Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹31.7 LAccepted-AOC | 1st | Accepted-AOC The M/s Agrawal Builders is being lowest bidder and found reasonable. | |
| 2 | 2nd₹36.0 L+₹3.7 L (11.5%)Rejected-Finance | 2nd | Rejected-Finance L2 | |
| 3 | 3rd₹36.0 L+₹3.7 L (11.5%)Rejected-Finance | 3rd | Rejected-Finance L3 | |
| 4 | 4th₹39.5 L+₹7.2 L (22.2%)Rejected-Finance | 4th | Rejected-Finance L4 | |
| 5 | 5th₹39.5 L+₹7.2 L (22.5%)Rejected-Finance | 5th | Rejected-Finance L3 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
6 Nov 2024, 6:00 pmClosed
GE AWC MHOW
GE AWC MHOW
SPL REPAIRS TO CONVERSION OF LT OVERHEAD LINES TO UNDER GROUND CABLES AT AWC KLP AREA AND MES COLONY UNDER GE (AWC) MHOW
2024_MES_678365_1
8776 GE(AWC) /MHOW / OF 2024-25
Open Tender
Civil Works
Item Rate
180 days
GE AWC MHOW
Please refer tender documents
7 documents required · 7 mandatory
₹500
Yes
GE AWC MHOW
₹80,000
Yes
13 Jan 2025
7 Oct 2024
7 Nov 2024
8 Oct 2024
6 Nov 2024
23 Oct 2024
Amount
Supplying, laying, fixing, jointing and testing LT under ground XLPE insulated, galvanised teel strip or wire armoured heavy duty electric cable with alumimium conductor, 1100 volts grade, cross sectional area 10 Sqmm x 4 Core, IS 7098 marked, with electric connection lugs, laid in trenches/under floor or fixed naked with walls / on poles/ in ducts / in GI pipes etc. and including taking down complete all as specified and directed. Note - Excavation, earth work, sand cushioning, PCC cover and GI pipe shall be measured and paid separately.
Description all as per Sl. Item No. 01 above but 16 sqmm x 4 Core
Description all as per Sl. Item No. 01 above but 120 sqmm x 3.5 Core
Dismantling of old unserviceable ACSR or AAC conductors, all as specified and directed
Dismantling of old unserviceable GI earth wire or service feeder or distribution span all as specified and directed
Dismantling of old unserviceable insulators of any type and any size all as specified and directed
Supply and laying GI pipe 'light grade' 40 mm in trenches, under floors, roads, along poles for protection of cables with all necessary fittings and sealing ends complete all as specified and directed.
Description all as per Sl. Item No. 05 above but GI pipe 'light grade' 80 mm
Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for laying of cables, pipes etc. and getting out all excavated material in any type of soil complete all as specified and directed.
Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed.
Removing of excavated surplus soil to a distance not exc 50 m and depositing where directed at a level not exc. 1.5 m above the starting point complete all as specified and directed.
Material and labour for locally available river sand cushioning for under ground cable in trenches 8 cm before laying and 15 cm after laying of cable and punned thickness of sand shall be measured and paid for 18 cm only after punned/consolidated thickness complete all as specified and directed.
Supply and laying unreinforced PCC Cable protection cover, class LV, type-1 flat with size 250 x 150 x 40 mm laid flat width wise complete all as specified and directed.
M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth strip of size 25 x 4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate no. 3 of SSR Part - 1, connected to earthing test point and complete all as specified and directed. Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) earth chamber, RCC 1:1.5:3, type A-1 cover slab, 40 mm thick reinforced with 6 mm dia TMT bar @ 150 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, 20 mm bore medium grade GI watering pipe, 15 mm bore GI light grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc.
Supply , installation , testing and commissioning .LT PANEL board outdoor type (CPRI Approved) of sutiable size Kiosk type factory assembled fabricated and of suitable size angle iron, channel and MS sheet 3 mm to 3.15 mm thick (inner compartment is 2.0mm thick) double door type , front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and netural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables cubical type duly powder coated over a coat of primer , grouting of panel 60 cm above the ground level by provisind 90 cm long angle iron frame bottom of panel 40x40x5 mm thick , welded on all four corners , embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate upto 30 cm and,grouting the panel board on and including suitable size foundation structure with the following components. (a) MCCB 630 amps 4 pole, 50 KA 415 volts , Ics =100 % Icu Adjustable short circuit setting type (incoming) – 01Nos (b) MCCB 250 Amps 4 pole , 36 KA 415 Volts , Ics =100 % Icu Adjustable short circuit setting type (out going ) - 02 Nos (c) MCCB 63 Amps 4 pole , 25 KA 415 Volts , Ics =100 % Icu Adjustable short circuit setting type (out going ) - 07 Nos (d) MCB TPN 40 Amps 3phase and neutral -03 Nos. (e) Aluminium Bus bar of capacity 800 Amps 3 phase and neutral -1 set. (f) Digital type voltmeer 0-500 volts. (g) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 Nos (h) Indicating lamps R,Y& B -01 set
Supply , installation , testing and commissioning .LT PANEL board outdoor type (CPRI Approved) of sutiable size Kiosk type factory assembled fabricated and of suitable size angle iron, channel and MS sheet 3 mm thick (inner compartment is 2.0mm thick) double door type , front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and netural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables cubical type duly powder coated over a coat of primer , grouting of panel 60 cm above the ground level by provisind 90 cm long angle iron frame bottom of panel 40x40x5 mm thick , welded on all four corners , embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate upto 30 cm and,grouting the panel board on and including suitable size foundation structure with the following components. (a) MCCB 200 amps 4 pole, 36KA 415 volts , Ics =100 % Icu Adjustable short circuit setting type (incoming) – 01Nos (b) MCCB 100 Amps 4 pole , 25 KA 415 Volts , Ics =100 % Icu Adjustable short circuit setting type (out going ) - 01 Nos (c) MCCB 63 Amps 4 pole , 25 KA 415 Volts , Ics =100 % Icu Adjustable short circuit setting type (out going ) - 03 Nos (d) MCB TPN 40 Amps 3phase and neutral -03 Nos. (e) Aluminium Bus bar of capacity 400 Amps 3 phase and neutral -1 set. (f) Digital type voltmeer 0-500 volts. (g) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 Nos (h) Indicating lamps R,Y& B -01 set
S&F in replacement of PVC junction box IP - 66 Thermoplastic PC- GFS Polycarbonate weatherproof Junction Box with Degree of protection against mechanical load IK09 (10 Joule) with plain walls for cable entries to be drilled individually. The plain side walls on the four sides can be drilled and customized for cable entries from any direction. The Junction box Internally embedded polyurethane material Gaskit. Lid fasteners shall not have screws but shall be with quarter turn locking knobs . The junction box shall fulfill the following standards Weatherproof : UV resistant due to solar radiation, Rainwater proof, temperature resistant. Salt water proof & shall be suitable for off-shore applications. IEC 60670-22 : Particular requirements for connecting boxes and enclosures. IEC 60695 – 2 – 11 : Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 960 deg C. IEC 60529 : IP 66 degree of protection. colour: black, RAL 9011 Degree of protection against mechanical load IK09 (10 Joule) Technical details Cat.no.- KF 2500 with MCB 6A SP ,4nos 16sq.mm terminal Block Dimension in mm- 205 x 255 x 112 mm
M & L in replacement for Rigid non-metallic PVC FRLS conduit heavy duty of size 20mm external dia , exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc to be fixed along the pole and including taking down complete all as specified and directed .
Supplying, laying, fixing, jointing and testing LT services cable heavy duty electric cable with copper conductor, 1100 volts grade, cross sectional area 1.5 sqmm 3 core, ISI marked, with electric connection lugs, fixed naked with walls / on poles/ on high mast / in GI /PVC pipes etc. and including taking down complete all as specified and directed.
Design,Supply, installation, testing and commissioning of bus bar chember box of size 0.5Mx0.8Mx0.60M depth,(HxBxD) outdoor type factory fabricated made out of CRCA sheet of 3.15 mm thick ,fully enclosed and angle iron frame of size 40 x 40 x 6mm thick and T section with front and rear openable double door shutter, dust and vermin proof and rear opening complete with locking arrangement, having a system of bus bars of aluminium of suitable size of 200 Amps duly insulated and mounted on Epoxy/porcelain insulators in totally enclosed chamber with 100 Amp 25 KA MCCB three phase and neutral arrangement 415 volts Ics =100 % Icu , AC, system. provn of suitable cable glands, duly powder coated and provn of digital time switch (proghrammable every 1 min with backup of 06 yrs ,28 memory locations,current capacity 16 Amp ,weekly program ,with changeover (1CO) total 28 programs complete all as specified and directed.
Design,Supply, installation, testing and commissioning of bus bar chember box of size 0.5Mx0.8Mx0.60M depth,(HxBxD) outdoor type factory fabricated made out of CRCA sheet of 3.15 mm thick ,fully enclosed and angle iron frame of size 40 x 40 x 6mm thick and T section with front and rear openable double door shutter, dust and vermin proof and rear opening complete with locking arrangement, having a system of bus bars of aluminium of suitable size of 400 Amps duly insulated and mounted on Epoxy/porcelain insulators in totally enclosed chamber with 200 Amp 36 KA MCCB three phase and neutral arrangement 415 volts Ics =100 % Icu , AC, system. provn of suitable cable glands, duly powder coated and provn of digital time switch (proghrammable every 1 min with backup of 06 yrs ,28 memory locations,current capacity 16 Amp ,weekly program ,with changeover (1CO) total 28 programs complete all as specified and directed.
MODI CORPORATION (BID ID -3148855)
Vinayak Trading House (BID ID -3158493)
Auto Traders (BID ID -3158585)
M/S UnitedConstruction (BID ID -3158388)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .