Executive Engineer
Electric Division JPDCL Udhampur
erection of 11 KV Line on 9mtr poles, 30mm sq. ACSR Conductor for creation of 25 KVA Sub stn. at Fruit Plant Nursery Pachound (Majouri Zone) District Udhampur
2024_PDD_256857_1
ED/Udh/10 of 2024-25 dt. 12-08-2024
Open Tender
Electrical Works
Turn-key
60 days
At Pachound
Please refer Tender documents.
2 documents required · 2 mandatory
₹600
Executive Engineer Electric Division JPDCL
₹11,800
26 Sept 2024
13 Aug 2024
3 Sept 2024
13 Aug 2024
2 Sept 2024
13 Aug 2024
13 Aug 2024 - 21 Aug 2024
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV Line on 9mtr poles, 30mm sq. ACSR Conductor for creation of 25 KVA Sub stn. at Fruit Plant Nursery Pachound (Majouri Zone) District Udhampur
9 mtr. Long ST Pole (ST-410 SP-33)
GI V-Cross arm with top bracket including clamp
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45KN, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of ST poles 9 mtr. with Aluminium paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 25 KVA Sub stn. at Fruit Plant Nursery Pachound (Majouri Zone) District Udhampur.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 kv GO, AB Switch 3 phase 3 pole 200 Amp Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galavinized Nuts and Bolts.
LT Fuse set made 50x6mm angle iron and 50x6mm Aluminium Bus bar strip fixed on Bus Bar insulator.
Cement bottoming 1:2:4 mix as per REC standards 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
3-Ø 4-Wire Prodigy Meter
VIBRANT CONSULTANT
SWASTIK ELECTRICAL AND CONSTRUCTION WORKS
VEENA CONSTRUCTION CO.
M/S VAISHNO TRADERS
SUMIT SHARMA
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .