Loading…
Loading…
Tender Value
₹76.6 L
EMD Value
₹1.5 L
Closing Date
18 Dec 2025, 1:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TECHNICAL
15 conditions · 4 needing a document upload
Clause Regarding GST: (a) All the Bidders/tenderers should ensure that they are GST Compliant and their quoted tax Structure are as per GST LAW.(b) Tenderer Should Furnish their GSTIN numbers representing the States in Which they are registered GST, along with address of Registered Office.(c)The Contract is under GST Act and rules as applicable time to time.
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(AnnexureVIB of Tender Documents).
41 conditions · 11 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Balanced Works For (i) At NTSK: Replacement of Overaged split bamboo wall quarters by Type-II Qtrs(DS-100 Units) (ii) At TSK: Replacement of split bamboo wall of Qtrs by Brick wall( 24 Units)
LV-T-14-TSK-916-R~NFR
LV-T-14-TSK-916-R
Open
Works - General
14 Months
Tinsukia, Assam
₹0
₹1.5 L
18 Dec 2025
26 Nov 2025
4 Dec 2025
82 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 72,65,123 | ||
| — | 648.00 | — | — | ||
| Supply, fitting, fixing, testing & commissioning of wiring materials for concealed type wiring of light point from main/sub-main board to the points by 1.5 mm.sq.single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with modular type switch 6 A, ceiling rose, GI box with suitable modules for fixing switches. | — | — | — | 4,23,792 | |
| — | 324.00 | — | — | ||
| Supply, fitting, fixing, testing & commissioning of wiring materials for concealed type wiring of Fan Point/Exhaust fan point from main/sub-main board to the points by 1.5 mm.sq.single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with modular type switch 6 A, ceiling rose, Modular GI metal box with suitable modules for fixing switches & Regulators and 1.0 sq mm multistrand FRLS copper Cable in green for earth contuinity wire . | — | — | — | 3,06,180 | |
| — | 486.00 | — | — | ||
| Supply, fitting, fixing, testing & commisioning of wiring materials for concealed type wiring 5 A plug point from main/sub-main board to the points by 1.5 mm. sq. single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with modular type switch & socket 5 A ,GI metal box with Suitable modules for fixing switch/socket with 1.0 mm² unsheathed FRLS copper cable in green colour for earth continuity wire. | — | — | — | 2,08,008 | |
| — | 486.00 | — | — | ||
| Supply, fitting, fixing, testing & commisioning of wiring materials for concealed type wiring 15 A plug point from main/sub-main board to the points by 4 mm. sq. single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with modular type switch & socket 15 A , GI metal box with Suitable modules for fixing switch/socket with 1.0 mm² unsheathed FRLS copper cable in green colour for earth continuity wire. | — | — | — | 5,97,780 | |
| — | 54.00 | — | — | ||
| Supply, fitting, fixing , testing & commissioning of wiring materials for concealed type call bell points by 1.5 mm.sq.single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with , GI box with suitable bell push switch 6 amps, bell & ceiling rose and suitable modules for fixing switches. | — | — | — | 39,204 | |
| — | 162.00 | — | — | ||
| Supply, fitting, fixing of Wiring materials for Geyser point wiring from DB/ sub main board to the points by 4 mm. sq. single core multi-strand FRLS copper cable through heavy duty PVC pipe complete with modular type switch & socket 16 A , 3 Module Plate, GI metal flush box with Suitable modules for fixing switch/socket with 1.0 mm² unsheathed FRLS copper cable in green colour for earth continuity wire. . One 16 Amps DP MCB 'B' series in MCB enclosure to be provided near Geyser as controlling switch | — | — | — | 2,09,142 | |
| — | 162.00 | — | — | ||
| Supply, fitting fixing of concealed AC point wiring with 6.0 Sq mm copper cable and16A MCB Protected Power Point and Push Starter with 1.0 SQ mm single core multistrand copper cable in green for earth continuity wire. | — | — | — | 2,93,220 | |
| — | 162.00 | — | — | ||
| Supply, fitting, fixing of 5 Step Modular Fan Regulator 2 Module 100W having capacitive technology for more efficiency and less heat loss compaitable with BLDC fan technology. | — | — | — | 67,554 | |
| — | 54.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of wall mounted type 16 way double door MCB DB having IP 43 protection, Shrouded Neutral Bar & Bus Bar, Cement Spill Protector & Door Earthing with the following domestic switchgears:- (i) RCBO 40Amps SPN(2 Module) Conforms to IEC 61009 breaking capacity 10kA, Sesitivity(In)=100mA = 1 No. ii) 40 Amps. DP MCB 'C' series, 240/415 V, 50 Hz, 10 kA BC (In accordance with IS/IEC 60898-1) =1 No. iii) 32 Amps. SP MCB "C" series (In accordance with IS/IEC 60898-1) 240V, 50Hz,10kA =3 Nos.iv)10 Amps. SP MCB "C" series (In accordance with IS/IEC 60898-1) 240V, 50Hz,10kA =3 Nos. V) 25 Amps MCB DP 'C' Series = 3 Nos for AC circuit.The outgoing cables should be 6 Sq. mm S/c copper cables and should be properly dressed using PVC flexible pipe 20 mm Dia. | — | — | — | 7,43,850 | |
| — | 27.00 | — | — | ||
| Supply, fitting, fixing, testing and commissioning of wall mounted 4 way MCB SPN DB Double Door having IP 63 protection, Shrouded Neutral Bar & Bus Bar, Cement Spill Protector & Door Earthing with the following domestic switchgears :- (i) 63 Amps DP MCB "C" Series(2 Module), 240/415 V, 50 Hz, 10 kA BC (In accordance with IS/IEC 60898-1) =2 No | — | — | — | 1,41,480 | |
| — | 7290.00 | — | — | ||
| Supply, drawing and connection of single core 2.5 sq. mm PVC insulated & unsheathed multistrand FRLHS copper cable conforming to IS: 694 for voltage grade upto 1100 Volts , as per direction of supervisor incharge at site. through rigid PVC conduit pipe 32 mm dia concealed through walls/surface as required. | — | — | — | 2,82,852 | |
| — | 5400.00 | — | — | ||
| Supply, drawing and connection of single core 4.0 sq. mm PVC insulated & unsheathed multistrand FRLHS copper cable conforming to IS: 694 for voltage grade upto 1100 Volts , as per direction of supervisor incharge at site. through rigid PVC conduit pipe 32 mm dia concealed through walls/surface as required. | — | — | — | 3,06,180 | |
| — | 3710.00 | — | — | ||
| Supply, drawing and connection of single core 6.0 sq. mm PVC insulated & unsheathed multistrand FRLHS copper cable conforming to IS: 694 for voltage grade upto 1100 Volts , as per direction of supervisor incharge at site. through rigid PVC conduit pipe 32 mm dia concealed through walls/surface as required. | — | — | — | 3,15,350 | |
| — | 18.00 | — | — | ||
| Supply, fitting, fixing of Bus Bar Chamber 3 phase and Neutral (4P) with Copper Busbar 63 Amps, 4 way .The busbar chamber to be fabricated using sheet steel (CRCA) of 1.6mm thickness and epoxy powder coated to give superior & lasting finish. The bus bar sections to be made of ETP grade copper & dull tin plated and the bus bar supports are made of DMC (Dough moulding compound). The neutral bus bar to be fully rated. The Bus Bar Chamber should conform to IS:8623/IEC 60439 (Panel sub assemblies) IS: 2147/IEC60529 (Degree for protection) | — | — | — | 1,74,150 | |
| — | 1000.00 | — | — | ||
| Supply, laying and testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable size 16 mm.sq. 2 core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. . For laying of above cable by digging of trench and excavation of earth to depth 0.75 Mtrs. and breadth 0.5 Mtrs. below the ground level and a layer of sand of 0.075 Mtrs. thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of sand of 0.075 Mtrs. thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. The cable route markers should be provided along the route of cables to indicate their presence so that damage/accident are Not caused by inadvertent digging. Cable To be drawn by , Suitable GI clamps through Structure/Wall /GI pipe for Sub- power supply of building as per direction of Engineer Incharge at site. | — | — | — | 4,27,000 | |
| — | 1500.00 | — | — | ||
| Supply, laying and testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable size 25 mm.sq. 2 core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. . For laying of above cable by digging of trench and excavation of earth to depth 0.75 Mtrs. and breadth 0.5 Mtrs. below the ground level and a layer of sand of 0.075 Mtrs. thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of sand of 0.075 Mtrs. thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. The cable route markers should be provided along the route of cables to indicate their presence so that damage/accident are Not caused by inadvertent digging. Cable To be drawn by , Suitable GI clamps through Structure/Wall /GI pipe for Sub- power supply of building as per direction of Engineer Incharge at site. | — | — | — | 7,17,000 | |
| — | 730.00 | — | — | ||
| Supply, laying and testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable size 50 mm.sq. 4 core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. . For laying of above cable by digging of trench and excavation of earth to depth 0.75 Mtrs. and breadth 0.5 Mtrs. below the ground level and a layer of sand of 0.075 Mtrs. thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of sand of 0.075 Mtrs. thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. The cable route markers should be provided along the route of cables to indicate their presence so that damage/accident are Not caused by inadvertent digging. Cable To be drawn by , Suitable GI clamps through Structure/Wall /GI pipe for Sub- power supply of building as per direction of Engineer Incharge at site. | — | — | — | 7,74,530 | |
| — | 18.00 | — | — | ||
| Supply, fitting, fixing of 200 Amps outdoor type cable junction box, angle frame mounted, dust & vermin proof, complete with rain cap, aluminium basbar of suitable size for TPN, 200 Amps, 415 V made out of 16 SWG CRCA sheet duly painted, Cable Junction Box Size: (lxbxh=450x 450x600 mm). The base of the fedder pillar junction box to be provided with CC foundation of propotion 1:1.5:3( cement, sang,Chips) after connection of Ug cables. | — | — | — | 1,60,902 | |
| — | 216.00 | — | — | ||
| Supply, fitting , fixing of LED Batten 20W, 4 Ft, ultra slim co-extruded polycarbonate channel with integrated electronic driver should be as per IEC: 62384/IS:16104( SMPS based constant current output, THD<20%), IP20 protection, color temperature=6500K, rated input voltage=230V AC, 50 Hz, power factor=0.9, view angle>=120°, lumens output not less than 100 lm/Watt, operating voltage range: 140-270 V AC. LED Should be as per LM-80/IS:16105. Fixture Size: (LXWxH=1156x25x35 mm +/-1) LED Chip specification. | — | — | — | 54,216 | |
| — | 54.00 | — | — | ||
| Erection of earth by 80 mm dia 3 Mtrs. long (Medium Gauge) GI pipe , 6 SWG GI wire,GI nuts, bolts including masonry materials for earthing pit, salt, charcoal etc. and construction of earth pit covered with CI plate having locking arrangement and watering pipe as per drg. Nos.CEE/STD/1 | — | — | — | 2,35,116 | |
| — | 27.00 | — | — | ||
| Supply, fitting fixing of SMC Multi-Meter BOX for housing 4 nos. 1 ph and 2 nos. 3-ph Kwh meters. The Meters to be installed in the Staircase for ease of Meter Reader for taking readings. (Box Size: 530x450x175 mm). | — | — | — | 1,36,215 | |
| — | 54.00 | — | — | ||
| Supply , Fixing and testing of vertical type wall mounted storage Geyser of Capacity 25 Ltrs BEE 5 Star rated , 240V, 50Hz with Maximum power consumption of 2KW , dry powder fero glass line coating technology for inner tank with incoloy heating element with minimum 4 years warranty , ABS outer body , 2 units of PVC connector pipe with length of 450mm length for hot and cold water supply with complete accessories including external knob for temp control and Earth Leakage Circuit Breaker(ELCB). | — | — | — | 6,51,402 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .