Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.7 LAccepted-AOC 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹28.8 L+₹52,350 (1.85%)Rejected-Finance TP 117 2ND FLOOR MAURYA ENCLAVE PITAMPURA DELHI 110034 | DELHI | DELHI | DELHI | 110034 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹29.8 L+₹1.6 L (5.51%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹32.5 L+₹4.2 L (14.9%)Rejected-Finance HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD PIN 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹47.4 L
EMD Value
₹94,800
Closing Date
31 Jan 2020, 6:00 pmClosed
GE E/M BASE HOSP DELHI CANTT
GE E/M BASE HOSP DELHI CANTT
REPAIR/MAINTENANCE OF E/M INSTALLATION AND ALLIED WORKS AT CABINET SECT UNDER GE E/M BASE HOSPITAL DELHI CANTT-10
2020_MES_311218_1
GE/BH-51/2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE E/M BASE HOSP DELHI CANTT
Meeting enlistment criteria of MES with regard to having satisfactory completed requisite value works annual turnover, working capital, fixed assets. No recovery outstanding in any govt dept security clearance etc.
7 documents required · 7 mandatory
₹500
GE E/M BASE HOSP DELHI CANTT
₹94,800
Yes
11 Mar 2020
2 Jan 2020
3 Feb 2020
3 Jan 2020
31 Jan 2020
17 Jan 2020
Amount
M&L for painting of machineries, equipments, suction & discharge lines complete of water supply installation with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the water supply installation to be painted are as under: (a) Centrifugal Pump with motor 15 HP - 02 Nos (b) Centrifugal Pump with motor 12.5 HP - 03 Nos (c) Centrifugal Pump with motor 10 HP - 01 No (d) Centrifugal Pump with motor 7.5 HP - 2 Nos (e) Centrifugal Pump with motor 3 HP - 01 No (f) Suction & discharge lines upto dia 300mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of machineries, equipments, suction & discharge lines complete of Fire fighting installation with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the Fire fighting installation to be painted are as under: (a) Centrifugal Pump with motor 125 HP - 01 Nos (b) Centrifugal Pump with motor 100 HP - 03 Nos (c) Centrifugal Pump with motor 60 HP - 03 Nos (d) Jockey Pump with motor 15 HP - 3 Nos (e) Diesel Engine 140 BHP - 01 No (f) Suction & discharge lines upto dia 300mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of machineries, equipments, suction & discharge lines complete of Sewage installation (East & West) of MS Bldg with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the Sewage installation to be painted are as under: (a) Centrifugal Pump with motor 12.5 HP - 01 Nos (b) Centrifugal Pump with motor 10 HP - 07 Nos (c) Suction & discharge lines upto dia 150mm (d) Sluice valves, butterfly valves and non-return valves
M&L for painting of machineries, equipments, suction & discharge lines complete of Sewage installation (East & West) of CRF Bldg with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the Sewage installation to be painted are as under: (a) Centrifugal Pump with motor 5 HP - 04 Nos (b) Centrifugal Pump with motor 3 HP - 02 Nos (c) Suction & discharge lines upto dia 150mm (d) Sluice valves, butterfly valves and non-return valves
M&L for painting of machineries, equipments, suction & discharge lines complete of DG Set installation with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the DG Set installation to be painted are as under: (a) DG Set 750 KVA - 03 Nos (b) DG Set 160 KVA - 01 Nos (c) Fuel Tank 1000 ltrs - 03 Nos (d) Fuel Tank 360 ltrs - 01 Nos (e) Centrifugal Pump Set 7.5 HP - 03 Nos (f) Suction & discharge lines upto dia 150mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of machineries, equipments, suction & discharge lines complete of AC Plant installation with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the AC Plant installation to be painted are as under: (a) Centrifugal Pump with motor 40 HP - 07 Nos (b) Centrifugal Pump with motor 30 HP - 07 Nos (c) Centrifugal Pump with motor 5/3 HP - 04 Nos (d) Screw-type Compressor Unit 250 TR - 4 Nos (e) Condensor Unit 250 TR - 04 Nos (f) Suction & discharge lines upto dia 300mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of machineries, equipments, suction & discharge lines complete of Forced Ventillation installation with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of machineries in the Forced Ventillation installation to be painted are as under: (a) Blower Motor 40 HP - 01 Nos (b) Blower Unit 60000 CFM - 01 Nos (c) Monoblock Pump with motor 5/3 HP - 01 No (d) Cooling Tower with structure - 1 Nos (e) Suction & discharge duct inside the installation. (f) Suction & discharge lines upto dia 80mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of Cooling towers with induced draught motors & FRP Tank of AC Plant including suction & discharge lines around the coolilng tower complete with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of items to be painted are as under: (a) Cooling Tower with motor & FRP Tank complete of cap 500 TR - 01 Nos (b) Cooling Tower with motor & FRP Tank complete of cap 250 TR - 02 Nos (c) Suction & discharge lines inside the cooling tower area upto dia 300mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of Cooling towers with induced draught motors & FRP Tank of DG Set including suction & discharge lines around the coolilng tower complete with two coats of synthetic enamel paint of superior quality after scraping, cleaning and preparation of old painted surfaces complete. Details of items to be painted are as under: (a) Cooling Tower with motor & FRP Tank complete of cap 70 TR - 03 Nos (b) Cooling Tower with motor & FRP Tank complete of cap 20 TR - 01 Nos (c) Suction & discharge lines inside the cooling tower area upto dia 150mm (g) Sluice valves, butterfly valves and non-return valves
M&L for painting of complete incinerator accessories like primary chamber, secondary chamber, chimney up to top end, electric motor with blower, all existing gas pipe lines, operating valves and all other connected accessories with 2 coats of heat resistant paint of superior quality after scrapping, cleaning and preparation of all old painted surfaces complete all as specified and directed.
M&L for opening and taking down of LPG gas pipe lines complete by removing all control valves, pressure gauges, high/low pressure cut outs, pressure regulator, gas strainer, gas operating valves, flexible pipes and cleaning of gas pipe line from inside with wire brushes and liquid detergent for removing of deposited scaling/corrosion and refixing of gas pipe line and all control valves & other connected accessories as described, leakage test and testing of complete system for smooth functioning of the incinerator up to the satisfaction level and all as directed by the Engr-in-charge. Note: - Cost of any cutting, welding, machining wwork , jointing work required shall deemed to be included in quoted rates.
M&L for Removing and cleaning sludge/silt/mud deposition from West side sewage sump of MS bldg at cabinet sectt sump size 8.0 mtr dia X 7.0 mtr deep (in two portions) with help of vaccum type pump, necessary T&P and disposal of the collected sludge/silt/mud deposition from sewage installation site to low lying area of NDMC / Ghazipur sanitary land by means of necessary transport all up to the entire satisfaction of Engr-in-Charge and site requirement all as directed. (i) All necessary T&P shall be arranged by the contractor. (ii) The contractor shall be responsible for cleanliness of equipment and sewage pump house in and arround the surrounding area.
All as per item No-12 above but from East side sewage sump of MS bldg.
All as per item No-12 above but from East side sewage sump of CRF Building (sump size 3.30 mtr dia X 3.30 mtr deep).
All as per item No-12 above but from West side sewage sump of CRF Building (sump size 3.30 mtr dia X 3.30 mtr deep).
M&L for cleaning of semi underground main incoming water supply RCC tank / sump of capacity 50000 gallons water supply /fire fighting storage by the following methods. (i) Removing / taking out accumulated mud/ solid waste particles etc deposited at the bottom of the sump and walls and disposed off the same to Gazipur sanitary land MC low lying area by PVC vehicles. The cost of transport / vehicle is deemed to be included in the unit rate of the items. (ii) Washing the RCC sump by clean water and bleaching powder solution after brooming with wire brush all side of wall of sump and dirt and deposited surplus etc all as per site requirement and as directed.
All as per ser item No. 16 here-in- before but cleaning of RCC over head tank of 10,000 gallons capacity of roof of 11 storied 'E' block complete all as specified and as directed.
All as per Ser item No.16 here-in- before but cleaning of RCC over head tank of 5000 gallons capacity at roof of 04 storied 'F' and 'D' block complete all as specified and as directed.
M&L for dewatering, cleaning of service tanks with high pressure water jet to remove all masses, algae & dirt and removal of dirty water alongwith sludge using sludge machine and dispossal of the same to a safe distance and appling of anti bacterial sterlization spray to walls, floor and pour water purifier bleaching powder to the tank and clean manually and drainout the dirty water complete of PVC tank of capacity upto 2000 ltrs all as specified and directed by engr-in-charge
Dismantling the existing water storage tank and S&F in replacement of rotational molded polyethylene water storage tank in multilayers of capacity 2000 ltr (Cylindrical vertical with closed top) hoisted and fixed in position on existing wall, stage, roof & RCC staging complete all as specified in SSR Part-I including complete connection of inlet and outlet pipe, tank nipple, float valve etc. Make : - Sintex/ Rotex
All as per sl item No 20 above but capacity of 1000 ltr.
All as per sl item No 20 above but capacity of 500 ltr.
S&F in replacement of unserviceable sensor suitable for water level indicator of approved make or as per existing make.
S&F in replacement of float Lever Controller switch all as specified and directed by Engr-in-Charge.
Testing of water sample as per IS-10500 collected from part of MS bldg complex from M/S Shri Ram Institute for Industrial research / Bharat test house, Delhi as and when directed by Engineer-n- Charge.
M&L for flushing/removing mud/silt in borewell casing pipe of size 200 mm bore by using heigh pressure compressor machine including removing sludge/silt diposite at the low laying area (WQMC area/Gajipur land) Complete all as directed by Engr-in-Charge.
Lifting of MS ERW column pipes of size 50mm bore from bore well by tripod and chain pulley. Dismantling/removing unserviceable/corroded portion upto any length with the help of welding machine/cutter complete all as specified and as directed.
M&L for MS ERW column pipes of size 50 mm bore, heavy duty cutting welding jointing and lowering to bore well complete all as specified and as directed.
Lifting of defective submersible pump set of capacity 7.5 HP/5.0 HP from bore well of depth 40 to 50 mtr by using Tripod and chain pulley and transportation from the site of cabinet to work shop for repair. Transporting back to its original location after carried out necessary repair work and lowering the pump set to bore well for the smooth functioning of submersible pump set complete all as specified and as directed.
Lifting of defective submersible pump set of capacity 7.5 HP/5.0 HP from bore well of depth 40 to 50 mtr by using Tripod and chain pulley and transportation from the site of cabinet to work shop for repair. Opening the pump set and cutting the burnt winding and removing it from pump motor. Cleaning the motor thoroughly and rewinding with new super enamelled copper wire as per original gauge and weight. Insulating varnishing, re- assembling and transporting back to its original location and lowering the pump motor to bore well for the smooth functioning of submersible pump set complete all as specified and as directed.
M&L bush suitable for submersible electric motor of capacity 7.5 HP/5.0 HP as per existing model. Make-Tata/HMT/SKF/NBC.
S&F in replacement of flat submersible cable 3 core of size 6 sqmm, copper conductor complete all as specified and directed.Make:- Finolex/ Havells /Standard
S&F in replacement of saftey wire for hanging submersible pumpset in bore well complete all as specified and directed by Engr in charge.
S&F in replacement of Automatic voltage regulator suitable for Jyothi make alternator of 750KVA DG set.
M&L for disconnecting LT supply and taking out LT draw out EDO type ACB 440V 1250 Amp of (Make:- C&S /L&T) for servicing. Replacing defective parts if any with new as per the existing make and model. Cleaning the fixed and moving parts, removing dust particles by using high speed blower applying grease/jelly to moving mechanism and moving parts, tightening nut bolts of all the components.Reconnecting the cable after carried out servicing and repair work.Testing the ACB for the entire satisfaction of Engr-in-charge all as specified and directed at site. Note:- New spare parts required for making ACB serviceable shall be measured and paid seperately under relavent item of sch.
Supply only isolating JAW contacts suitable for 1250Amp LT draw out EDO type ACB complete all specified and directed at site. (Make- C&S/L&T)
Supply only polyester resin cast CT 1250/5A suitable for 1250/1600Amp LT draw out EDO type ACB complete all as specified and directed at site. (Make- C&S/L&T)
Supply only ARC Chutes for Air circuit brekers EDO type suitable for 1250 Amp ACB complete all as specified and direted at site. (Make:- C&S /L&T)
Supply only Pole Unit for Air circuit brekers EDO type suitable for 1250 Amp ACB complete all as specified and directed at site. (Make:- C&S/L&T)
Supply only Draw out terminals for Air circuit brekers EDO type suitable for 1250 Amp ACB complete all as specified and directed at site. (Make:- C&S /L&T)
Supply only Lower terminals for Air circuit brekers EDO type suitable for 1250 Amp. (Make:- C&S /L&T)
Supply only Upper terminals for Air circuit brekers EDO type suitable for 1250 Amp. (Make:- C&S/L&T)
Supply only Charging motor for Air circuit brekers EDO type suitable for 1250 Amp. (Make:- C&S/L&T)
Supply only shunt trip and closing coil for Air circuit brekers EDO type suitable for 1250 Amp. (Make:- C&S/L&T)
Supply only manual Charging handle for Air circuit brekers EDO type suitable for 1250/1600 Amp. (Make:- C&S/L&T)
Supply only under voltage trip device compact with UVT coil for Air circuit brekers EDO type suitable for 1250/1600 Amp. (Make:- C&S / L&T)
Supply only Safety shutter assembly for Air circuit brekers EDO type suitable for 1250 Amp. (Make:- C&S/L&T)
Supply only Earth fault relay with NCT for Air circuit brekers EDO type suitable for 1250/1600 Amp. (Make:- C&S / L&T)
M&L for disconnecting LT cable and opening AMF panel for servicing. Replacing defective parts if any with new as per existing make and model. Cleaning the fixed/ moving all parts, removing dust particles by using high speed blower, tightening nut bolts and checking all relays, timers and other components. Reconnecting the cable after carried out servicing and repair work.Testing the AMF panel for the entire satisfaction of Engr-in-charge all as specified and directed at site. Note:- New spare parts required for making AMF panel serviceable shall be measured and paid seperately under relavent item of sch.
Supply only electronic alternator voltage relay for AMF panel to operate 415/440 AC Volt, (Make-PIC/L&T/ AE) .
Supply only under voltage relay 440/220 volt AC circuit for AMF Panel, (Make - PIC or Equivalent)
Supply only electronic engine cranking relay to operate in 440/220 volt AC circuit in AMF Panel. (Make - PIC or Equivalent)
Supply only electronic earth fault relay for AMF panel suitable to operate in 440/220 volt AC circuit in AMF panel suitable for 750 KVA DG Set. (Make - PIC or Equivalent)
Supply only over current relay for AMF panel suitable to operate in 440/220 volt AC circuit in AMF panel suitable for 750 KVA DG Set. (Make - PIC or Equivalent)
Supply only reverse power relay for AMF panel suitable for 750 KVA DG Set. (Make - PIC or Equivalent)
Supply only electronic timer for AMF panel suitable for 750 KVA DG Set. (Make - PIC/Teknika or Equivalent)
Supply only main contactor 4 pole, 400 amps, Model MNX-4002P 440/415 volts,50 Hz 415 Volt including connector and mounting accessories,thimbles,nuts, bolts etc all as specified and directed at site. (Make:- TC Model No LCIF330)
M&L for overhauling the heat exchanger of 750 KVA DG set by dismantling from engine chassis frame and carrying to the authorised workshop (Cummins), cleaning and descaling all the dirt/slit in heat exchanger with cleaning cooling tubes including pressure testing for leakage all as per strandard engineering practice including refixing at site to the engine at its original position incl cleaning inlet and out let MS/GI pipes up to 100mm bore all as per site requirement and directed by Engr-in- Charge.
M&L for disconnecting electrically and mechanically defective induction electric motor of capacity 100 HP electrically operated three phase 415 volt,shifting to civil workshop for repair,strip opening for inspection,cutting of unserviceable burnt winding, taking out,cleaning of slots,rewinding with new super enameled ,of existing size of copper conductor winding wire and replacement of unserviceable burnt insulating materials,sleeves etc,varnishing and other connected works,re-assembling,re-fixing at site,electrical connection fixing with pump set with nuts,bolts,washers as per original position and testing complete all as directed for satisfactory operation. Note :- (i) T&P items and any other minor items required for installation and commissioning of electric motor will deemed to be including in the quoted rates. (ii) Any electric connection,nut, bolts,washers,flanges including welding and cutting work will deemed to be including in quoted rates. (iii) Any major spares/ parts required for making the motor serviceable shall be measured and paid separately under relevant items of Sch.
All as per srl item No 59 here-in-before but capacity of 60 HP
All as per srl item No 59 here-in-before but capacity of 15 HP
All as per srl item No 59 here-in-before but capacity of 12.5 HP
All as per srl item No 59 here-in-before but capacity of 10 HP
All as per srl item No 59 here-in-before but capacity of 7.5 HP
All as per srl item No 59 here-in-before but capacity of 5 HP
All as per srl item No 59 here-in-before but capacity of 3 HP
All as per Ser item No 59 here-in-before but capacity of 1.5/1.0 HP
M&L for dismantling defective centrifugal/mono block pump of capacity 125 HP and shifting from installation to civil work shop for repairing and replacement of bearings, impeller, shaft, gun metal bush, gland packing and gland plate, nut bolt and washers,studs, gaskets etc. and reassembling /fixing at site to it's original position incl testing on load for smooth functioning all as directed including transportation charges,testing and commissioning all as directed by the Engineer-in- Charge. Note :- (i) T&P items and any other minor items required for installation and commissioning of pump set will deemed to be including in the quoted rates. (ii) Any spares/ parts required for making the pump set serviceable shall be measured and paid separately under relevant items of Sch.
All as per srl item No 68 here-in-before but capacity of 100 HP
All as per srl item No 68 here-in-before but capacity of 60 HP
All as per srl item No 68 here-in-before but capacity of 15 HP
All as per srl item No 68 here-in-before but capacity of 12.5 HP
All as per srl item No 68 here-in-before but capacity of 10 HP
All as per srl item No 68 here-in-before but capacity of 7.5 HP
All as per srl item No 68 here-in-before but capacity of 5 HP
All as per srl item No 68 here-n-before but capacity of 3 HP
All as per Ser item No 68 here-in-before but capacity of 1.5/1.0 HP
Supply only Ball bearing for electric motor of capacity 100 HP as per existing model/6315 2Z Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 60 HP as per existing model 6314 2Z Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 15 HP as per existing model 6307 2Z Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 12.5/10.0 HP as per existing model 6306 2Z Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 7.5 HP as per existing model 6205 2Z Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 5 HP( Pump & motor) as per existing model 6204 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 3 HP(Pump & motor) as per existing model 6203 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 78 here-in-before but of capacity 1.5/1.0 HP(Pump & Motor) as per existing model 6202 Make-Tata/HMT/SKF/NBC.
Supply only Ball bearing for Pump of capacity 125 HP as per existing model/6313 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 86 here-in-before but of capacity 100 HP as per existing model 6312 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 86 here-in-before but of capacity 60 HP as per existing model 6311 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 86 here-in-before but of capacity 15 HP as per existing model 6207 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 86 here-in-before but of capacity 12.5 HP as per existing model 6206 Make-Tata/HMT/SKF/NBC.
All as per Ser Item No. 86 here-in-before but of capacity 10/7.5 HP as per existing model 6205 Make-Tata/HMT/SKF/NBC.
Supply only Gun metal/CI Impeller (as existing) suitable for centifugal pump of capacity 125 HP
All as per Ser Item No. 92 but of capacity 100 HP
All as per Ser Item No. 92 but of capacity 60 HP
All as per Ser Item No. 92 but of capacity 15 HP
All as per Ser Item No. 92 but of capacity 12.5 HP
All as per Ser Item No. 92 but of capacity 10 HP
All as per Ser Item No. 92 but of capacity 7.5 HP
All as per Ser Item No. 92 but of capacity 5 HP
All as per Ser Item No. 92 but of capacity 3 HP
All as per Ser Item No. 92 but of capacity 1.5/1.0 HP
Supply only complete gasket set suitable for centrifugal pump set of capacity 125 HP
All as per Ser Item No. 102 but of capacity 100 HP
All as per Ser Item No. 102 but of capacity 60 HP
All as per Ser Item No. 102 but of capacity 15 HP
All as per Ser Item No. 102 but of capacity 12.5 HP
All as per Ser Item No. 102 but of capacity 10 HP
All as per Ser Item No. 102 but of capacity 7.5 HP
All as per Ser Item No. 102 but of capacity 5 HP
All as per Ser Item No. 102 but of capacity 3 HP
All as per Ser Item No. 102 but of capacity 1.5/1.0 HP
Supply only gun metal shaft suitable for centrifugal pump set of capacity 100 HP as per existing model and make for Kirloskar/Crompton Greaves make pump set all as required and as direted by the Engr-in-Charge.
All as per Ser Item No. 112 here-in-before but of capacity 60 HP
All as per Ser Item No. 112 here-in-before but of capacity 15 HP
All as per Ser Item No. 112 here-in-before but of capacity 12.5 HP
All as per Ser Item No. 112 here-in-before but of capacity 10/7.5 HP Note for Item No. 78 to 116: Labour Charges for fixing of item no. 78 to 116 are included in the quoted rate of item no. 59 to 77.
M&L for re-metaling/machining work for shaft of centrifugal pump set of capacity 125 HP,welding, grinding, polishing and matching to reqiured size/shape complete all as suitable to the pump and as directed by the Engr-in-charge.
All as per Ser Item No. 117 here-in-before but of capacity 100 HP
All as per Ser Item No. 117 here-in-before but of capacity 60 HP
All as per Ser Item No. 117 here-in-before but of capacity 15/12.5 HP
All as per Ser Item No. 117 here-in-before but of capacity 10/7.5 HP
All as per Ser Item No. 117 here-in-before but of capacity 5/3 HP
All as per Ser Item No. 117 here-in-before but of capacity 1.5/1.0 HP
Supply and fixing MS coupling including flexible tyre, nuts, bolts and washers suitable for centrifugal motor pump set 125 HP capacity complete match with existing one Make - Mitutoya Shakti/Unique/Lovejoy/Dunlup or equivalent.
All as per Ser Item No. 124 but of capacity 100 HP
All as per Ser Item No. 124 but of capacity 60 HP
All as per Ser Item No. 124 but of capacity 15/12.5 HP
All as per Ser Item No. 124 but of capacity 10/7.5 HP
M&L opening of 60000 CFM centrifugal DIDW blower, cleaning of all parts, dismantling and taking out unserviceable ball bearing and fixing of new ball bearings, alignment of blower and pulley block, welding/cutting work and replacement of unserviceable/rusted MS sheet pieces as required at site, re-assembling of the same and re-fixing at existing location by proper tightening of nuts, bolts and washers complete all as specified and as directed. Note: - (i) Cost of new nuts, bolts, washers as required at site will deemed to be included in quoted rates. (ii ) Cost of ball bearings will be paid separately under relavent item of sch.
Taking out old unserviceable celluloid honeycomb filter pad of thickness 200mm from forced ventilation, cleaning the tower completely and fixing new celluloid honeycomb filter pad of thickness 200mm as per existing for forced ventilation at CRF complete all as specified and directed.
M&L disconnecting electrically, opening of 40 HP electric motor, 3 phase, 415 volts of Make-Kirloskar, cleaning of all parts, dismantling and taking out unserviceable ball bearing and fixing of new ball bearings, Varnishing of motor, alinment of pulley, re-assembling of the same and re-fixing at existing location by proper tightening of nuts, bolts and washers all as specified and as directed. Note: - (i) Cost of ball bearings will be paid separately under relavent item of sch. (ii) Cost of new nuts, bolts, washers as required at site will deemed to be included in quoted rates.
Supply only ball bearing for electric motor of capacity 40 HP 6312/C3. Make-Tata/HMT/ SKF/ NBC.
Supply only ball bearing for 60000 CFM centrifugal DIDW blower of 6315/C3 Make- Ventil Air as per existing model. Make-Tata/HMT/ SKF/ NBC.
Supply only ball bearing for 20000 CFM airwasher unit's blower of P210 as per existing make and model complete all as directed by Engr-in-charge.
S&F in replacement of 'V' belt of size B-84 Make-Fenner/Dunlup
S&F in replacement of 'V' belt of size B-195 Make-Fenner/Dunlup
S&F in replacement of 'V' belt of size B-230 Make-Fenner/Dunlup
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-50 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-45 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-40 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-32 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-25 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-18 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of 3 pole power contactor, 3 phase, 415 volts, 50 Hz type MNX-12 including front mounting add-on auxiliary contact block Make-L&T/ABB/Siemens.
S&F in replacement of MCCB Four pole 250 Amps,36KA,415 volts with thermal magnetic release model DPX 250 of Make:- Legrand/ Havells/ ABB
S&F in replacement of MCCB Three pole 100 Amps,36KA,415 volts with thermal magnetic release model DPX 160 of Make:- Legrand/ Havells/ ABB
S&F in replacement of overload relay suitable for range 14-23 A, type MN2 (As per existing sample) Make-L&T/ABB/Siemens.
S&F in replacement of overload relay suitable for range 30-50 A,(As per existing sample) Make- L&T/ABB/Siemens.
S&F in replacement of overload relay suitable for range 45-75 A, type MN5,(As per existing sample) Make- L&T/ABB/Siemens.
S&F in replacement of electronic timer, 3 phase, 240/415 volts, 50 Hz type ET-100, 12 to 120 second of Make-L&T/ABB/Siemens.
S&F in replacement of single phase preventer 415 volts, suitable for 3 phase supply. Make:Minilec/L&T/AE
S&F in replacement of 3 Phase, 415 volt, 50 Hz Semi Automatic Star- Delta starter in sheet steel enclosure suitable for 12.5/ 7.5 HP motor. Make-Havells/L&T/HPL
S&F in replacement of 3 phase,415 volt, 50 Hz, DOL starter suitable for upto 7.5/5 HP motor. Make-Havells/L&T/HPL
S&F in replacement of electronic battery charger with input 240V AC and output 24V DC (As per existing sample) Make- Teknika TE-1200 or equivalent
S&F in replacement of sealed lead acid battery of 12V, 12AH capacity (as per existing sample) Make- Exide,type EP 12-12 or equivalent.
M&L for Indicator lamp LED type of any colour as per site requirement out of Red/Yellow/Blue or green Make-L&T/AE/Siemens
Removing cable connections and taking out unserviceable/ burnt on load change over switch 4 Pole 1250 Amps and Supply, installation & testing of on load change over switch 4 Pole 415 Volts, 50 Hz, 1250 Amps, complete as specified and directed. Make:Havells(Cat No. IHCNF01250)/L&T
Lifting of old unserviceable submersible pump set of capacity 5 HP from bore well of depth 40 to 50 mtr disconnecting electrical cables and coloumn pipe from submersible pump set and Supply, installation, lowering,commisioning & testing of submersible pump set 5HP/3.7KW,50mm outlet size, head range 50-11 meters and discharge150-330 LPM complete all as specified and as directed by Engr-in-charge
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr in deep for foundation etc.or for shafts,wells,cesspits,mainholes,pierholes etc.in any type of soil for foundation and getting out and leveling of bottom surface to required level complete all as specified and directed.
Returning filling including leveling,watering and well ramming soil in layers not exceeding 25 Cm complete all as specified and directed.
Removing the excavated materials not exceeding 50 m and depositing where directed at level not exceeding 1.5 m above the starting level complete all as specified and directed.
Cutting of existing road/PCC/RCC/Hard standing for laying of pipe including making good the distrubed surface to match with the adjoining surfaces with PCC 1:3:6 type C2 using 20 mm graded stone aggregate complete all as specified and directed.
Supplying, laying and connecting in replacement GI water tubing 100mm bore, medium grade with all fittings with screwed and socketed joints and fixed complete in trenches, wall ceiling or laid in floor complete and making good the disturbed surface all as specified and directed by Engr-in-charge. Make:- TATA/BST/JINDAL
All as per ser item No 164 here-in-before but size 80 mm bore
All as per ser item No 164 here-in-before but size 50 mm bore
All as per ser item No 164 here-in-before but size 40 mm bore
All as per ser item No 164 here-in-before but size 25 mm bore
All as per ser item No 164 here-in-before but size 20 mm bore
All as per ser item No 164 here-in-before but size 15 mm bore
Supply,laying,testing and connecting in replacement MS Pipe Size 300 mm dia, 6.3 mm thick heavy duty, flanged ends including rubber packing nut, bolt ,washer and butt welded fittings conforming to IS -3589 complete in trenches, wall, ceiling or laid in floor complete and making good the disturbed surface all as specified and directed by Engr-in-charge. Make : Jindal/Tata/BST
All as per ser item No 171 here-in- before but of size 200 mm bore but of thickness 5.9 mm thick
All as per ser item No 171 here-in- before but of size 150 mm bore but of thickness 5.4 mm thick
All as per ser item No 171 here-in- before but of size 100 mm bore but of thickness 5.4 mm thick
All as per ser item No 171 here-in-before but of size 80 mm bore but of thickness 4.85 mm thick
Supply and fixing in replacement of heavy duty, lined flexible pipe of size 100 mm dia including re-connecting of existing foot valve after cleaning in sewage installations under ground all as per site requirement and all as diected.
S&F in replacement of Sluice Valve Class PN 1.6, 200 mm dia flange type suitable for external bye pass arrangement including nut,bolts & washers etc complete all as specified and directed by Engineer-in- Charge. Make :- Kirloskar/Sant/Kartar
All as per ser item No 177 here-in- before but of size of 150 mm bore
S&F in replacement of Butter fly valve 300 mm bore flange type suitable for external bye pass arrangement including nut,bolts & washers etc complete all as specified and directed. Make :- Sant/Kartar/Kirloskar
All as per ser item No 179 here-in- before but of size of 200 mm bore
All as per ser item No 179 here-in- before but of size of 150 mm bore
All as per ser item No 179 here-in-before but of size of 100 mm bore
AAll as per ser item No 179 here-in-before but of size of 80 mm bore
All as per ser item No 179 here-in-before but of size of 50 mm bore
Supply and fixing in replacement of cast iron body, Non return valve size 100 mm bore suitable for insertion between flanges complete all as specified and as directed. Make :- Kirloskar/Sant/Kartar)
All as per ser item No 185 here-in- before but of size of 80 mm bore
All as per ser item No 185 here-in- before but of size of 50 mm bore
S&F in replacement of Y type strainer MS body flanged ends suitable for pipe line of size 300 mm dia complete all as specified and as directed.(Make : Sant/Kirloskar/Kartar)
S&F in replacement Gun -metal ,globe or gate valves with iron wheel head, screwed/ flanged both ends as per site requirement of size 80 mm bore.Make : Sant/Kartar/Leader
All as per Ser item No 189 above but 50 mm bore
All as per Ser item No 189 above but 40 mm bore
All as per Ser item No 189 above but 25 mm bore
All as per Ser item No 189 above but 20 mm bore
All as per Ser item No 189 above but 15 mm bore
S&F in replacment of Ball brass valves,high pressure,with polythene float and flynut 50mm bore complete,screwed for iron pipe or brass ferrule and fixed all complete all as specified and directed.
All as per Ser item No 195 here-in-before but 40 mm bore
All as per Ser item No 195 here-in-before but 25 mm bore
All as per Ser item No 195 here-in-before above but 20 mm bore
M & L in replacement of PTMT float valve complete with epoxy coated aluminium rod and HD wall of size 25 mm bore, complete all as specified and directed. Make : Prayag/Leader/Prima
All as per Ser item No 199 here-in-before but of size 20 mm bore
All as per Ser item No 199 here-in-before but of size 15 mm bore
S&F in replacement of Gun Metal Foot valve of 100 mm bore complete all as specified and directed. Make : Sant/Kirloskar/Kartar/Swastik
All as per ser item No 202 above but 80 mm bore .
All as per ser item No 202 above but 50 mm bore .
All as per ser item No 202 above but 40 mm bore .
All as per ser item No 202 above but 25 mm bore .
Attending of complaints of external water supply installation as and when required / called up by this office for non functional of borewell submersible pumps or any water supply mains / distribution lines / control valves to make the water supply installation functional round the clock. minor repair will be carriedout on spot and other major item will be measured & paid seperately complete all as specified and directed. Note :- (i) T&P items and any other minor items required for making water supply installation functional will deemed to be including in the quoted rates.
Supply only in replacement of GI socket 50mm / 40mm size ISI marked complete all as specified and directed
Supply only in replacement of GI socket 25mm / 20mm / 15mm size ISI marked complete all as specified and directed
Supply only in replacement of GI elobow 50mm / 40mm size ISI marked complete all as specified and directed
Supply only in replacement of GI elobow 25mm / 20mm /15mm size ISI marked complete all as specified and directed
Supply only in replacement of GI union 50mm / 40mm size ISI marked complete all as specified and directed
Supply only in replacement of GI union 25mm / 20mm / 15mm size ISI marked complete all as specified and directed
Supply only in replacement of GI equal tee 50mm / 40mm size ISI marked complete all as specified and directed
Supply only in replacement of GI equal tee 25mm / 20mm /15mmsize ISI marked complete all as specified and directed
Supply only in replacement of GI nipple of size 50mm / 40mm into 4 inch / 6 inch long ISI marked complete all as specified and directed
Supply only in replacement of GI nipple of size 25mm / 20mm /15mm into 4 inch or 6 inch long ISI marked complete all as specified and directed
Supply only in replacement of GI reducer of size 50/40mm or 50/25mm ISI marked complete all as specified and directed
Supply only in replacement of GI reducer of size 40/25mm or 40/20mm ISI marked complete all as specified and directed
Supply only in replacement of GI reducer of size 25/20mm or 25/15mm or 20/15mm ISI marked complete all as specified and directed. Note for Item No. 208 to 220: Labour Charges for fixing of item no. 208 to 220 are included in the quoted rate of item no. 207.
M&L opening of 80000 CFM centrifugal DIDW blower, cleaning of all parts, dismantling and taking out unserviceable ball bearing and fixing of new ball bearings, alignment of blower and pulley block, welding/cutting work and replacement of unserviceable/rusted MS sheet pieces as required at site, re-assembling of the same and re-fixing at existing location by proper tightening of nuts, bolts and washers complete all as specified and as directed. Note: - (i) Cost of new nuts, bolts, washers as required at site will deemed to be included in quoted rates. (ii ) Cost of ball bearings and shaft will be paid separately under relavent item of sch.
M&L opening of 20000 CFM airwasher unit, cleaning of all parts, dismantling and taking out unserviceable ball bearing and fixing of new ball bearings, alignment of blower and pulley block, welding/cutting work and replacement of unserviceable/rusted MS sheet pieces as required at site, re-assembling of the same and re-fixing at existing location by proper tightening of nuts, bolts and washers complete all as specified and as directed. Note: - (i) Cost of new nuts, bolts, washers as required at site will deemed to be included in quoted rates. (ii ) Cost of ball bearings and shaft will be paid separately under relavent item of sch.
Supply only gun metal shaft suitable for 20000 CFM centrifugal DIDW blower as per existing model and make all as required and as direted by the Engr-in-Charge.
Supply only gun metal shaft suitable for 60000 CFM centrifugal DIDW blower as per existing model and make all as required and as direted by the Engr-in-Charge.
Supply only gun metal shaft suitable for 80000 CFM centrifugal DIDW blower as per existing model and make all as required and as direted by the Engr-in-Charge.
Supply only ball bearing for 80000 CFM centrifugal DIDW blower of P215 complete all as per existing make and model and directed by Engr-in-charge
Supply only LPG gas duly filled in commercial gas cylinder of 19 Kgs capacity each in replacement of empty cylinders Make-Bharat Gas.
S&F in replacement gas control valve made out of brass of size 15 mm for fixing to individual control of each cylinder. Make-Vanaz/Audco/Equivalent ISI marked all as directed.
S&F in replacement heavy duty flexible gas connection pipe from pipe to gas cylinder as per existing size and sample all as directed.
GLIBS CONSTRUCTION
JIWAN DASS THAREJA AND SONS
national engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .