Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.8 LAdmitted-Finance 12 1 TECHSER HOUSE JALAHALLI MES RING ROAD SHARADAMBANAGAR BENGALURU BANGALORE KARNATAKA 560013 | BENGALURU URBAN | KARNATAKA | 560013 | L1 | Admitted-Finance | |
| 2 | L2₹7.9 L+₹12,975 (1.67%)Admitted-Finance 321 PATIL NAGAR BAWDHAN ROAD BAVDHAN BUDRUK PUNE MAHARASHTRA 411021 | PUNE | MAHARASHTRA | 411021 | L2 | Admitted-Finance | |
| 3 | L3₹17.0 L+₹9.2 L (118.2%)Admitted-Finance 8 13 ERANDWANE SUMITRA APARTMENTS OPP INGALE HOSPITAL PUNE MAHARASHTRA INDIA 411004 PUNE CITY MAHARASHTRA 411004 | PUNE | MAHARASHTRA | 411004 | L3 | Admitted-Finance | |
| 4 | L4₹19.8 L+₹12.0 L (154.0%)Admitted-Finance GF 3 F 12 KSSIDC BUILDING 5TH CROSS 1ST STAGE PEENYA INDUSTRIAL ESTATE BANGALORE | BENGALURU URBAN | KARNATAKA | 560058 | L4 | Admitted-Finance | |
| 5 | Not Admitted-Fee/PreQual/Technical 50 51 NARAYANASWAMY NAGAR CHERLAPALLY CHERLAPALLY HYDERABAD HYDERABAD TELANGANA 500051 | MEDCHAL MALKAJGIRI | TELANGANA | 500051 | - | Not Admitted-Fee/PreQual/Technical Others-Hard Copy not submitted |
| Sl No | Description | Qty | Unit | TECHSER POWER SOLUTIONS PVT LTD L1 | Prostarm Info Systems limited L2 | Power One Micro Systems (P) Ltd L4 | Power Technics Infosolutions Pvt Ltd L3 |
|---|---|---|---|---|---|---|---|
| 1.00Online UPS- Input supply: Three Phase, Output supply: Three Phase Supplying, installation, Testing & Commissioning of of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 deg C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swappable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of moduels requird for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch alongwith provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant International standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accoseries are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED ) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current.d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location etc. | |||||||
| 2.00 | 60KVA (Each Power module shall be < 10 KVA) | 1 | set | 3,72,025 ₹3,72,025 Lowest | 4,17,500 ₹4,17,500 | 12,13,632 ₹12,13,632 | 10,25,850 ₹10,25,850 |
| 3.00 | Rack and interlinks | 1 | set | - | 20,000 ₹20,000 Lowest | 60,000 ₹60,000 | 1,25,000 ₹1,25,000 |
| 4.00 | Batteries for 30 Min Back up | 1 | set | 3,36,000 ₹3,36,000 | 2,80,000 ₹2,80,000 Lowest | 6,15,200 ₹6,15,200 | 4,52,000 ₹4,52,000 |
| 5.00CABLING Power Cabling Supply and laying heavy duty 1100V grade XLPE outer sheathed & Fire Retarded Low Smoke (FRLS) cables indoor with Copper conductors as specified complete with: a) Cable clamps / trays on walls, floors, ceiling as required. b) Earthing the glands armouring etc. | |||||||
| 6.00 | SITC of Incomer cable from main input MCCB distribution board to UPS Incomer 1CX35 Sqmm Copper cable multi strand type including glanding and lugging ( Lug Qty 8 nos) . | 35 | Mtr | 1,000 ₹35,000 Lowest | 1,050 ₹36,750 | 1,250 ₹43,750 | 1,350 ₹47,250 |
| 7.00 | SITC of Outgoing cable from UPS output to main output MCCB distribution board 1CX35 Sqmm Copper cable multi strand type including glanding and lugging ( Lug Qty 08 Nos) ( Neutral cable lug Qty 02 nos ) | 35 | Mtr | 1,000 ₹35,000 Lowest | 1,050 ₹36,750 | 1,250 ₹43,750 | 1,350 ₹47,250 |
Tender Value
₹8.9 L
EMD Value
₹17,827
Closing Date
13 Jul 2026, 3:00 pmClosed
Director TMC
Engineering services, Ground Floor, Pushp Building (Old St. Jude Building), ACTREC 410210
SITC of 60 KVA UPS including batteries and accessories for New Animal Facility building at ACTREC
2026_TMC_912275_1
VK/ET-24/60 KVA UPS/2026
Open Tender
Electrical Works
Item Rate
120 days
ACTREC, Kharghar
As per tender terms and conditions
5 documents required · 5 mandatory
₹0
₹17,827
ACTREC, Kharghar
24 Sept 2026
9 Jun 2026
14 Jul 2026
9 Jun 2026
13 Jul 2026
9 Jun 2026
9 Jun 2026 - 15 Jun 2026
16 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Online UPS- Input supply: Three Phase, Output supply: Three Phase
Supplying, installation, Testing & Commissioning of of following capacity at
full load (Unity Power Factor) at operating temperature 0 to 40 deg C,
Relative humidity 0 to 95%, Online double conversion true sine wave
Uninterrupted hot swappable (allow for the replacement or addition of
battery modules without shutting down the entire system) modular Power
Supply (UPS) system with N+1 modules (N denotes total number of moduels
requird for rated capacity). The UPS shall include a Rectifier, inverter,
battery bank suitable for 30 minutes back up (Battery VAH capacity shall not
be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full
load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass
switch alongwith provision for manual bypass, suitable isolation transformer
for additional protection against neutral faults etc. UPS shall have inbuilt
phase sequence correction. The UPS systems offered are to be of the latest
technology with Digital Control Microprocessor based for reliable operation
using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier &
inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design,
manufacturing and inspection process should confirm to the relevant International
standards such as IEC/EN/VDE. The operating efficiency of the
UPS systems shall be >96% while operating on battery mode and delivering
quality power to the 100% non-linear loads. Current total harmonic
effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC (
inductor (L) and a capacitor (C)) filters shall be included in UPS cost),
extreme power factor kit to be included to limit the input power factor (PF) to
0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be
kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7
leading power factor loads. UPS shall be suitable for incoming supply AC :
3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt,
50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output.
Non condensing, noise level less than 60db at 1 meter distance, protections:
Input Under voltage over voltage, abnormal out voltage, battery over
charging, output over current, short circuit protection, battery deep
discharge protection, 10KV surge. UPS must comply with low voltage
electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part
I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type
UPS. Communication RS232/RS485/SNMP port open protocol for BMS
integration, all hardware & software for iOT Communication as per approved
by Engineering in charge. Required battery racks and interconnecting
copper conductor cables of suitable size and connectors and all required
accoseries are inclusive of the cost). This system must provide a means for
logging and alarming of all monitored points plus email notification. Forced
air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS
should be able to handle at least 80% of the load, Noise Level 65 DB at 1
meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS:
16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or
more LC Display / LED ) to display : a) Input: Voltage, current, Frequency. b)
Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current.d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage.
f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On
LCD/LED): UPS should capture and display up to 3000 events like: Over
temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit /
Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data:
No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains
Mode of Operation /Battery Mode of Operation / Bypass feeding the load /
UPS Fault /Battery charging and discharging, overload, battery voltage and
battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS
Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under
Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over
Temperature. The UPS should have QR code which should contain
drawing, test report OEM manual,Geo- Tag of manufacturing location etc. | - | - | - | - |
| 2 | 60KVA (Each Power module shall be < 10 KVA) | 1 | set | - | - |
| 3 | Rack and interlinks | 1 | set | - | - |
| 4 | Batteries for 30 Min Back up | 1 | set | - | - |
| 5 | CABLING
Power Cabling
Supply and laying heavy duty 1100V grade XLPE outer sheathed & Fire Retarded Low Smoke (FRLS) cables indoor with Copper conductors as specified complete with:
a) Cable clamps / trays on walls, floors, ceiling as required.
b) Earthing the glands armouring etc. | - | - | - | - |
| 6 | SITC of Incomer cable from main input MCCB distribution board to UPS Incomer 1CX35 Sqmm Copper cable multi strand type including glanding and lugging ( Lug Qty 8 nos) . | 35 | Mtr | - | - |
| 7 | SITC of Outgoing cable from UPS output to main output MCCB distribution board 1CX35 Sqmm Copper cable multi strand type including glanding and lugging ( Lug Qty 08 Nos) ( Neutral cable lug Qty 02 nos ) | 35 | Mtr | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.87 MB
TD.pdf
Tender Documents • 1.72 MB
BOQ_958756.xls
BOQ • 0.29 MB
AnnexureForm.xls
Additional Documents • 0.12 MB
PREBID.pdf
PDF • 0.68 MB
specifications.pdf
PDF • 0.73 MB
Corrigendum.pdf
PDF • 0.42 MB
Corrigendum.pdf
PDF • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .