Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹16.9 LAccepted-AOC 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | 1 | Accepted-AOC L1 | |
| 2 | 2₹18.6 L+₹1.7 L (9.88%)Rejected-AOC | 2 | Rejected-AOC L2 | |
| 3 | 3₹21.4 L+₹4.4 L (26.2%)Rejected-AOC 01 KATYANI CONSTRUCTION COMPANY H NO 1 SHOP NO 1 RATAN LAL NAGAR KANPUR NAGAR UTTAR PRADESH 208022 | KANPUR NAGAR | UTTAR PRADESH | 208022 | 3 | Rejected-AOC L3 | |
| 4 | 4₹25.8 L+₹8.9 L (52.6%)Rejected-AOC | 4 | Rejected-AOC L4 |
Tender Value
Refer Docs
EMD Value
₹26,000
Closing Date
1 May 2021, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Electricity Transmission Circle-II, U.P. Power Transmission Corporation Ltd. 57- George Town, Prayagraj
04/ETC-II(P)/ 2021-2022
2021_UPTCL_584216_1
04/ETC-II(P)/ 2021-2022
Open Tender
Electrical Works
Item Rate
90 days
Koraon
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
EE,ETD-NAINI,PRAYAGRAJ
₹26,000
18 Sept 2021
24 Apr 2021
3 May 2021
24 Apr 2021
1 May 2021
24 Apr 2021
120 days
Amount
Part "A" Supply
Supply of bolted type tension fitting along with turn buckle and all accessories for single panther conductor for 40 MVA T/F Bay as per sample.
Supply of bolted type tension fitting without turn buckle and all accessories for single panther conductor for 40 MVA T/F Bay as per sample.
Supply of bolted type tension fitting along with turn buckle and all accessories for twin Moose conductor for 132/33 KV Main Bus, 20 MVA T/F-Ist & IInd and 40 MVA T/F Bay as per sample. .
Supply of bolted type tension fitting without turn buckle and all accessories for twin Moose conductor for 132/33 KV Main Bus, 20 MVA T/F-Ist & IInd and 40 MVA T/F Bay as per sample.
Supply of post insulator clamp duly made of LM-6 Alluminium Alloy suitable for 132 KV Post insulator and single panther conductor complete with GI nuts, bolts, spring & washer as per sample.
Supply of PG clamp duly made of LM-6 Allu. Alloy suitable for ACSR Moose to Panther conductor complete with 04 no. 16x75 mm size GI bolts, nuts, spring & plane washer as per sample.
Supply of PG clamp duly made of LM-6 Allu. Alloy suitable for ACSR Moose to Moose conductor complete with 04 no. 16x75 mm size GI bolts, nuts, spring & plane washer as per sample.
Supply of 132 KV Isolator bimetalic terminal clamp made of LM-6 Alluminum Alloy suitable for twin panther conductor complete with GI nut & bolts and washers.
Supply of 132 KV Tendam Isolator bimetalic terminal clamp made of LM-6 Alluminum Alloy suitable for twin panther conductor complete with GI nut&bolts and washers.
Supply of 02 no. U Bolted Type Single suspenstion fitting assembly suitable for twin ACSR Moose conductors and 33 KV Suspenstion Disc insulator string (comprising of 03 no. 70 KN Disc insulator) complete with hardware fitting, socket eye, Ball Hook, Yoke Plate, J-Hook etc. as per technical specification as per sample.
Supply of spacer suitable for 132/33 KV Bus Bar twin ACSR Moose conductor with 250 mm spacing and duly made of LM-6 alluminum alloy, complete with 12 mm dia HDG Bolts, Nuts, Spring & Plane washer as per technical specification as per sample.
Supply of spacer suitable for 33 KV twin ACSR Moose conductor with 90 mm spacing and duly made of LM-6 alluminum alloy, complete with 12 mm dia HDG Bolts, Nuts, Spring & Plane washer as per technical specification as per sample.
Supply of 33 KV CT bimetalic terminal connecter duly made of LM-6 alluminium alloy. along with bimetalic sleeve/plate suitable for twin ACSR Moose conductor complete with 04 no. 12 mm size GI Bolts, Nuts & Washers as per technical specification as per sample.
Supply of 33 KV CB bimetalic terminal connecter duly made of LM-6 alluminium alloy. along with bimetalic sleeve/plate suitable for twin ACSR Moose conductor complete with 04 no. 12 mm size GI Bolts, Nuts & Washers as per technical specification as per sample.
Supply of 33 KV Isolator bimetalic terminal connecter duly made of LM-6 alluminium alloy. along with bimetalic sleeve/plate suitable for twin ACSR Moose conductor complete with 04 no. 12 mm size GI Bolts, Nuts & Washers as per technical specification as per sample.
Supply of 33 KV Post Insulator clamp made of LM-6 alluminium alloy. along with bimetalic sleeve/plate suitable for twin ACSR Moose conductor complete with 04 no. 12 mm size GI Bolts, Nuts & Washers as per technical specification as per sample.
Supply of U Bolt 20 mm dia with double nuts, bolts and washer.
Part "B" Work - Construction of 01 nos. 132 & 33 KV Bay for Installation of additional 40MVA 132/33KV T/F at 132 KV S/S Koraon. The work includes the following :-
Shorting, shifting & loading of galvanized material on private vehicle at Electy. Fabrication Unit Naini, Prayagraj.
Safely carriage of substation structure from Electy. Fabrication Unit Naini to 132 KV S/S Koraon on private vehicle (per truck basis).
Unloading, shorting, shifting & stacking in proper order as per member wise of above material at 132 KV S/S Koraon, Prayagraj.
Erection of following structure & equipments including their shifting from storage place at the sub-station to erection site :-
Lattice type auxilliary structure
132 KV CT Junction box
132 KV Tandem Isolator with Post Insulator
132 KV Bus Isolator with Post Insulator
132/33 KV Transformer Control & Relay Panel
33 KV Isolator
33 KV CT Junction box
Stringing of 132 KV Jack bus bar of single ACSR Panther conductor including hoisting of Disc Insulator, Tension String with Tension Fitting alongwith Shifting of the Conductors etc. from stores at the Sub Station to Switchyard. (1 Job per Phase per Section)
Opening of existing jumper of 132 KV Main Bus of 132 KV Bus coupler, 20 MVA T/F-I&II, 132 KV Solar Bay, 132 KV Salaiyakhurd Bay & 132 KV Rewa Road Bay including shifting of jumper from work site to store site.
De-stringing & dismanting of existing of 132 KV Main Bus Bar of single ACSR Moose conductor including de-hoisting of disc insulator, tension string with tension fitting from gantry alongwith shifting the old material etc. from switchyard to store at the Substation. (1 Job per Phase per Section)
Laying & stringing of 132 KV Main Bus Bar of twin ACSR Moose Conductors including hoisting of Disc Insulator, Tension String with Tension Fitting alongwith Shifting of the materials etc. from Stores to Switchyard. (1 Job per Phase per Section)
Fixing of 250mm size spacers between above laid 132 KV Main Bus Bar conductors of twin ACSR Moose conductors.
Jumpering of Equipments of 132 KV Bus coupler, 20 MVA T/F-I&II, 132 KV Solar Bay, 132 KV Salaiyakhurd Bay & 132 KV Rewa Road Bay with the help of ACSR Panther conductor with Main Bus by suitable clamps/connectors including, cutting, bending, shaping etc. of the Conductor as per Site Requirement.
Opening of existing jumper of ACSR Moose/Panther conductor of 33 KV Feeder's Bays, 33 KV Bus Transfer, 33 KV Bus coupler and 20 MVA T/F-I & II including shifting of jumper from work site to store site.
De-stringing & dismanting of existing of 33 KV Main bus and 20 MVA T/F-I & II Bay of single ACSR Moose/Panther conductor including de-hoisting of disc insulator tension string with tension fitting from gantry alongwith shifting the old conductor tension fitting etc. from switchyard to store at the Substation (01 Job per Phase per Section)
Laying & stringing of 33 KV Main Bus, 20 MVA T/F- I & II and 40 MVA T/F of twin ACSR Moose Conductors including hoisting of Disc Insulator Tension String with Tension Fitting alongwith Shifting of the Conductors, Tension Fittings, Spacers etc. from Stores at the Sub Station to Switchyard. (1 Job per Phase per Section)
Fixing of 250mm size spacers between above laid 33 KV Main Bus Bar & 20 MVA T/F-I&II and 40 MVA T/F Bay of twin ACSR Moose conductors.
Jumpering with 33 KV Main Bus of twin ACSR Moose conductor with 20 MVA T/F-I & II and 40 MVA T/F & section isolator with the help of twin ACSR Moose/Panther conductor and suitable clamps/connectors including, cutting, bending, shaping etc. of the Conductor as per Site Requirement.
Fixing of 90 mm size spacer on jumpers of 20 MVA T/F-I & II and 40 MVA T/F.
Earthing by Cutting, Straightening & Laying 500 mm below Inside Ground & above Ground of Following sizes M.S. Flat to Provided by the Department for Diagonal / Double Earthing of the Main & Aux. Structures, Equipments and Cable Trenches including Welding with Main Earth Mat and with the Object to be Earthed including Excavation of Trenches & its Back Filling etc. as per Details below :-
Earthing of LA with 75x10 mm of size MS Flat.
Earthing of Main & auxiliary structure and equipments (CBs, Isolators, CTs, PTs, C&R Panel, DPP, Junction Boxes etc. with 50x6 mm size M.S. Flat.
Earthing of cable trench with 25mm x 6mm/ 25x5mm size M.S. Flat.
Making of Shielding Mesh for 132 KV LAs in new 40 MVA T/F by Fabrication of 06 No. 3 Meter Long Electrodes with 36 mm dia. M.S. Round Bar having 150 mm long Conical Shape and then its Piercing Vertically in the Ground with Top 500 mm below Ground Level, Jointing the Electrodes with 75 × 10 mm size M.S. Flat by Welding for making of Mesh, Connecting the Shielding Mesh with Main Earth Mat at 2 Places and finally, Painting of the Shielding Mesh / Earthing Strips with Anti-Corrosive Paint, with due Digging of Earth / Trench & its Back Filling. (1 Job per Bay)
Making of delta earthing of 33 KV LA by fabrication of 4 No. 3 Mts. MS round 40 mm dia electrodes its placing inside the ground and connecting all 4 Nos. eletrodes with 75x10 mm M.S. flat laying around as per drawing. Painting and jointing with 75x10 mm M.S. flat laying around as per drawing, paint the joints with black japan paint of good quality after proper cleaning of joint by wire brush.
Painting of M.S. Earthing Strips by Rubbing with Sand Paper & Wire Brush, then Painting with 1 Coat of Red Oxide Primer & 2 Coats (The 2nd Coat of Paint shall be Applied at the Gap of 48 hrs. when 1st Coat of Paint is Done & Checked by concerned J.E. / S.D.O.) of 1st Quality Synthetic Enamel Paint of Asian / Berger / Nerolac make in Bus Green Colour as per Details below :-
75 × 10 mm size M.S. Earthing Strip in Bus Green Colour
50 × 6 mm size M.S. Earthing Strip in Bus Green Colour
25 × 6 mm / 25 × 5 mm size M.S. Earthing Strip in Bus Green Colour
Laying of Following sizes Control Cables in Cable Trenches from Control & Relay Panels in Control Room to various Equipments, Junctions Boxes etc. in Switchyard as per Cable Schedule including Shifting of Cables in Drums from Storage Place at the Sub Station to Erection Site and Shifting Back the Balance Cables to Stores at the Sub Station :-
Interconnection & Termination of various sizes above Laid Control Cables with the transformer control & relay panel to various Equipments & Equipments to Equipments in 40 MVA T/F (132 & 33 KV Bay) Bays including Extending D.C. Supply from DCDB and A.C. Supply from ACDB to C&R Panel and various Equipments including Making necessary Holes in Gland Plates, wherever Required alongwith Providing & Fixing of Appropriate sizes Cable Glands, Providing of Ferrules for each Core of the Cables, then Termination with Crimping type Copper Lugs alongwith Preparation of Inter-Connection Drawing and Commissioning of the Bay in Co-ordination with T&C Wing including Providing of 2 Sets of Hard Copies of as Executed Inter-Connection Drawing. (1 Job per Bay) :-
Cable Termination in new additional 40 MVA T/F Control and relay panel.
Providing & fixing of name plate made of 02 mm thick aluminium Sheets with covering of 3HP retro reflective sheeting of size 300mmX150mm plate to be fixed with the help of nuts & bolts of already installed equipment's structure as per sample.
Providing & fixing of phase plate equipment (R,Y,B phase of 02 mm thick aluminium sheets of size 5" dia covering of 3M HIP/MDG retro reflected sheet in single piece with all mounting with GI nut and bolts after opening of old rusted and damaged phase plate (01 set = R,Y,B Phase).
Providing of 3 Phase L.T. A.C. Supply Cubicals of size 1200×600×500 mm with Hinged Door and Proper Locking Arrangement duly made of 16 SWG M.S. Sheet and Painted with Grey Colour Synthetic Enamel Paint. The L.T. A.C. Supply Cubical should be Fitted with 3 No. 100 Amp. Aluminum Bus Bar (3 Phase + Neutral), 5 No. 32 Amp. TPN MCB, 6 No. 40 Amp. DP MCB, 40 No. Link type Terminal Bock, Cable Glands etc. with Internal Wiring and then Installation of each L.T. A.C. Cubical on M.S. Angle Frame Structure after due Fabrication with the help of Scrap M.S. Angles to be Provided by the Department Free of Cost and Grouting of Legs of the M.S. Angle Frame Structure in the Ground with C.C. Mixture and Painting of the M.S. Angle Frame Structure with Synthetic Enamel Paint. (1 Job per L.T. A.C. Cubical)
Excavation of earth size 300x500 mm for making trench for laying of power cable between ACDB to AC Cubical box including making of holes in main trenches walls for passing of cable as per site situation and backfilling after completion of work.
Laying of 3.5 core alluminium power cable between ACDB to AC Cubical box of in already excavated trench including associated work to complete the job.
Termination of above power cable by providing proper size of Al. Dowell/Jenison makes lugs, its crimping and connecting with both side equipment including cost of lugs and all other associated works to completed the job.
Earthing of L.T. A.C. Supply Cubical with Providing & Fixing of 600 × 800 × 8 mm size G.I. Plate with its Top At Least 3 Meter below the Ground Level with 20 mm dia. G.I. Pipe & Funnel for Watering, 1 No. 8 SWG G.I. Wire Earthing Lead etc. with Alternate Layer of Charcoal / Coke and Salt At Least 150 mm Thick Around it.
HARE KRISHNA ENERGY PROJECTS
Katyani Construction Co.
M/s S.S. Refregeration
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .