diesel generators- DG Sets Diesel Generators- DG Sets ( 1 ) Technical Specifications Specification Specification Name Values Allowed Values OUTPUT CAPACITY RATING/PHASE Nominal Rated Capacity (KVA) 125 As per GeM Catalogue. (or higher) No of Phase - Single phase
Three Phase ENGINE Make of Engine - - Model Number of Engine - - Capacity of Engine (cc) - - Engine Power (kWm) - - ISI Marking to IS :10001 for engine false - BIS license No
if applicable - - Type of Engine cooling Liquid Cooled Air Cooled
Liquid Cooled Type of governer Mechanical Mechanical
Electronic (or higher) Class of governer A1 A0
A1
A2 (or higher) Number of cylinders (nos) 6 - No of Strokes (nos) 4 - 1/4 Rated RPM of Engine (RPM) - 1500
3000 Overload capacity for one hour for every 11 hours continuous running at full load (%) 10 - Specific Fuel Consumption (gm/kWh) - - Starting voltage (volt) 12 - ALTERNATOR AC GENERATOR(ALTER NATOR) Make - - AC GENERATOR(ALTER NATOR) model Number - - Rating of AC Generator (KVA) 125 - Power Factor of AC generator 0.8 - Efficiency at rated Power factor at 75% of full Load 92.2 - Compliance of Alternator to IS:13364(part-1) Yes - Type of alternator Brushless - Voltage Regulation Grade VG 2 - Alternator IP Rating IP 23 - Class of Insulation H - CONTROL PANEL Control Panel AMF Manual
AMF IP Rating of Control Panel IP 53 - ACOUSTIC ENCLOSURE Sheet Thickness 1.8 1.6
1.8
2
1.2 Higher is better Thickness of Foam 40 - Density of Foam for sound insulation 40 - Noise level at 1 meter (dB) 75 - BATTERY Battery Type & Specification Low Maintenance free to IS: 14257 for high cranking performance - Battery capacity (Ah) - - No of batteries 1 - TEST REPORTS Availability of Type test report for Engine from Yes - 2/4 Central govt/NABL/ILAC accredited laboratory Test Report number and date(Engine) - - Name and address of laboratory(Engine) - - Availability of Type test report for Alternator from Central government/NABL/ILAC accredited laboratory Yes - Test Report number and date(Alternator) - - Name and address of laboratory(Alternator) - - DG set meet requirements of Enviro nmental(Protection) Rules 1986
in respect of noise and emission norms
as described in STC Yes - WARRANTY INSTALLATION & COMMISSIONING Warranty 1 Installation & Commissioning With Installation With Installation
Without Installation Agreed to STC of the Product Yes - * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Ram Krishna Bhatt 228001
MEJARFGANJ SULTANPUR 1 15