| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.1 LAccepted-AOC KG 115 SABIRA MANZIL HBR 2ND STAGE VENKATESH PURAM BANGALORE 560 045 | BENGALURU URBAN | KARNATAKA | 560045 | ₹22.1 L Quoted ₹23.1 L | L1 | Accepted-AOC Being lowest bidder and reasonable |
| 2 | L2₹25.0 L+₹1.9 L (8.30%)Rejected-AOC | ₹25.0 L+₹1.9 L (8.30%) | L2 | Rejected-AOC Not being lowest bidder |
| 3 | L3₹28.3 L+₹5.2 L (22.5%)Rejected-AOC | ₹28.3 L+₹5.2 L (22.5%) | L3 | Rejected-AOC Not being lowest bidder |
| 4 | L4₹31.7 L+₹8.6 L (37.3%)Rejected-AOC | ₹31.7 L+₹8.6 L (37.3%) | L4 | Rejected-AOC Not being lowest bidder |
| 5 | L5₹35.6 L+₹12.5 L (53.9%)Rejected-AOC | ₹35.6 L+₹12.5 L (53.9%) | L5 | Rejected-AOC Not being lowest bidder |
Tender Value
Refer Docs
EMD Value
₹75,000
Closing Date
14 Oct 2020, 6:00 pmClosed
GE I R nd D West Bengaluru
GARRISON ENGINEER I R nd D WEST BANGALORE DRDO COMPLEX CV RAMAN NAGAR BANGALORE
REPAIRS AND MAINT OF CEILING FANS, EXHAUST FANS, PEDESTAL FANS, GEYSERS, KWH METERS, INTERNAL WIRING AND CONNECTED WORKS AT RESIDENTIAL COMPLEX UNDER GE(I) RndD (WEST) BENGALURU
2020_MES_366069_1
GE(I) R ND D (WEST)/BAN/33 OF 2020-21 8830E8
Open Tender
Civil Works
Item Rate
180 days
Bengaluru
Class and Category as per NIT
8 documents required · 8 mandatory
₹500
GE I R nd D West Bengaluru
₹75,000
Yes
26 Nov 2020
15 Sept 2020
20 Oct 2020
16 Sept 2020
14 Oct 2020
1 Oct 2020
16 Sept 2020 - 30 Sept 2020
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc removing serviceable materials to store for keeping in safe custody or for offering credit (credit for all the retrieved items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc., all as specified and as directed.
Material and labour for concealed Point wiring with PVC insulated unsheathed, multi stranded copper conductor FRLS cable of size 1.5 sq.mm, 1100 grade, with PVC insulated unsheathed multi stranded copper conductor cable of size 1.5 sq.mm for earth continuity wire, drawn into and including non metallic rigid PVC conduit of suitable size, medium grade ISI marked including metal flush boxes of suitable size, modular white cover plate and holding plate for mounting switches/ sockets etc fixed on walls/ roof surface concealed in walls including all necessary wall cutting and making good disturbed surface complete all as specified and directed for One light / fan / bell point controlled by one, one way switch 5/6 Amps complete all as specified and as directed. Note : i) The quoted rate shall deemed to include the cost of metal flush boxes, modular white cover plate, provision of blank plates as per requirement and making the disturbed surfaces to match with the existing. ii) Cutting and chases in brick / block masonry for conealed wiring, including making good the disturbed surfaces matching with adjacent shall deemed to be included in the quoted rate.
All per Serial Item No 2 here-in-above, but suitable for 3-pin, socket outlet 5 Amps, fixed on independent board.
All per Serial Item No 2 here-in-above, but suitable for 3-pin, socket outlet 5 Amps, fixed on same board.
All per Serial Item No 2 here-in-above, but two way switch point controlled by 2-way switch.
Material and labour for, concealed Point wiring for One power point, 3 pin 15 amps socket out let 230 Volt 50HZ on Independent board with 2.5 sq.mm (nominal area) PVC unsheathed, PVC insulated, multi standard copper conductor cable of 1100 Volts, FRLS grade, single core cable drawn through rigid non metallic concealed PVC Conduit of suitable size, medium grade, ISI marked fixed on walls / ceiling / roofs along with 2.5 sq.mm cable but in green colour as continuous earthing wire and connecting to common earth dolly complete with modular white cover plate with frame and metal flush box for mounting switch socket combinations as required complete all as specified and as directed. Note : i) The quoted rate shall deemed to include the cost of metal flush boxes, modular white cover plate, provision of blank plates as per requirement and making the disturbed surfaces to match with the existing. ii) Cutting and chases in brick / block masonry for conealed wiring, including making good the disturbed surfaces matching with adjacent shall deemed to be included in the quoted rate.
Supply and fix Modular Switch, One module , One way, 5/6 Amps, 240 Volts all as specified and as directed.
Supply and fix Modular Switch, 2-way, 1 module, 6 Amps complete all as specified and directed.
Supply and fix, Modular socket outlet 5/6 Amps 5 pin, complete all as specified and directed.
Supply and fix, Modular socket outlet 6/16 Amps 5 pin, complete all as specified and directed.
Supply and fix in repairs, Modular bell push switch, one module, single pole, 230 volts 5/6 Amps capacity all as specified
Supply and fix in repairs, Modular fan Regulator,120 W, electronic stepped type, 230 Volts 2 module, complete all as specified and as directed.
Supply and fix in repairs, Ceiling rose surface type, Bakelite, 65 x 50 mm ISI marked with three terminals all as specified and as directed.
Supply and fix in repairs, Ding Dong bell, working on 230 volts, single phase complete all as specified and as directed.
Supply and fix in repairs, lamp holder PVC/polycarbonate type with black plate, suitable for 9 W LED lamp (including 9 watt lamp) complete all as specified and as directed.
Taking down unserviceable FTL light fitting, Supply and fix, wall mounted LED tube light fitting with lamp, 18 Watt, 4 feet, with high lumen output, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, complete with diffuser, polyester louver & integrated electronic driver as per cat No LUMILINEBS18WLED830SPCWH of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Taking down unserviceable FTL light fitting, Supply and fix, wall mounted LED tube light fitting with lamp, 9 Watt, 2 feet, with high lumen output, environmental friendly, energy efficient LED, with accessories, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, complete with diffuser, polyester louver with 9 watt LED tube & integrated electronic driver 9 W fitting as per cat No LUMILINEBS9WLED830SPCWH of make Havells or techno commercially equivalent makes specified here-in-after complete all as specified.
Taking down existing unserviceable down lighter fitting, Supply and fix, 36 / 40 W, LED, down lighter fitting, efficient luminaire, 2'x2', Ultra modern designed architectural LED luminaire which provides soft-light and glare free symmetrical illumination suitable for ceiling, IP 20 protection Class I, system electrical efficiency > 85%, system efficacy > 120 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH , 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, integral drivers, prewired and connecting with 3 Core, 1 sq mm sheathed copper flexible cable, including lamps complete all as specified and directed. MAKE:- Cat No.VENUSNEOHE2X2PLR36WLED8XXS of Havells or techno-commercially equivalent model in Philips / CG / Syska complete with all accessories pre-wired, all as specified and as directed.,
Supply only, 25 W, LED security light fittings with lamp 25 W,with high lumen output, environmental friendly, energy efficient LED, with die cast aluminium body, with lamps and accessories, IP 20 protection, system electrical efficiency > 85%, system efficacy > 100 lm/W, operating voltage between 140 - 270 V, AC, 50 Hz, TDH, 10%, power factor ≥ 0.95, surge protection 2.5 kV, colour temperature 5700 K, CRI > 80, intergral drivers, fittings made of powder coated housing, enclosed with glass cover in frame, connecting to loop boxes electrically, light fitting conforming to Cat No ENDURAPEARLSL25WLED 757SASYTOPCMP of Havells or techno commercially equivalent approved model, prewired and connecting with 3 Core, 1 sq mm sheathed copper flexible cable, complete all as specified and directed.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, stranded copper conductor cable, 2 runs of single core of size 6 Sq mm and one run of earth continuity conductor of size 6 Sq mm to be drawn through and including 20 mm wide / dia PVC Casing and capping / PVC conduit medium Grade fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - Two runs of 6 sq.mm cable, one run of 6 sq mm earth wire and one run of PVC conduit shall be measured as one length.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, stranded copper conductor cable, 4 runs of single core of size 6 Sq mm and one run of earth continuity conductor of size 6 Sq mm to be drawn through and including 20 mm wide / dia PVC Casing and capping / PVC conduit medium Grade fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - Four runs of 6 sq.mm cable, one run of 6 sq mm earth wire and one run of PVC conduit shall be measured as one length.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, stranded copper conductor cable, 4 runs of single core of size 4 Sq mm and one run of earth continuity conductor of size 4 Sq mm to be drawn through and including 20 mm wide / dia PVC Casing and capping / PVC conduit medium Grade fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - Four runs of 4 sq.mm cable, one run of 4 sq mm earth wire and one run of PVC conduit shall be measured as one length.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, stranded copper conductor cable, 2 runs of single core of size 4 Sq mm and one run of earth continuity conductor of size 4 Sq mm to be drawn through and including 25 mm wide / dia PVC Casing and capping / PVC conduit medium Grade fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - Two runs of 4 sq.mm cable, one run of 4 sq mm earth wire and one run of PVC conduit shall be measured as one length.
Taking down unserviceable sub main wiring, supply and fixing Sub main wiring using FRLS grade PVC insulated unsheathed, 1100 volts grade, stranded copper conductor cable, 2 runs of single core of size 10 Sq mm and one run of earth continuity conductor of size 10 Sq mm to be drawn through and including 25 mm wide/ dia PVC Casing and capping / PVC conduit medium Grade fixed on surface / concealed in walls / roof / floors complete all as specified and as directed. NOTE: - Two runs of 10 sq.mm cable, one run of 10 sq mm earth wire and one run of PVC Casing and capping / PVC conduit shall be measured as one length.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB SPN 8 way (Horizontal), double door with Sheet metal enclosure, flush mounted, prewired, 240 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respecitve items.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB SPN 12 way (Horizontal), double door with Sheet metal enclosure, flush mounted, prewired, 240 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respecitve items.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB TPN 4 way (Horizontal), double door, with Sheet metal enclosure, flush mounted, prewired, 415 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respecitve items.
Taking down unserviceable sheet metal enclosure/ DB, supply and fix, MCB DB TPN 8 way (Horizontal), double door, with Sheet metal enclosure, flush mounted, prewired, 415 V, AC, 50 Hz, Factory made, powder coated, IP-42 protection conforming to IS-13032 universal mounting with 200 Amps rated copper bus bar, neutral link, earth link, earthing studs, detachable gland plates with knockouts on both sides, etc complete all as specified and as directed. Notes : i) All unused modules shall be provided with blanking plate for which the cost is deemed to be included in the cost of MCB DBs. ii) MCB/ Isolators will be measured and paid separately as supply and fix under respecitve items.
Supply and fix in repairs, sheet metal enclosure, SPN, 20 Amps, with MCB SP 20 Amps ('C' Curve, 230 Volts AC, 50 Hz, 10 kA, breaking capacity), with a two pin, earth plug and socket, complete all as specified.
Supply and fix in repairs, sheet metal enclosure, TPN, 32 Amsp, with MCB TPN 32 Amps ('C' Curve, 415 Volts AC, 50 Hz, 10 kA, breaking capacity), with a three pin, earth plug and socket, complete all as specified.
Supply and fix in repairs, sheet metal enclosure, TPN, 63 Amsp, with MCB TPN 63 Amps ('C' Curve, 415 Volts AC, 50 Hz, 10 kA, breaking capacity), with a three pin, earth plug and socket, complete all as specified.
Supply and fix, MCB SP, 240 volts, 6 to 32 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB SPN, 240 volts, 40 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB TPN, 415 volts, 63 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Supply and fix, MCB TPN, 415 volts, 100 Amps, 50 Hz, 10 KA breaking capacity, 'C' Series all as specified and as directed.
Disconnecting and taking down unserviceable MCCB in any position, Supply and fix, MCCB TPN, 100 Amps, working on 440 volts, 50 Hz AC supply, 25 kA, SKB1, series complete, all as specified and as directed.
Taking down existing ceiling fan/exhaust fan of any sweep with blade and down rods etc from ceiling/walls by unscrewing the nut bolts, opening the split pin and keeping in safe custody repairing and re-fixing the same after repairs, preparing the surfaces and spray painting with two coats of synthetic enamel paint, writing MES No. complete all as specified and as directed. Note: Repairs shall be measured and paid for separately under respective items.
Taking down existing unserviceable exhaust fan of any sweep with blade and louvers and depositing same in AGE E/M store yard, Supply and fix, exhaust fan 230/240 Volt, 50 Hz, single phase, AC supply, 300 mm sweep with louvers complete with metal body powder coated with protective steel bird guard on wall of building with and including provision of 3 core 1.5 Sq.mm flexible cable from ceiling rose to exhaust fan including writing MES number on exhaust fan motor using synthetic enamel paint of approved tint, complete all as specified and directed. MAKE:- Model: Ventil Air-DSP of Havells or techno-commercially equivalent model in Almonard / Bajaj.
Making holes in existing wall surfaces for fixing exhaust fans of 300 mm sweep, , finishing the disturbed surfaces matching with adjoining surfaces, complete all as specified and directed.
Disconnecting, taking down ceiling fan, with blade, inspecting motor assembly, replacing burnt out capacitors, split pins, etc, servicing, cleaning, greasing, removing all deposited materials, checking for smooth functioning, re-assembling the same complete all as specified and directed. NOTE:- Cost of spare parts shall be measured and paid for separately under respective items.
Rewinding of ceiling fan motor with super enameled copper winding wire of suitable gauge after cutting and removing burnt winding, including varnishing of new winding and drying up carefully all as specified and directed.
Supply and fix, capacitor of 2.5 mfd for ceiling fan, single phase, 230 V, complete all as specified and directed.
Supply and fix, capacitor of 4 mfd for exhaust fan, single phase, 230 V, complete all as specified and directed.
Dismantling / opening of exhaust fan of 300/450mm sweep motor assembly inspecting all dismantled parts repairing replacing the unserviceable parts and following components with new ones including oiling greasing reassembling motor assembly all as specified and directed. NOTE:- NOTE:- Cost of spare parts shall be measured and paid for separately under respective items.
Rewinding of exhaust fan motor 300/450 mm sweep with super enameled copper winding wire of suitable gauge after cutting and removing burnt winding, including varnishing of new winding and drying up carefully all as specified and directed.
Disconnecting burnt cables of size 16 Sq mm (4 runs, 4 core) from MCCB DB / TPN / Cubical, removing the burnt cable, providing suitable length of 1100 V, FR grade, copper conductor cable (approx 0.5 m of 4 runs cable), crimpling with copper lugs of suitable size, connecting back to bus bar, testing for any loose connections, tightening with suitable nuts, bolts, washers, complete all as specified and as directed.
All as per Serial Item No 46 here-in-above, but for cable of size 25 Sq mm (4 runs).
All as per Serial Item No 46 here-in-above, but for cable of size 35 Sq mm (4 runs).
Taking down existing unserviceable electric meters of any type, Supply and fix new electric energy meters, domestic type, 10 - 60 Amps, AC, single phase, digital type, static energy meter of accuracy class 1.0, working on 240 volts, 50 Hz, with back lit LCD display with special features like TOD, tamper logging, optical communication port & display in absence of power all as per Cat No. WM101BC7DDHBOX 10-60 Amps of L&T or other techno commercial equivalent model in Secure / HPL as approved including load test for at least 4 hours and recording the reading on hourly basis, obtaining the users signature, complete all as specified and as directed. Note: i) Old unserviceable electric meters shall be deposited to AGE E/M (R&D) West storeyard. ii) The quoted rate shall deemed to be inclusive of connecting, testing and switching-on, on prevailing load for atleat 4 Hours, recording the readings on hourly basis and obtaining the users signature.
Taking down existing unserviceable electronic energy meters of any type, Supply and fix new electronic energy meters, domestic type 10-60 Amps, AC, 3-phase digital type, static energy meter of accuracy Class 1.0 working on 240 V, 50 Hz, with back light LCD display with special features like TOD, Tamper logging, optical communication port and display in absence of power all as per CAt No Secure 1 - Credit 300 10-60A of Secure or techno commercial eqauivalent of L&T / HPL complete, including taking down existing unserviceable meters of any type and depositing to AGE E/M store yard, complete all as specified and as directed. Note: i) Old unserviceable electric meters shall be deposited to AGE E/M (R&D) West storeyard. ii) The quoted rate shall deemed to be inclusive of providing 3 mm thick hylum sheet mounting plate of suitable size (to be provided inside the meter box of MS sheet) as per manufacturer's instructions, drilling holes of suitable size, fixing the meter with screws, wooden gutties, etc., connecting, testing and switching-on, on prevailing load for atleat 4 Hours, recording the readings on hourly basis and obtaining the users signature.
Taking down unserviceable geyser of capacity 25/50 liters from site and shifting to civil work shop for its tank welding/soldering or repairing, replacing unserviceable parts if any, complete and refixng at the same locations, including painting with one coat of white paint complete all as specified and as directed. NOTES :- Parts replaced shall be paid and measured seperately under relevant items as supply only.
Supply only Heating element coil for 2500/2000 Watts capacity with rubber bush complete all as specified and as directed.
Supply only Thermostatic switch suitable for for geyser complete all as specified and as directed.
Supply only PVC Hot and Cold type connection pipe 15/20mm dia 450mm long with couplers and washers on both sides suitable for cold and hot water lines complete all as specified and as directed.
Taking down unserviceable, ceiling fans, depositing same in AGE E/M Storeyard, Supply and fix, Ceiling fan BEE 5 star rated complete 1200mm sweep, energy efficient suitable to function on 230V, single phase, AC supply, white colour, with down rod 300mm long, capacitor 2.5 mfd, canopies, nuts, bolts and washers and connecting with and including provision of 3 core 1.5 sq.mm PVC sheathed flexible copper conductor from ceiling, writing MES number on ceiling fan motor complete all as specified and directed. MAKE:- Auro Plus of Crompton Greaves or techno-commercially equivalent model in BAJAJ / HAVELLS / USHA
Taking down unserviceable, storage water heaters depositing same in AGE E/M Storeyard, Supply, installation, testing and commissioning of vertical type electric storage water heater of capacity 25 litre, BEE five star rated, 230 Volt, AC, 50Hz, comprising of heating element 2000/2500 Watt, puf insulation, both power indicating LED lamp and heating indicating LED lamp, actual standing energy loss per 24 hours / 45°C temperature difference not to exceed 0.5KWH, re-heating time for 35°C temperature rise not to exceed 20 minute, adjustable thermostat (temperature range in °C is 25-75±5), rated water pressure (N/sq.cm, water head (metre)) is 80/80, glass lined tank, glass coated heating element (to prevent water scale formation on element), temperature control knob, anode ord (to protect tank from corossive element), thermal cutout, safety valve (the safety valve shall be designed to automatically relieve pressure and discharge water in case the pressure overshoots the preset limits), with and including provision of necessary suitable 3-core copper cable, suitable plug top, , fixing of geyser on wall / surface with and including provison of suitable size of wall mouting bracket and 100mm length anchor bolts, including provision of all necessary plumbing work, civil works etc., complete all as specified and directed. MAKE:- AO Smith / Racold / Venus / Jaquar Note : PVC rigid pipe connection for hot and cold water shall be measured and paid separately under respective item of this Schedule.
Demolishing old earthing pit, and providing new earthing pit with material and labour for earthing complete with Galvanized Iron earth plate electrode 600 mm x 600 mm x 6.3 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to GI earth strip of 32 x 6 mm, by means of bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 20 mm bore (light grade) connected to earthing test point all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 40 mm bore light grade GI pipe for watering funnel wire mesh, PCC chamber in cement concrete (1:3:6), type C1 , manhole cover with RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover and MS frame etc., complete all as specified and as directed NOTES :- (i) The quoted rate deemed to include earth strip and protection pipe up to 7.5 metre from earth plate / earth point/test point. (ii) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
kamadhenu Electricals
SRI LAKSHMI CONSTRUCTIONS
SREE VARU ELECTRICALS
Solar Electricals and Electronics
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .