| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹9.5 LAdmitted-Finance | -28.21% | ₹9.5 L | L1 | Admitted-Finance |
| 2 | L2₹9.5 LAdmitted-Finance | -27.99% | ₹9.5 L | L2 | Admitted-Finance |
| 3 | L3₹9.9 LAdmitted-Finance | -25.13% | ₹9.9 L | L3 | Admitted-Finance |
| 4 | L4₹10.4 LAdmitted-Finance | -21.60% | ₹10.4 L | L4 | Admitted-Finance |
Tender Value
₹13.3 L
EMD Value
₹26,505
Closing Date
23 Mar 2026, 3:00 pmClosed
EE/ELD-12, DDA
O/o EE/ELD-12, DDA Paschim Vihar, New Delhi-110063
Augmentation/SITC of 4 Meter GI Pole along with 45-Watt LED Street Light Fittings including allied accessories Feeder Pillar, Cable and Supply and Replacement of Submersible Pump Set etc. for NHP, Boda Kuan, Ashok Vihar, Phase-2 under HD-2, HZ.
2026_DDA_902879_1
61/EE(E)/ELD-12/DDA/2025-26
Open Tender
Electrical Works
60 days
Horticulture Division
As per tender notice
11 documents required · 11 mandatory
₹0
₹26,505
Yes
7 Apr 2026
17 Mar 2026
24 Mar 2026
17 Mar 2026
23 Mar 2026
17 Mar 2026
17 Mar 2026 - 23 Mar 2026
Supplying, Fabrication and Installation of 4 mtr. high Pole made out of 65 mm dia. NB, B-class GI Pipe ISI marked duly welded with MS Base Plate of size 300 mm x 300 mm x 12 mm thick with stiffener of size 130 mm x 60 mm x 5 mm thick; top edge to be blunted with a horizontal flat>5 mm (No sharp edge), suitable Earth Stud on Base Plate, making suitable size hole in pole at a height of 2.5 meter from base plate for cable entry/exit, painting & numbering of pole, making suitable size hole in base plate for cable entry/exit into the pole and fixing the pole on the existing foundation with the existing nuts-bolts, washers etc. complete as required.
Supplying and Fixing of Single Over Hang (SOH) Bracket- for 50-80 dia. MS/GI Pole made of MS Pipe with 300 mm long top galvanized MS Tube of suitable diameter for Light Fitting accommodation, connection etc. complete as required.
Supplying and Fixing of Double Over Hang (DOH) Bracket- for 50-80 dia. MS/GI Pole made of MS Pipe with 300 mm long top galvanized MS Tube of suitable diameter for Light Fitting accommodation (Angle as per EIC/AE direction).
Providing and Laying in Position, 1:2:4 (1 Cement : 2 Coarse sand : 4 Graded Stone Aggregate) Reinforced Cement Concrete Foundation of size 450 mm x 450 mm x 1200 mm deep (900 mm below Ground Level and 300 mm above Ground Level) including excavation of earth, refilling, providing, cutting, bending and placing in position, Reinforcement of Cold Twisted Bars of 12 mm dia.- 1200 mm long (approx.)- 8 Nos. and Reinforcement Ring of Cold Twisted Bar of 8 mm dia.- 1400 mm long (approx.)- 6 Nos. (with suitable spacing) including centering & shuttering as required with Providing, Fixing and Positioning of One Set of Foundation Bolts comprising of 4 Nos., 16 mm dia. 750 mm long J-Type MS bolts (Threaded portion shall be galvanized) along with 3 Nos. GI nuts and 2 Nos. GI washers etc. per bolt and 1 No. anchor plate (3 mm thick) of suitable size and providing 63 mm (OD) DWC pipe ISI marked for cable entry & exit etc. complete as required.
Supplying, Installation, Testing & Commissioning of Street Light LED Fixture Powder Coated Pressure Die Cast Aluminum body with driver as per the requirement with Driver Efficiency>85%, Input voltage: 140-270 Volt AC, Frequency 50/60 Hz, Operating Temp range-5°C to 50°C, Internal Surge Protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency>85%, THD<10% as per IEC 61000-3-2 , PF≥0.95, IP- 66, IK-10, CRI>70, Under Voltage and Over Voltage Protection, EMI-EMC As per CISPR 15, Lenses for Beam Angle as per IESNA type I/II/III as per the width of the road and the project requirement, suitable to fit in up to 65 mm dia. pipe, life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching)<5, Maximum Power Consumption should not more than the specified rating and Fixture shall be of relevant BIS Standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC Insulated Copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System Lumen Efficacy≥120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED Fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal Management: Heat Sink of Aluminum Housing such that LED Junction Temperature shall not rise above 90°C). 45 Watt
Supply and Installation of Pole Connector Box made out of Glass Reinforced Polyester Sheet Moulding Compound Conforming to IS:13410-1992 Grade-S1 of Outside Dimensions 280 mm (H) x 170 mm (W) x 115 mm (D) (all the corners of the box should be round & not pointed ones) suitable to mount on 40/50/65/80 mm dia. GI Pole with the following Provisions/Accessories Mounting in Box etc. complete as required. a) 2 Nos. Clamps made out of 19 mm x 3 mm MS Strip of suitable Length for Mounting Box on the Pole. b) Water Tight Front Cover with 2 Nos. Stainless Steel Hinges & 1 No. Screw for Tightening. c) 4-Way, 220 V, 30 A, Dough Moulded Connector with SMC with Stainless Steel Inserts- 1 No. d) 16 A, Moulded SMC Rewireable Kit-Kat- 1 No. e) Suitable size Hole at suitable Location on Rear Wall for Cable & Wire Entry in the Connector Box. f) Earthing Bolt M6 x 20 mm. g) Neutral Link- 1 No.
Supplying of following sizes of XLPE (Cross Linked Poly Ethylene) Insulated PVC Sheathed Alumimium Conductor Armoured Power Cable of 1.1 KV grade including connection, testing etc. as required. 2C x 16 sq. mm
4C x 25 sq. mm
Providing and Fixing 6 SWG dia. GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub-main wiring/cable as required.
Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size Direct-In-Ground including Excavation and Refilling the Trench etc. as required, but Excluding Sand Cushioning and Protective Covering. Up to 35 sq. mm
Laying of one number PVC Insulated and PVC Sheathed/XLPE Power Cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required. Up to 35 sq. mm
Supplying and drawing of following sizes FRLS PVC Insulated Copper Conductor, Single Core Cable in the existing surface/recess steel/PVC conduit as required. 3C x 1.5 sq.mm
Supplying and Laying of following size DWC HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS: 14930, Part-II complete with fitting and cutting, jointing etc. direct-in-ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia. (OD-63 mm & ID-51 mm nominal)
Supplying, Fabrication and Installation of Wire Mesh Protection Frame for Existing Feeder Pillar, constructed from 10 SWG MS wire mesh with a Nominal size of 75 mm x 25 mm Rectangle. The Frame dimensions are 1.5 mtr. (Width) x 1.00 mtr. (Depth) x 2.00 mtr. (Height). It includes a Base Frame made of 40 mm x 40 mm x 6 mm MS Angle Iron, MS Strip Supports of 40 mm x 6 mm, and 0.5-meter-long leg supports of the same Angle Iron, all as per the approved drawing. Additionally, provide a suitably sized door, Supply and Fix a godown lock with locking arrangement, painting, and grouting with 1:2:4 Cement Concrete Foundation, as approved by the Engineer-in-Charge, complete as required.
Supplying and Replacement of Submersible Pump Set (Water Filled Motor)-4W Series suitable for operation on 3-Phase, 220-415 Volts, 50 Hz AC supply of following specifications: a) Head Range: 7-32 Meter or 23-105 ft b) Discharge Range: 140-330 LPM c) Capacity: 3 Hp/2.2 KW d) No. of Stages: 7 e) Outlet Pipe Size: 50 mm f) Suitable Size Cable: 10 Meter (minimum) g) Capacitor Run: 50 μF (minimum) h) Capacitor Start: 120/150 μF (minimum) The work shall also include Lifting and dismantling of existing Submersible Pump Set, Lowering and installation of new pump set in the existing bore well up to the required depth with existing GI pipes and Submersible Cable, Water-proof jointing of Submersible Cable, Replacement of necessary accessories (nuts, bolts, washers, packing, nipple, reducer, connections, etc.) and testing, commissioning etc. complete as required including rebate for dismantle Pump Set.
Supplying of PVC Sheathed, PVC Insulated Copper Conductor Flat Submersible Cable of following size including connection, testing etc. complete as required. 3C x 2.5 sq. mm
Supplying and Replacement of following size Double Flanged of "B" Class GI Pipe conforming to IS:1239 including welding and all fittings (elbows, tees, flanges, reducers/tapers), nuts, bolts, gaskets, painting and accessories etc. complete as required including rebate for dismantle material. 40 mm dia.
Earthing with GI Earth Pipe 4.5 meter long, 40 mm dia. including accessories, and Providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
Providing and Fixing 25 mm x 5 mm GI Strip on surface or in recess for connection etc. as required.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.03 MB
NIT61.pdf
Tender Documents • 1.68 MB
BOQ_948978.xls
BOQ • 0.27 MB
PWD7.pdf
Additional Documents • 2.02 MB
Download all tender documents and submit your bid