 25 X 3mm size make-Hager/Havells/Legrand/Anchor/schnider
Single pole (SP)
Single pole and Neutral (SP&N)
Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 240 volts, RCCB 30mA . Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. . The RCCB should be Replacement Warranty will be 3 years.
100Amp kit kat
63Amp ICTPN Main switch on MS angle frame
S/F of 20W 4' LED fitting Surface LED Light fitting , Lumens Efficacy minimum rating should meet :105 lumen per watt 6500k (Make-Havels/Panasonic/ Philips/Bajaj/Crompton
S/F of 90W LED street light fitting , Lumens Efficacy minimum rating should meet :105 lumen per watt 6500k (Make-Havels/Panasonic/ Philips)
16sq.mm 4core
25sq.mm 3 1/2 core
50sqmm 3 1/2 core
70sqmm 3 1/2 core
1.5sq.mm 3core
Trenching with sand spreading and bricks laying and laying of cable in trench in 2 1/2' depth .pvc cable upto 25sqmm
Trenching with sand spreading and bricks laying and laying of cable in trench in 2 1/2' depth .pvc cable from 25sqmm to 120sqmm
3.5C x 70 sq.mm
3.5C x 35 sq.mm
4 C x16 sq.mm
Supply and fixing of 3P+N ,63 A industrial Insulated Plug and socket Make-havells DHDPBEN063 / Plycab/ anchor-panasonic/schnider-electric( Instalation in OT room)
S/F of 1200mm Brush Less Direct Current BLDC Ceiling fan with Low wattage consumption fan , Heavy Duty,durable, copper winding,Aluminium blade(ISI mark) Crompton Grave/Khaitan/Havells/Orient/Polycab/V-Guard
Portable Fire Extinguisher System Supplying, installation, testing and commissioning of CO2 type Fire Extinguisher 4.5 kg capacity confirming to IS: 2878 made from ISI marked seamless cylinder confirming to IS: 7285, fitted with ISI marked controlled valve confirming to IS: 3224, high pressure 1mtr discharge hose & horn complete with initial gas charged with carrying handle & wall mounting bracket as per direction of Engineer-in-charge. Make-Safex/Fireshield/Ceasefire
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_583486.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_2.pdf
PDF • 1.58 MB
Tendernotice_1.pdf
PDF • 0.50 MB
BOQ_583486.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .