Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.0 CrAccepted-AOC | ₹1.0 Cr | L1 | Accepted-AOC Accepted lowest quoted tenderer |
| 2 | L2₹1.1 Cr+₹6.4 L (6.10%)Rejected-AOC | ₹1.1 Cr+₹6.4 L (6.10%) | L2 | Rejected-AOC Rejected other than lowest quoted tenderer |
| 3 | L3₹1.1 Cr+₹8.8 L (8.40%)Rejected-AOC | ₹1.1 Cr+₹8.8 L (8.40%) | L3 | Rejected-AOC Rejected other than lowest quoted tenderer |
| 4 | L4₹1.2 Cr+₹12.5 L (11.9%)Rejected-AOC A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | ₹1.2 Cr+₹12.5 L (11.9%) | L4 | Rejected-AOC Rejected other than lowest quoted tenderer |
| Sl No | Description | Qty | Unit | JAZZCON ENGINEERS PVT LTD L1 | Avion Industries L2 | M/S ADHIKARI CONSTRUCTION CO. L4 | UMESH TRADERS L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, commissioning and testing transformer floor mounted capacity 3.15 MVA step down, outdoor type, 50 Cycle/Sec (50 Hz),conforming to IS 2026 Part-1 (2011) having No load Voltage ratio at rated voltage 33 KV/11 KV , AC double wound core type copper wound oil immersed oil natural air naturally cooled (ONAN) type with external cooling tubes/ fins, transformer delta connection on primary side (33 KV) and star connection on secondary side (11 KV) in accordance with vector symbol DYN-11 and having tapping ranges from + 10% to - 15% @ 1.25% (20 steps/ 21 Positions) changed by means of auto ON LOAD TAP CHANGING arrangement alongwith its panel RTCC(Remote tap changer control alongwith AVR) with option for manual tap changing arrangement. The voltage regulation shall be as per IS. The limit of temperature rise after continuous full load run not exceeding 50 degree celsius for Oil and not exceeding 55 degree celsius for winding resistance as specified in SSR Part I and IS 2026 shall be suitable & adjustable to suit the maximum ambient temperature prevelling at the site .The Winding shall be made with 99.9% pure electrolytic grade copper, insulated with high grade paper Insulation (Class A) and the Losses in transformer i.e. No load losses and load losses are as per IS 2026 tolerance limit (No load Loss : 3.0 KW ( Sub to IS Tolerance) Load Loss at 100% Load and 75 Degree Celsius : 16 KW @ 3.5 MVA base ( Sub to IS Tolerance) the %Impedance- 7.15% @3.15 MVA base (sub to IS Tolerance) complete all as specified and as directed.
Make - Crompton/ Schneider /ABB/Siemens | 1 | Each Job | 66,14,000 ₹66,14,000 | 69,00,000 ₹69,00,000 | 49,99,999 ₹49,99,999 Lowest | 57,50,000 ₹57,50,000 |
| 1.01The manufacturer of transformer must have ISO certificate with LAB approved by NABL to ascertain genuine product quality. The manufacturer shall provide 05 Years warranty certificate for the transformer supplied to the department through contractor and a affidavit to this regard shall also be submitted by the Contractor. The transformer shall be completed with following fittings and accessories :- (a) Cable boxes on 11 KV secondary side for 3 core XLPE 185 sqmm x 3 core cable end.LV bushings on 11 Kv side must be as per 12 KV class. (b) HV bushing with arching horn on 33 KV side and must be of 36 KV class. (c) Oil conservator with filling hole and cap drain plug and oil level gauge. (d) Dehydrating breather with connecting pipe first fill of dehydrating agent (silica gel) and oil seal. (e) Explosion relief vent mounted on tank with double diaphragm and equaliser pipe connection to conservator air space (pressure release device). (f) Air release plug. (g) Shutoff valve between the conservator and cooilng tubes. (h) Filter valve with threaded adopter (Top and bottom). (j) Thermometer pocket. (k) Inspection cover. | |||||||
| 1.02(l) Jacking pads, handling and lifting lugs. (m) Skid type underbase channel with Wheels. (n) Rating plate and terminal marking plate. (o) Extra bushing for neutral out side the LV side. (p) First filling of transformer oil. Transformer oil shall be as per IS:335 (Year 1993) (q) Cover lifting eyes. (r) Double float Bucholz relay with trip and alarm contacts. (s) Dial type oil temperature indicator with alarm and trip contacts. (t) Dial type winding temperature indicator with alarm and trip contacts. (u) Overloading capacity as per IS :6600 (Year 1978) (v) Noise level as per NEMA TR 1 (w) Foundation as per manufacturer's instructions including Rail section and channel embeded in foundation of suitable size in and incl RCC/PCC platform incl ramp and necessary earthwork and excavation as directed. Make: Crompton/ Schneider /ABB/Siemens (x) OLTC (on load tap changer) RTCC (remote tap change control) panel along with AVR control Relay. (y) Marshalling box | |||||||
| 2.00 | Supply and installation, testing and commissioning of Outdoor type HT 33 KV ,3 phase, 50 cycles 1600 Amps, 25 kA, Non-Extensible fixed Type , SF6 Gas insulated compact switchgear comprising of motorised fixed type Breaker contacts including the following with all necessary standard fitting :-
(a) Live tank SF6 breaker with rated pressure of SF6 in operating chamber at 20 degree C - 5 kg/sqcm with motorised spring type operation for closing and opening.
(b) Rated voltage 36 KV (rms), rated current 1600 Amp at 50 Hz.
(c) No of poles - 3 with SF6 gas parameters as per IEC-60376.
(d) Rated assymetric breaking current 28.4 kA.
(e) Rated short circuit peak withstand current at rated voltage 62.5 kA (peak).
(f) Rated short time withstand current 26.3 kA for 1 sec and 3 sec.
(g) Integrated non-removable spring-charging operating handle and ON/OFF push buttons mechanically attached to the mechanisum.
(h) Rated break time </=80 ms, closing time </=100 ms, Opening time </=50 ms.
(j) Arc proof cable covers with self interlocking mechanism earth switch, disconnector.
(k) Mechanical indications for breaker ON, OFF, EARTH TRIP, Spring Charged-Discharged. | 1 | Each Job | 3,90,000 ₹3,90,000 Lowest | 7,00,000 ₹7,00,000 | 9,99,999 ₹9,99,999 | 5,75,000 ₹5,75,000 |
| 3.00 | Supply, install, testing and commissioning indoor type Control and Relay Panel(CRP) for 33 KV SF6 breaker made of CRCA Sheet 2mm thick, standard size, prewired with suitable size copper conductor, enclosed cubical type free standing, dust tight, vermin proof, powder coated RELAY CONTROL PANEL FOR PROTECTION METERING OF 33 KV EQUIPMENT AND TRANSFORMER, suitable for 24 V DC supply, duplex type to house the following accessories as per the following specification :-
(A) Control & Relay Panel.
(a) Control & Relay Panel - Siplex type - 01 No.
(b) Colour code wiring - 01 No.
(c) Paint shade - 631 of IS5 - 01 No.
(d) Neoprene Gaskets - 01 No.
(e) Degree of protection - IP55 - 01 No.
(f) Control voltage - 110 VDC - 01 No.
(B) Meters.
(a) Digital Ammeter with ASS - 01 No.
(b) Digital voltmeter with VSS - 01 No.
(c) Multifunction Meter - 01 No. | 1 | Each Job | 3,70,000 ₹3,70,000 Lowest | 6,10,000 ₹6,10,000 | 9,99,999 ₹9,99,999 | 5,17,500 ₹5,17,500 |
| 3.01(d) Energy Meter - 01 No. (C) Indication Lamps LED Type. (a) Breaker ON - Red - 01 No. (b) Breaker OFF - Green - 01 No. (c) Auto trip indication - Amber - 01 No. (d) Trip circuit healthy - Clear - 01 No. (e) Spring charged - Blue - 01 No. (f) RYB Indication - 01 No. (D) Accessories. (a) Push Button for trip circuit healthy check - 01 No. (b) Trip Neutral close switch - 01 No. (c) Local remote switch - 01 No. | |||||||
| 3.02(d) Panel space heater with thermostat & switch - 01 No. (e) Panel illumination lamp with switch - 01 No. (f) 2/3 pin plug with switch - 02 Nos. (g) 6 - Window Annunciator - 01 No. (h) Hooter - 01 No. (j) Semaphore Indicator - 01 No. (k) Mimic Diagram - 01 No. (l) Test terinal block - 01 No. (E) Relays. (a) Numerical communication non-drawout type relay with 50/51/50N for overcurrent and earth fault protection- 01 No. (b) Trip Circuit supervision relay - 01 No. (c) Master trip relay - 01 No. (d) Transformer Differential Relay-01 No as per suitable PS class CTs connection in 33 KV side and 11 KV side - 01 No. (e) Auxiliary relay -03 Nos for protection of following: (i) One for Buchholz Relay alarm & trip (ii) Second for Oil Temp alarm and trip (iii) Third for Winding Temp Alarm and Trip | |||||||
| 4.00 | Supplying, installation, commissioning and testing HT 11 KV 630 Amp Vacuum Circuit Breaker panel of 3 with 01 incoming and 2 outgoing indoor type, horizontal isolation type, motor operated spring charged having rupturing capacity 18.4 KA for 1 sec by connecting to the HT Panel board with the help of copper bus bar of suitable size duly enclosed in CRCA frame and panel shall be not less than 2.0 mm thickness and comprising of the following including dismantling and taking out the old unserviceable VCB -3 Nos all as specified and directed by Engr -in- Charge . The Panel shall be manufactured by approved OEM.
(a) Electrical and mechanical interlock and automatic safety shutter door.
(b) Power pack for control circuits/
(c) Assembly of three vaccum interrupter complete with epoxy support insulator and self alligning finger type isolating contacts, 630 Amps breaking capacity 18.4 KA
(d) 230 Volts AC motorised mechanism, spring charging with independent closing /tripping push buttons and menhanical breaker "close/open" spring charged / discharged indication.
(e) Mechanical operation counter
(f) Electrical release coil 24 Volts DC
(g) Shunt trip /close coil 24 volts DC | 1 | Each Job | 19,18,000 ₹19,18,000 | 17,50,000 ₹17,50,000 | 24,99,999 ₹24,99,999 | 15,52,500 ₹15,52,500 Lowest |
| 4.01(h) Auxillary Switch (j) 230 Volts AC single phase 80 watt rated strip heater with toggle switch and thermostat-03 Nos (for each 03 VCBs) (k) Cable termination for 1 x 3C x 185 Sq mm XLPE cable (for incoming & outgoing). (l) Digital Ammeter flush type CT operated - 03 sets (For incoming VCB and outgoing VCBs). (m) Digital Voltmeter flush type - 03 sets (For incoming VCB and outgoing VCBs). (n) Digital Multimeter/ Energy analyser flush type - 03 sets (For incoming VCB and outgoing VCBs). (o) Numerical type 3 phase over current and earth fault relay with 50/51/50N/51N protection, - 03 Nos (For incoming VCB and outgoing VCBs) Make:- ABB/SEIMENS/SCHNEIDER/CG (p) Numerical type 3 phase over/ under voltage relay with 27/59 protection, -03 Nos (For incoming VCB and outgoing VCBs) ABB/Seimens/Schneider/ CG/Ashida/C&S/L&T (q) Master Trip Relay of make: CG or equivalent in make as mentioned in Appendix 'A' to PS - 03 Nos (For incoming VCB and outgoing VCBs) (r) LED Indication lamps for Breaker ON, Breaker OFF, Auto Trip, Trip circuit healthy, Spring Charged, RYB indication as per standard colour code. | |||||||
| 4.02(s) Push button for Trip Circuit healthy. (t) Cable gland of suitable size. (u) Cubical LED illumination lamp - 01 . (v) Potential transformer ratio three single phase draw out type 11 KV/rt3/110V/rt3 class 0.5, burden 100 VA (set of 3) - 1 set for Incomer VCB. (w) Battery bank, comprising of 02 Volt, 180 AH, 12 Nos battery and battery charging system made of 1.6 mm thick CRCS sheet all as specified 24 volts DC for Auxillary supply. (x) Epoxy Rasin cast CT of ratio 400-200/ 5-5 class 0.5/ 5P10, burden 15VA/15 VA for incomer VCB (set of 3) - 1 set. (y) Epoxy Rasin cast CT of ratio 300-150/ 5-5 class 0.5/ 5P10, burden 15VA/15 VA for outgoing VCBs (set of 3) - 2 sets. (z) PS class CT of suitable rating for the differential relay protection connection in the 11 KV side | |||||||
Tender Value
₹1.2 Cr
EMD Value
₹1.9 L
Closing Date
10 Nov 2025, 6:00 pmClosed
HQ CWE New Cantt Prayagraj
HQ CWE Prayagraj
PROVISION OF STANDBY POWER TRANSFORMER 3.15 MVA WITH CONNECTED WORKS AT AYODHYA UNDER AGE (I) AYODHYA CANTT.
2025_MES_718366_2
81990/AYD/E8
Open Tender
Civil Works
Item Rate
180 days
Ayodhya
Class B and Category b(iii)
6 documents required · 6 mandatory
₹1,000
AGE (I) Ayodhya
₹1.9 L
Yes
7 Feb 2026
25 Oct 2025
17 Nov 2025
25 Oct 2025
10 Nov 2025
3 Nov 2025
Amount
Supply, installation, commissioning and testing transformer floor mounted capacity 3.15 MVA step down, outdoor type, 50 Cycle/Sec (50 Hz),conforming to IS 2026 Part-1 (2011) having No load Voltage ratio at rated voltage 33 KV/11 KV , AC double wound core type copper wound oil immersed oil natural air naturally cooled (ONAN) type with external cooling tubes/ fins, transformer delta connection on primary side (33 KV) and star connection on secondary side (11 KV) in accordance with vector symbol DYN-11 and having tapping ranges from + 10% to - 15% @ 1.25% (20 steps/ 21 Positions) changed by means of auto ON LOAD TAP CHANGING arrangement alongwith its panel RTCC(Remote tap changer control alongwith AVR) with option for manual tap changing arrangement. The voltage regulation shall be as per IS. The limit of temperature rise after continuous full load run not exceeding 50 degree celsius for Oil and not exceeding 55 degree celsius for winding resistance as specified in SSR Part I and IS 2026 shall be suitable & adjustable to suit the maximum ambient temperature prevelling at the site .The Winding shall be made with 99.9% pure electrolytic grade copper, insulated with high grade paper Insulation (Class A) and the Losses in transformer i.e. No load losses and load losses are as per IS 2026 tolerance limit (No load Loss : 3.0 KW ( Sub to IS Tolerance) Load Loss at 100% Load and 75 Degree Celsius : 16 KW @ 3.5 MVA base ( Sub to IS Tolerance) the %Impedance- 7.15% @3.15 MVA base (sub to IS Tolerance) complete all as specified and as directed. Make - Crompton/ Schneider /ABB/Siemens
The manufacturer of transformer must have ISO certificate with LAB approved by NABL to ascertain genuine product quality. The manufacturer shall provide 05 Years warranty certificate for the transformer supplied to the department through contractor and a affidavit to this regard shall also be submitted by the Contractor. The transformer shall be completed with following fittings and accessories :- (a) Cable boxes on 11 KV secondary side for 3 core XLPE 185 sqmm x 3 core cable end.LV bushings on 11 Kv side must be as per 12 KV class. (b) HV bushing with arching horn on 33 KV side and must be of 36 KV class. (c) Oil conservator with filling hole and cap drain plug and oil level gauge. (d) Dehydrating breather with connecting pipe first fill of dehydrating agent (silica gel) and oil seal. (e) Explosion relief vent mounted on tank with double diaphragm and equaliser pipe connection to conservator air space (pressure release device). (f) Air release plug. (g) Shutoff valve between the conservator and cooilng tubes. (h) Filter valve with threaded adopter (Top and bottom). (j) Thermometer pocket. (k) Inspection cover.
(l) Jacking pads, handling and lifting lugs. (m) Skid type underbase channel with Wheels. (n) Rating plate and terminal marking plate. (o) Extra bushing for neutral out side the LV side. (p) First filling of transformer oil. Transformer oil shall be as per IS:335 (Year 1993) (q) Cover lifting eyes. (r) Double float Bucholz relay with trip and alarm contacts. (s) Dial type oil temperature indicator with alarm and trip contacts. (t) Dial type winding temperature indicator with alarm and trip contacts. (u) Overloading capacity as per IS :6600 (Year 1978) (v) Noise level as per NEMA TR 1 (w) Foundation as per manufacturer's instructions including Rail section and channel embeded in foundation of suitable size in and incl RCC/PCC platform incl ramp and necessary earthwork and excavation as directed. Make: Crompton/ Schneider /ABB/Siemens (x) OLTC (on load tap changer) RTCC (remote tap change control) panel along with AVR control Relay. (y) Marshalling box
Supply and installation, testing and commissioning of Outdoor type HT 33 KV ,3 phase, 50 cycles 1600 Amps, 25 kA, Non-Extensible fixed Type , SF6 Gas insulated compact switchgear comprising of motorised fixed type Breaker contacts including the following with all necessary standard fitting :- (a) Live tank SF6 breaker with rated pressure of SF6 in operating chamber at 20 degree C - 5 kg/sqcm with motorised spring type operation for closing and opening. (b) Rated voltage 36 KV (rms), rated current 1600 Amp at 50 Hz. (c) No of poles - 3 with SF6 gas parameters as per IEC-60376. (d) Rated assymetric breaking current 28.4 kA. (e) Rated short circuit peak withstand current at rated voltage 62.5 kA (peak). (f) Rated short time withstand current 26.3 kA for 1 sec and 3 sec. (g) Integrated non-removable spring-charging operating handle and ON/OFF push buttons mechanically attached to the mechanisum. (h) Rated break time </=80 ms, closing time </=100 ms, Opening time </=50 ms. (j) Arc proof cable covers with self interlocking mechanism earth switch, disconnector. (k) Mechanical indications for breaker ON, OFF, EARTH TRIP, Spring Charged-Discharged.
Supply, install, testing and commissioning indoor type Control and Relay Panel(CRP) for 33 KV SF6 breaker made of CRCA Sheet 2mm thick, standard size, prewired with suitable size copper conductor, enclosed cubical type free standing, dust tight, vermin proof, powder coated RELAY CONTROL PANEL FOR PROTECTION METERING OF 33 KV EQUIPMENT AND TRANSFORMER, suitable for 24 V DC supply, duplex type to house the following accessories as per the following specification :- (A) Control & Relay Panel. (a) Control & Relay Panel - Siplex type - 01 No. (b) Colour code wiring - 01 No. (c) Paint shade - 631 of IS5 - 01 No. (d) Neoprene Gaskets - 01 No. (e) Degree of protection - IP55 - 01 No. (f) Control voltage - 110 VDC - 01 No. (B) Meters. (a) Digital Ammeter with ASS - 01 No. (b) Digital voltmeter with VSS - 01 No. (c) Multifunction Meter - 01 No.
(d) Energy Meter - 01 No. (C) Indication Lamps LED Type. (a) Breaker ON - Red - 01 No. (b) Breaker OFF - Green - 01 No. (c) Auto trip indication - Amber - 01 No. (d) Trip circuit healthy - Clear - 01 No. (e) Spring charged - Blue - 01 No. (f) RYB Indication - 01 No. (D) Accessories. (a) Push Button for trip circuit healthy check - 01 No. (b) Trip Neutral close switch - 01 No. (c) Local remote switch - 01 No.
(d) Panel space heater with thermostat & switch - 01 No. (e) Panel illumination lamp with switch - 01 No. (f) 2/3 pin plug with switch - 02 Nos. (g) 6 - Window Annunciator - 01 No. (h) Hooter - 01 No. (j) Semaphore Indicator - 01 No. (k) Mimic Diagram - 01 No. (l) Test terinal block - 01 No. (E) Relays. (a) Numerical communication non-drawout type relay with 50/51/50N for overcurrent and earth fault protection- 01 No. (b) Trip Circuit supervision relay - 01 No. (c) Master trip relay - 01 No. (d) Transformer Differential Relay-01 No as per suitable PS class CTs connection in 33 KV side and 11 KV side - 01 No. (e) Auxiliary relay -03 Nos for protection of following: (i) One for Buchholz Relay alarm & trip (ii) Second for Oil Temp alarm and trip (iii) Third for Winding Temp Alarm and Trip
Supplying, installation, commissioning and testing HT 11 KV 630 Amp Vacuum Circuit Breaker panel of 3 with 01 incoming and 2 outgoing indoor type, horizontal isolation type, motor operated spring charged having rupturing capacity 18.4 KA for 1 sec by connecting to the HT Panel board with the help of copper bus bar of suitable size duly enclosed in CRCA frame and panel shall be not less than 2.0 mm thickness and comprising of the following including dismantling and taking out the old unserviceable VCB -3 Nos all as specified and directed by Engr -in- Charge . The Panel shall be manufactured by approved OEM. (a) Electrical and mechanical interlock and automatic safety shutter door. (b) Power pack for control circuits/ (c) Assembly of three vaccum interrupter complete with epoxy support insulator and self alligning finger type isolating contacts, 630 Amps breaking capacity 18.4 KA (d) 230 Volts AC motorised mechanism, spring charging with independent closing /tripping push buttons and menhanical breaker "close/open" spring charged / discharged indication. (e) Mechanical operation counter (f) Electrical release coil 24 Volts DC (g) Shunt trip /close coil 24 volts DC
(h) Auxillary Switch (j) 230 Volts AC single phase 80 watt rated strip heater with toggle switch and thermostat-03 Nos (for each 03 VCBs) (k) Cable termination for 1 x 3C x 185 Sq mm XLPE cable (for incoming & outgoing). (l) Digital Ammeter flush type CT operated - 03 sets (For incoming VCB and outgoing VCBs). (m) Digital Voltmeter flush type - 03 sets (For incoming VCB and outgoing VCBs). (n) Digital Multimeter/ Energy analyser flush type - 03 sets (For incoming VCB and outgoing VCBs). (o) Numerical type 3 phase over current and earth fault relay with 50/51/50N/51N protection, - 03 Nos (For incoming VCB and outgoing VCBs) Make:- ABB/SEIMENS/SCHNEIDER/CG (p) Numerical type 3 phase over/ under voltage relay with 27/59 protection, -03 Nos (For incoming VCB and outgoing VCBs) ABB/Seimens/Schneider/ CG/Ashida/C&S/L&T (q) Master Trip Relay of make: CG or equivalent in make as mentioned in Appendix 'A' to PS - 03 Nos (For incoming VCB and outgoing VCBs) (r) LED Indication lamps for Breaker ON, Breaker OFF, Auto Trip, Trip circuit healthy, Spring Charged, RYB indication as per standard colour code.
(s) Push button for Trip Circuit healthy. (t) Cable gland of suitable size. (u) Cubical LED illumination lamp - 01 . (v) Potential transformer ratio three single phase draw out type 11 KV/rt3/110V/rt3 class 0.5, burden 100 VA (set of 3) - 1 set for Incomer VCB. (w) Battery bank, comprising of 02 Volt, 180 AH, 12 Nos battery and battery charging system made of 1.6 mm thick CRCS sheet all as specified 24 volts DC for Auxillary supply. (x) Epoxy Rasin cast CT of ratio 400-200/ 5-5 class 0.5/ 5P10, burden 15VA/15 VA for incomer VCB (set of 3) - 1 set. (y) Epoxy Rasin cast CT of ratio 300-150/ 5-5 class 0.5/ 5P10, burden 15VA/15 VA for outgoing VCBs (set of 3) - 2 sets. (z) PS class CT of suitable rating for the differential relay protection connection in the 11 KV side
Supply and fixing lightning arrester expulsion type complete with all fitting transmission class, discharge cap 65 kilo amp 33000 volt all as directed by Engr in charge
Supply, installation, testing and commissioning of air brake off load line /Bus isolator switch rotating type vertical highest system voltage 36 KV rated current 400 Amps triple pole ,each pole consist of insulating pedestals 03 Nos. on galvanized steel base as per BSS/IS including rotating blade of HDE copper and fixed contacts of same material , arcing horns of adequate section to brake magnetizing current of transformer with size of 25 mm dia GI medium grade pipe for operation from ground level and operating handle (handle shall be covered with insulating material) complete with both off and on positions complete all as specified and directed. Note : The isolator shall be operated through mechanism.
Supply, installation, testing and commissioning 33 KV current transformer oil cooled out door single phase, oil immersed and self cooled type of ratio 400-200/5-5-5-5 Amp and class suitable for metering and protection equipment installed on control panels terminal block as specified below :- (a) Normal System Voltage-33 KV (b) Highest System Voltage-36 KV (c) Rated Primary current- 630 Amp (d) Rated secondary current- 5 Amp (e) Nos of Core - 4 (f) Core01: Accuracy class 5P10, 10VA, ALF ≥10 (g) Core02: Accuracy Class 1.0, 10VA, ISF ≤ 5 (h) Core 03 Protection core accuracy class -PS,Protection knee point voltage- 300 Volt at lower ratio (j) Core 04-Spare (k) Continuous thermal current rating 120 % of rated primary current (l) Temp rise at rated contineous thermal current over ambient at site - Less than or equal to 45 degree C (m) Insulation Level- 36/70 KV.170 KVP (n) 1.2/50 Micro second impulse withstand test voltage- 170 KV (peak) (o) Short time thermal current rating for one second - 25 KA/1 Second (p) Dynamic Current Rating - 62.5 KA ( peak) (q) Porcelain Bushing type - Hollow Cylinder (r) Creepage distance of HV bushing - 900 mm (min) (s) Primary & Secondary winding material - Copper. Make: CROMPTON GREEVES/SCHNEIDER/ABB/SEIMENS/AE
Supply installation, testing and commissioning Potential Transformer (PT) oil cooled out door single phase ( Earthed type) of voltage ratio 33 KV/110 V class 3P/0.5, burden 50 VA insulation level of 70/170 KV as specified below:- (a) Normal System Voltage-33 KV (b) Highest System Voltage-36 KV (c) Rated Primary voltage- 33 KV/√3 (d) Rated secondary voltage- 110 V/√3 (e) Nos of LT winding 2 (f) Metering Core Accuracy class - 0.5 (g) Metering Core Rated Burden- 50 VA (h) Nos of Phase- Single (Earthed Type) (j) Protection core accuracy class - 3P (k) Protection core rated Burden - 50 VA (l) Rated Voltage Factor - 1.2 continuous & 1.5 for 30 Sec (m) Insulation Level- 36/70 KV.170 KVP (n) Temp rise at rated continuous thermal current over ambient at site - 45 0C (o) Porcelain Bushing type - Hollow Cylinder (p) 1.2/50 micro second impulse with stand test Vol-170 KV (Peak) (q) Creepage distance of HV bushing - 900 mm (min) (r) Primary & Secondary winding material - Copper Make: CROMPTON GREEVES/SCHNEIDER/ABB/SEIMENS/AE
Supply and install HT 33 kV Drop out fuse with double stack channel type insulator including fixing arrangements all as specified and directed by Engr-in-Charge.
Supply and install HT 33 kV Post insulator including fixing arrangements all as specified and directed by Engr-in-Charge.
Supply & laying XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, grade having cross sectional area size 185 Sq mm, 3 core complete all as specified and directed.
Supply & fix cable jointing kit for 11 KV(E) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm .
Supply and fixing light grade galvanised iron pipe conforming to IS : 1239 and ISI marked with all fittings fixed on walls/poles, crossing of road etc for protection of cable complete all as specified and directed and of following sizes :-
100 mm nominal bore
S&F danger notice plate 1.6 mm thick mild steel sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of appropriate size for 11 KV/33KV system size 25 x 20 cm all as specified and conforming to IS: 2551- 1982.
M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with copper earth plate earth electrode 60 cm x 60 cm x 3.15 mm, burried directly vertically in ground in a pit of depth not less than 2.25 metres below ground level with the top edge of earth plate at a depth not less than 1.8 m below normal ground level connected to and including copper earthing strip 20 x 3 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing strip protected by galvanised iron or steel pipe 50mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil,charcoal, salt,funnel , PCC pit and RCC cover complete all as specified & directed. Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust and common salt as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.(for transformer)
Supply & erection of main busbar on busbar gantries with ACSR conductor including laying, stringing & binding of conductors and fixing of disc fittings with disc string sets complete in all respects.
Supply & erection of T connector complete all as specified and directed.
Supply & fixing of PG Clamps heavy duty with nut & bolts suitable for panther conductor for jumpering complete in all respects.
Supply and fixing of Run through clamp for lightning arrestors, CT and PT all as specified and directed.
Supply, Laying of coarse aggregate 40mm grade as specified and directed.
Supply & fixing cross arms, bracing, supports, clamps, back plate fabricated from structureral steel section including nut, bolts, washer, welding, cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under and one finishing coat of aluminium paint etc all as specified and directed by Engr-in-Charge.
Supply, laying for fixing , passing through pipe 1100 volts grade PVC insulated copper conductor unarmoured 4 Sq mm in nominal cross section 4 core.
Supply and lay PVC insulated PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded Copper conductor of size 1.5 sq mm 2 core 1100 Volts grade complete all as specified & directed.
Supply and lay PVC insulated PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded Copper conductor of size 8 Core ,1.5 Sq mm complete all as specified & directed.
M&L for Earthing complete as per electrical plate No 3 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0mm, burried directly vertically in ground in a pit of depth not less than 2.25 metres below ground level with the top edge of earth plate at a depth not less than 1.5 m below normal ground level, connected to galvanisediron or steel strip 32X6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing wire protected by galvanised iron or steel pipe 50 mm bore medium grade and connected to continuous earth strip on pole/ test point. Watering pipe shall be 20mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil,charcoal, salt,funnel , PCC pit and RCC cover complete all as specified & directed by Engr-in-Charge. Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust and common salt as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.(For GOD, LA, CT, PT, VCB,& steel structure)
M&L for Earth continuity conductor or main earthing lead fixed to walls or to poles or any other indicated situation for loop earthing with 32 mm x 6 mm aluminium strip complete all as specified and as directed by Engr-in-Charge.
Labour for Shifting of Vaccuum circuit breaker- 01 Nos outdoor type 33 KV including disconnecting HT Cable & Bus bar for making of proposed breaker complete all as specified and directed by Engineer - in- Charge Note: The lifting machine & hydra rates should be deemed to be included in quoted rate.
Labour for Shifting of Vaccuum circuit breaker- 03 Nos indoor type 11 KV including disconnecting HT Cable & Bus bar for making of proposed breaker complete all as specified and directed by Engineer - in- Charge Note: The lifting machine & hydra rates should be deemed to be included in quoted rate.
Labour for Shifting of 2 MVA Power transformer after disconnecting all electric connections fro HT and LT side and earthing terminals from the transformer from old existing RCC/ PCC platform and necessary earth work complete all as specified and directed by Engineer - in- Charge Note: The lifting machine & hydra rates should be deemed to be included in quoted rate.
Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation of poles, stays or for taking out/laying of cables and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in soft/loose soilcomplete all as specified and directed by Engr-in-Charge.
Removing excavated materials (soil) n. exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning to underground cable with clean dry river sand complete all as specified and directed by Engr-in-Charge. Note:- Punned thickness only shall be measured & Paid complete all as specified & directed.
Supplying and laying reinforced precast concrete cable cover, Class HV, Type I, flat, size 300mmx l80mm x 40mm for protection of UG Cable all as directed.
M&L for Cement concrete for filling in foundations or making good of Road, PCC Floor, supports etc. Type B1, 1:2:4, using 20 mm graded crushed stone aggregate including necessary form work and fair finishing of exposed surface of concrete / facia finish with cement mortar complete all as directed
M/L for Cement concrete for filling in foundations or making good of Road, PCC Floor, supports etc. Type B1, 1:3:6, using 20 mm graded stone crushed aggregate including necessary form work and fair finishing of exposed surface of concrete / facia finish with cement mortar complete all as directed.
Avion Industries (BID ID -3480300)
UMESH TRADERS (BID ID -3479384)
M/S ADHIKARI CONSTRUCTION CO. (BID ID -3471280)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.06 MB
Tenderdocument0.pdf
Tender Documents • 0.64 MB
BOQ_825033.xls
BOQ • 0.39 MB
Errata0.pdf
Additional Documents • 0.18 MB
Specialcondition.pdf
Additional Documents • 0.14 MB
Particularspecifications0.pdf
Additional Documents • 0.58 MB
Makes0.pdf
Additional Documents • 0.55 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .