Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
5 Nov 2021, 2:30 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGINEER STD 2ND RAJBAGH
OFFICE OF THE EXECUTIVE ENGINEER STD 2ND RAJBAGH
Augmentation of 33/11 kV Receiving Station Arizal from 1x6.3 MVA to 2X6.3 MVA
2021_PDD_143362_1
eNIT No STD-II / 83 of 2021-22 Dated 09-10-2021
Open Tender
Electrical Works
Turn-key
45 days
BUDGAM
Please refer Tender documents.
4 documents required · 4 mandatory
₹1,700
EXECUTIVE ENGINEER STD 2ND RAJBAGH
Exempted
8 Nov 2021
11 Oct 2021
6 Nov 2021
11 Oct 2021
5 Nov 2021
11 Oct 2021
180 days
Amount
Electrical Works
Installation, Testing and Commissioning, of 33/11kV, 6.3MVA Power Transformer I/C carriage, loading, unloading etc (Material to be provided by the department)
Supply, Installation, Testing and commissioning of 11kV VCB Panel with breaker complete Set of reputed make 2 O/C (overcurrent) and 1 E/F (earth fault) relay (IEC61850) , Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port complete (12 kV, 1250A, 25 kA, Outgoing) complete with copper bus and other allied accessories Note:- Outgoing 11KV Panel VCB panel should be having 11KV CT of Ratio 600-300/5-5-5A
Supply, Installation, Testing & Commissioning of 33KV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type)
Supply, Installation, Testing & Commissioning of 33kV Isolator without Earthing Blade (36kV,1250A, Outdoor, 3 poles, 25 kA)
Supply, Installation, Testing & Commissioning of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less
Supply, Installation, Testing & Commissioning of 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi Core, Outdoor) (1 No. per Φ)
Supply and Erection of 9 Mtr. Long ST Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard
Supply, Installation, Testing & Commissioning of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m
Supply, Installation, Testing & Commissioning of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
P/F of GI Pipe structure of nonimal bore 200, 5.9 mm thick as per REC standards
Providing and fixing of Lugs, Ferrules of sorts etc.
Providing and fixing of Galvanised Nuts & Bolts
Supply,Laying,Testing, and commissioning of 11KV 400sqmm Xlpe Power Cable, THREE CORE, ALUMINIUM CONDUCTOR, XLPE INSULATED, ARMOURED CABLES as per IS IS 7098 Part-2 (Make: Havells/ Gloster/Finolex)
Supply,Laying,Testing, and commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS.
Supply,Laying,Testing, and commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS.
Supply,Laying,Testing, and commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS
Proviidng,Laying,stringing ,tensioning and binding of 0.2 ACSR Conductor (Panther) as per REC construction standards
P/F of T- Clamps /Pad Clamps of sorts of standard make
P/F of GI Channel/Angle/Flat of sizes including clamps as per site requirement
Supply installation testing and commissioning of 33kV Polymeric composite Disc Insulator with fitting (36KV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm) suitable for 0.2ACSR
Supply installation testing and commissioning of 33kV Polymeric composite Pin Insulator (36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm ) suitable for 0.2ACSR
Providing and fixing of Indoor Heat Shrinkable Cable Termination Kits
Providing and fixing of outdoor Heat Shrinkable Cable Termination Kits
Supply, Installation, Testing & Commissioning of Yard Lighting by way of using 1 no 9m long GI high mast pole continuously tappered of optogonal of cross section incl suitable shall raft foundation using 2 no 250w each LED Flood light confirming to IP-66 complete with all accessories and suitable control feeder panel
Providing and painting of ST poles with one coat of Red oxide and two coats of aluminium paint to give even shade of reputed brand
Providing and Fixing of Earthing of ST Poles Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip
Supply, Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Civil Works: Bidders shall quote the rates inclusive of carriage
Transformer/Equipment Foundation
Earth work and excavation by manual means over areas (exceeding 30 Cm and upto depth 1.5 mtr in width as well as 10 Sq m on plan) including disposal of excavated earth upto 1 meter from cutting edge ,disposed earth to be levelled and neatly dressed in all kinds of soil.
Providing and laying of stone soling in the excavated trenches, duly hand packed on level including ramming with iron hand rammers etc
Providing and laying in position of mud mat in 1:4:8 mix with 40 mm stone agg excluding the cost of centring and shuttering.(1 cement:4 coarse sand:8 stone aggregate of 20mm nominal size)
Providing and laying in position cement concrete in 1:2:4 mix with 20 mm (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size).
Reinforcement works including straightening, cutting , bending, placing in position and binding all complete using Thermo-mechanically treated bars
Centering and shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases for columns etc
Providing and fixing of MS Channel Iron of sorts as per site requirement
Earthing
Trench excavation of earth by manual means depth up to 1.5m and width not exceeding 1.5m in all kinds of soils
Supply and erection of steel work in welded sections complete
Filling back excavated earth in trench incl. ramming etc.
Construction of Cable Trench
Construction of Cable Trench by way of earth excavation in all sorts , providing and laying of lean pad in 1:4:8 mix with stone aggregate 20mm, cement concrete of M-15 1:2:4 mix with stone aggregate 20mm, 12mm Torr Steel for reinforcement, chequered plate (1m x0.8mx 5mm), angle iron (50x50x6mm), and 15mm thick plaster including cost of form work and carriage of materials as well as disposal of excavated earth. (Complete Job)
Yard Concreting/Metalling
Earthwork in surface excavation not exceeding 30cm in depth
Providing and laying of Dry Stone soling including spreading /levelling /ramming by manual means
Providing and laying in position cement concrete in 1:4:8 mix with 40 mm (1 cement:2 coarse sand:4 graded stone aggregate 40mm nominal size).
Providing and laying in position cement concrete in 1:2:4 mix with 20 mm (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size).
Supply/stacking/Laying/spreading including levelling of graded stone agg. 40mm nominal sizeby manual means
MUKHTAR AHMAD BANDAY
stage.html
html • 0.03 MB
tech_bid_open.pdf
PDF • 0.11 MB
tech_eval.pdf
PDF • 0.09 MB
fin_bid_open.pdf
PDF • 0.12 MB
boq_comp_chart.xlsx
xlsx • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .