Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.0 CrAccepted-AOC | ₹3.0 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹3.0 Cr+₹1.5 L (0.51%)Rejected-Finance KARNATAKA | RAICHUR | KARNATAKA | 584123 | ₹3.0 Cr+₹1.5 L (0.51%) | L2 | Rejected-Finance Being L2 |
| 3 | L3₹3.0 Cr+₹1.6 L (0.54%)Rejected-Finance | ₹3.0 Cr+₹1.6 L (0.54%) | L3 | Rejected-Finance Being L3 |
| 4 | L4₹3.3 Cr+₹29.1 L (9.80%)Rejected-Finance | ₹3.3 Cr+₹29.1 L (9.80%) | L4 | Rejected-Finance Being L4 |
Tender Value
₹2.8 Cr
EMD Value
₹3.5 L
Closing Date
15 Jan 2019, 6:00 pmClosed
CE AF UDHAMPUR ZONE
CE AF UDHAMPUR ZONE
PROVN OF STATION FIRE SECTION AT AF STN LEH
2017_MES_113035_1
CEAFU-32/2016-2017
Open Tender
Civil Works
Lump-sum
610 days
LEH
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,000
GE (P) AF LEH
₹3.5 L
Yes
29 Apr 2020
29 Sept 2018
17 Jan 2019
29 Sept 2018
15 Jan 2019
4 Dec 2018
5 Oct 2018 - 8 Oct 2018
Amount
Total amount of Sch 'A' part-I (Sec-I)( Bldg Work)
Sch 'A' Part-I (Sec II) ( Bldg Work) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Design, Supply, fabrication & erection of station fire section (Integrated temp controlled complex), fire section block Marked 'A' in Pre Engineered building block, including RCC foundation & specifications as listed complete all as specified and shown on detailed drawings.
Total amount of Sch 'A' part-II ( Plumbing Work)
Total amount of Sch 'A' part-III )(Section I) (Internal water supply)
Total amount of Sch 'A' part-IV Section-I (Internal Electrification)
Sch 'A' Part-IV Section-II (Internal Electrification) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
LED integrated batten T5 of 18/20Watt, 4 FT, white, indoor decorative PVC extruded T5 LED batten integrated type.
Lamp holder insulated body with back plate ISI marked for batten fittings including LED 9 Watt complete all as specified.
Surface mounted LED luminare for mirror lighting 6 watt Complete with lamp including connecting electricaly to ceiling rose using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 0.50 sqmm all as required.
LED Street light of 20 Watt , IP66 powder coated pressure die cast aluminium compact high power LED street light with heat resistant toughened glass including street light bracket made out of 40mm dia GI Pipe light grade 1.2 mtr long ,bent to shape, with all necessary fittings i.e nuts,bolts, clamps made out of flat iron 50X6mm -02 nos.and necessary electric connection complete all as specified and as directed by Engr-in-Charge.
Bulkhead luminare LED type surface mounted comprising of high brightness LEDs of 10Watt all as specified and as directed at site.
Ceiling fan 5 star rated (as per BEE recommendation) 1200mm sweep single phase 230 volts 50 Hz AC supply totally enclosed heavy duty motor with die cast alumn rotor complete with down rod, Regulator including hanging of fan, connecting electrically using 3 core 0.75sq mm PVC insulated flexible copper conductor cable over all sheathed all as specified and directed.
Heavy duty exhaust fan (as per BEE recommendation) 380mm sweep single phase 230 volts 50 Hz AC supply totally enclosed heavy duty motor with die cast alumn rotor mounted on two ball bearings complete louvers including cutting chases for fixing fan, connecting electrically using 3 core 0.75sq mm PVC insulated flexible copper conductor cable over all sheathed all as all as specified and directed.
Heavy duty exhaust fan (as per BEE recommendation) 230mm sweep single phase 230 volts 50 Hz AC supply totally enclosed heavy duty motor plastic body complete with louvers including cutting chases for fixing fan, connecting electrically using 3 core 0.75sq mm PVC insulated flexible copper conductor cable over all sheathed all as all as specified and directed.
MCB single pole & neutral 240 volts 6 to 32 amps,with rupturing capacity 10 KA, ISI Marked.
MCB single pole 240 volts 6 - 32 amps, with rupturing capacity 10 KA, ISI Marked.
MCB TP 415 volts 63 amps, with rupturing capacity 20 KA, ISI Marked.
Supply and fix LED spot light/focus light 16/18 watt swivel type to fix on surface and connecting electrically complete all as directed by Engr in charge.
Total amount of Sch 'A' part-V Section-I (External Electrification)
Sch 'A' Part-V Section-II (External Electrification) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Weather proof outdoor bus bar chamber, made out of 3.15mm thick MS sheet with front & rear Opening, powder coated, dust & vermin proof, IP-66 Protection comprising 4 Nos aluminium strips each of 200 Amps, 60cm long having 10cm min distance from the body, duly insulated mounted on epoxy insulators in horizontal position in stepped manner with 4 No’s mounting legs made out of 40mm x 40mm x 6mm angle iron grouted in PCC block of size 30cm x 30cm x 90cm (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and connections with size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils, including taking out old unserviceable bus bar chamber complete all as specified and directed by Engr-in-charge
(d) Electric Starter equipment :- the equipment will comprise the following :- (i) Maint free battery duly initial charged of suitable capacity & battery Lead of aqequate capacity Make of Battery Exide/Amron/ (ii) Starter Motor (iii) Starter gearing (iv) Start/Stop push button (v) Invertor cum battery charging 500 VA capacity suitable to work on 230 volts 50 Hz Ac supply system for charging of DG set batteriesto charge the set batteries externally when DG set is in off postion Make : sukam (vi) Alternator/dynamo of suitable capacity whiles DG set is running complete with auto cut out all as per manufacturer recommendation (e) PCC foundation for DG set of suitable size including 1 mtr working space all around the DG set and 0.2 mtr above and 0.3 mtr below FFL all as per manufacturer recommendation or as directed by Engineer-in Charge
Total amount of Sch 'A' part-VI Section-I (CENTRAL AIR HEATING)
SCHEDULE `A' PART-VI(Sec-II)(CENTRAL AIR HEATING) is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green filed under Col-6.
Design, Supply, fixing, commissioning and testing of vertically mounted Thermic Fluid Heater (TFH) capable of delivering a heat output 50000 K Cal/Hr using HSD oil complete in all respect, including following item of work. NOTE:-Boiler shall be provided for a system of 2 working simultaneously and one stand by on rotation basis. (a) Heater unit: heat exchanger, consisting of closely wound , helical, concentric coils, arranged to give adequate no of passes on flue gas side & made out of ERW tubes, confirming to IS 3059 Pt-I, suitable for high temperature all as per manufacturer design and of required head and capacity. (b) Pressure jet burner : suitable for light oil firing with stepless modulation mechanism all as per manufacturer design and of required head and capacity. (c) Combustion air fan with drive motor assembly all as per manufacturer design and of required head and capacity. (d) Control Panel : Dust protected pre-wired unit mounted air cooled control panel housing a burner management system , switchgear consisting of contactors, overload relays, fuses and MCB etc.all as per manufacturer design and of required capacity. (e) Circulating Pumps : Centrifugal Thermic fluid circulating pumps suitable for high temp operation, coupled with electric motor drive, mounted on common base frame all as per manufacturer design and of required head and capacity. CONTD...
(f) DE Tank : Derator cum expansion tank consisting of expansion, derator and buffer vessels , gauge glass assembly and level switches. Nozal for inlet and outlet on derator for drain on buffer vessel and for overflow, air vent and topup on expansion vessel all as per manufacturer design and of required head and capacity. (g) Fuel pump : with drive motor assembly all as per manufacturer design and of required head and capacity. (h) Piping work : required inside the plant room, including valves, pressure indicating instruments, insulation material, protective works etc all as per manufacturer design and of required head and capacity. (j) Oil line : with duplex filters on fuel line at the inlet of fuel pump, Y strainer on fuel line between fuel pump and burner, non return valve on fuel pump outlet and bypass line, non return valve on modulation and circulation line, fuel oil regulation valves for burner modulation, burner solenoid valve, fuel oil pressure gauge at burner inlet, fuel pressure gauge on by pass line etc all as per manufacturer design and of required head and capacity. (k) Thermic fluied line : inside the plant room with insulating material, spring loaded safety relief valves , Temp controller for stepless burner modulation on thermic fluid out let temp of the heater, switch for burner on/off cycle, burner interlocking with temp of thermic fluid at , differential pressure switch between inlet / outlet of fluid outlet all as per manufacturer design and of required head and capacity. (l) Burner programmer with matching flame sensor all as per manufacturer design. (m) Hooter mounted on control panel for audible safety alarm all as per manufacturer design. (n) Temp indicator cum-switch for high stack temp alarm for flue gases all as per manufacturer design. (o) Control wiring from CHS control panel to all pumps and equipment will be PVC insulated copper conductor multistranded 1100 volts graded. Note :- Thermic fluid and thermic fluid line including lagging from plant room to work place shall be provided as separate item of work .
Design and installation of Diesel (Fuel) storage tank of capacity of 1000 ltr made out of 5mm thick MS sheet complete all as specified and as directed.
Design and Installation of Thermic fluid Storage tank of capacity 500 Ltr made out of 5 mm thick MS Sheet complete with supply arrangement for toping up of service tanks including control/ drain valves all as required. (Inside the Plant room)complete all as specified and as directed.
Kaiflex insulation tubing of size 60mm inner dia and 19 mm thick including jointing, fixing material such as solvent adhesive, tape insulation self adhesive and polyshield coating, including polyglass tape and (Resin+hardner) two coats as per manufacturers recommendation complete all as specified.
Supply in barrels and filling of thermic fluid of capacity above 200°C Temp as vapourisation temprature complete all as specified and as directed.
Supply ,installation and erection of chimney 10mtr height as per design for 50000 kcal/hr complete all as specified and as directed.
Cutting the existing GI tubing of bore 80mm and inserting tee of size 80x80x50mm for taking out branch connection including connected material required for such connection such as GI nipple,union socket,earthwork etc complete all as specified and as directed.
Design,supply,install,commissioning and testing of double skin floor mounted air handling unit with 6 rows deep coil of nominal capacity approx 1500 CFM complete all as specified and as directed.
MCB TPN 32A ,415 volts with rupturing capacity 10KA,ISI Marked complete all as specified and as directed.
Total amount of Sch 'A' part-VII(LIGHTENING PROTECTION)
Total amount of Sch 'A' part-VIII ( ROAD/PATH/CULVERT)
Total amount of Sch 'A' part-IX (SECION I) (EXTERNAL WATER SUPPLY)
Sch 'A' Part-IX(Sec II) (EXTERNAL WATER SUPPLY) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Stainless steel (Fire retardant, closed cell, chemically cross linked insulation material with thermal & Acoustic Insulation) water tank CYL/12150/16-04/SS, Volume 1500Ltr, 1950mm HT with stand, 1230mm dia approx and LID dia 420 mm, with 38mm discharge, 38mm overflow, 25mm inlet and 50mm outlet with 20mm Airvent including complete fitting, installation and testing as per specified and directed
Valve pit of size (60 x 60 x 90 cm) consisting of random rubble uncoursed stone masonary in cement mortar 1:6, 50 mm thick coping with PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) incl excavation and earth work and disposal of surplus soil to a distance not exc 50 mtr and depositing where directed by Engr-in-Charge, plastering internally with 15 mm thick in cement mortar 1:6 and flush pointing externally in the same mortar as work proceed and mild steel sheet cover (3.15 mm thick) angle iron frame of 40 x 40 x 6 mm handle locking arrengement and painting with two coats of synthetic enamel paint over a coat of red oxide primer on steel surface complete all as specified and directed by Engr-in-charge.
Supply and fix Open well Submersible Pump 3 Phase 2 HP, Voltage Rating 440 Volts AC Rating 2 HP and 1.5 KW, head Range-9-21 Meter, Flow Range-475-130 LPM , Pipe Size (mm) 50x50 complete all as directed by Eng-in-charge
Supply and laying Three Core PVC Insulated & PVC Sheathed Industrial Cable for Submersible Pump Motors, 1100 Volts, of size 2.5 Sqmm complete all as specified and directed by Engr-in-charge.
Supply installation ,commissioning and testing LT panel outdoor cubical floor mounted type made of3.15mm thick CRCA sheet duly powder coated complete with aluminium bus bar having rating of 1.5 times of incoming MCB duly mounted on epoxy based fixed on angle iron frame of 40x40x6mm panel embedded in 40mm thick PCC 1:2:4 B-1 using 20mm stone aggregated and suitable to accommodate and including the following :- (a)MCB 63A,TPN,10 KA-01 NO (incoming) (b)MCB 25A, TPN, 10KA-02 NO (c)DOL starter 2 HP, 3 Phase -01 NO (d)Indicating lamp LED type (RYB) (e) Wiring complete of suitable size copper cable
Total amount of Sch 'A' part-X( SEWAGE DISPOSAL)
Total amount of Sch 'A' part-XI( AREA DRAINAGE)
Total amount of Sch 'A' part-XII(Sec I)( SECURITY FENCING AND GATE WORK)
Sch 'A' Part-XII(Sec II) (SECURITY FENCING AND GATE WORK) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Crossed Spiral Concertina coil 500 mm dia,madeup of 2.60mm HTGS spring core wire having tensile strength of 1600N/sqmm and Punched tape of 0.50mm thick and 13mm wide after crimming . Punched tape shall be of hot dipped galvanised min 200 micron and having medium barbs of 24mm width @ 35mm centre to centre. Each concertina coil shall be of min 50 turns and 5 clips in two turns i.e. 125 clips per coil. (Weight of coil 7 kg to be streched upto 3.25 RM i.e appx 2.15kg/Rm), complete all as specified and directed by Engr In Charge.
Total amount of Sch 'A' part-XIII(SITE CLEARANCE,EXCAVATION AND EARTH WORK)
Dee Ess Construction Co
Intrernational Engineers
M/S MIR HILAL CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .