EE
132 KV S/S Bharua Sumerpur
WORK OF MAJOR OVERHAULING AND REPAIRING OF 33 KV VACUUM CIRCUIT BREAKERS AT 132 KV SUBSTATION BHARUA SUMERPUR UNDER ETD HAMIRPUR
2021_UPTCL_602538_1
TS-33/ETD(H)/2021-22
Open Tender
Electrical Works
Lump-sum
90 days
132 KV S/S Bharua Sumerpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹177
Yes
Executive Engineer
₹1,500
Yes
3 Aug 2021
12 Jul 2021
2 Aug 2021
12 Jul 2021
2 Aug 2021
12 Jul 2021
90 days
Amount
Details of Work.
Major overhauling and repairing of following 33 KV VCB type circuit breaker at 132 KV S/S Bharua Sumerpur :-
(A) 33 KV VCB ABB Make of Bharua Sumerpur-I feeder (Mfg Year - 2015) (B) 33 KV VCB ABB Make of Bharua Sumerpur-II feeder (Mfg Year - 2016) (C) 33 KV VCB BHEL Make of Industrial-II feeder (Mfg Year - 2005) (D) 33 KV VCB ABB Make of Binwar feeder (Mfg Year - 2016) (E) 33 KV VCB ABB Make of Para Raipura feeder (Mfg Year - 2015) (F) 33 KV VCB CGEL Make of Laghudal-II feeder (Mfg Year - 2013) 1. By doing following work in each circuit breaker :- (i) Cleaning of porcelain of drive insulator and porcelain of vacuum interrupter from inside and outside of each pole. (ii) Checking & adjustement of snatch gap, travel of drive insulator rod & tie rod of each pole. (iii) Opening, repairing of mechanism by welding, drilling, machning and filling of material as per requirement and proper fitting of it in breaker cubicle. (iv) Oiling & greasing of crank gears by opening of lock circlip etc. (v) Replacement of worn out parts such as bush, rings, lock pins and latch etc. (vi) Checking & adjustment of oil daspot of breaker for its damping action. 2. After major overhauling and repairing of above VCB, following tests are to be carried out :- (i) Opening & closing time of breaker of each pole. (ii) Carrying out Contact Resistance Measurement (CRM test) of each pole. (iii) Checking of megger values of breaker poles. (iv) Checking triping of breaker at 70% DC voltage. (v) Checking the CLOSE/OPEN operation of breaker from REMOTE & LOCAL. (vi) Prepare and submit the site ovehauling report of each breaker.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
N D ASSOCIATES
MAXWEL ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .