Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.5 CrAccepted-AOC | ₹2.5 Cr | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹2.5 Cr+₹1.8 L (0.73%)Rejected-Finance | ₹2.5 Cr+₹1.8 L (0.73%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹2.5 Cr+₹2.0 L (0.82%)Rejected-Finance | ₹2.5 Cr+₹2.0 L (0.82%) | L3 | Rejected-Finance Other than lowest bidder |
| 4 | L4₹2.6 Cr+₹9.2 L (3.74%)Rejected-Finance | ₹2.6 Cr+₹9.2 L (3.74%) | L4 | Rejected-Finance Other than lowest bidder |
| 5 | L5₹3.0 Cr+₹49.9 L (20.2%)Rejected-Finance | ₹3.0 Cr+₹49.9 L (20.2%) | L5 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | M/S VED PAUL MAHAJAN L1 | Sarbat Construction Co L2 | MOHAN BROTHERS L4 | Continental Enterprises L3 | M/S PARDEEP KOHLI L5 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Drilling of Trail Bore Hole 300mm (12 inch) dia from ground level to 200 meter in any strata by ROTARY METHOD method as per IS : 2800 1979 (revised and amended) below ground level through any kind of strata soils/rocks, disposal of surplus soil within a distance of 100m, well rammming and stablizing of material , transportation of drilling Rig and other T&P required, keeping space for pea gravel packing in and including lowering and extraction of casing pipes of suitable thickness after lowering of designed assemble of EWR pipe, complete all as specified and as directed Engr-in-Charge. | 400 | RM | 10,300 ₹41,20,000 | 13,000 ₹52,00,000 | 13,500 ₹54,00,000 | 7,500 ₹30,00,000 Lowest | 14,500 ₹58,00,000 |
| 1.01Notes:- 1. ERW housing pipes shall be measured and paid seperately. 2. Casing pipe alongwith direct rotary drill Pipes with with tools shall be arranged by the contractor and the same shall remain property of contractor after extraction. 3. In case of non extraction of casing pipe during the course of drilling any type of mishappening, any type of fishing operation of failure of bore well the contractor will have no claim what so ever on this account. | ||||||||
| 1.02The contractor has to submit the test result/report as per IS:2800(Part-II -1979(with amendment) as following:- (a) Results of the tubewell depth and water level measurements. (b)Results of development and drawdown test are to be given in tabular form as per relevant IS. (c) The vertically test report shall be given as per the relevant IS. (d). The Housing/ Casing pipe shall be inserted only after certificate given by GE for sucessful trial bore hole. | ||||||||
| 2.00 | Enlargement of borehole from 300 mm to 500mm from Ground Level to 200 mtrs. Notes:- (i) The rate for development of trial bore beyond 200mtr depth, if ordered by GE depending upon the CGWB recommendation or the basis of the Electrical logging Report, will be admissible at the rate of this Item.
(ii)The note is applicable for Srl item No 1 verticality Test of the Tube-Well Structure shall be carried out by the contractor and the cost is deemed to be included in the Item rate. | 400 | RM | 2,000 ₹8,00,000 Lowest | 4,000 ₹16,00,000 | 6,100 ₹24,40,000 | 2,100 ₹8,40,000 | 6,900 ₹27,60,000 |
| 3.00Supplying, assembling including lowering and fixing liner assembly or strainer etc in position (net affective length shall only measured and paid) all as specified below. | ||||||||
| 3.01 | Mild steel ERW bevelled end pipe 300mm (12 inch) nominal bore having min 8 mm wall thickness confirming to IS:4270-2001 and all around welded with 03 Nos stiffeners of flat iron 75x8mm, 150 mm long, complete all as specified and as directed Engr-in-Charge. | 100 | RM | 6,000 ₹6,00,000 | 5,000 ₹5,00,000 Lowest | 6,550 ₹6,55,000 | 5,900 ₹5,90,000 | 7,500 ₹7,50,000 |
| 3.02 | Mild steel ERW bevelled end pipe 200mm (08 inch) nominal bore having min 8 mm wall thickness confirming to IS:4270-2001 and all around welded with 03 Nos stiffeners of flat iron 75x8mm, 150 mm long, complete all as specified and as directed Engr-in-Charge. | 260 | RM | 3,500 ₹9,10,000 Lowest | 5,000 ₹13,00,000 | 4,500 ₹11,70,000 | 3,600 ₹9,36,000 | 5,000 ₹13,00,000 |
| 3.03 | Mild steel ERW bevelled endslotted housing pipe nominal bore 200mm (12 inch) nominal bore having min 8 mm wall thickness confirming to IS:4270-2001 having slot size of 1.6mm x75mm as per (IS:8110:2000) and all around welded with 03 Nos stiffeners of flat iron 75x8mm, 150 mm long, complete all as specified and as directed Engr-in-Charge. | 40 | RM | 4,250 ₹1,70,000 Lowest | 5,200 ₹2,08,000 | 6,000 ₹2,40,000 | 4,600 ₹1,84,000 | 6,100 ₹2,44,000 |
| 4.00 | Housing pipe clamps made of MS flat of size 100 mmx 12mm and 750mm long for 300mm (12 inch) bore pipe with suitable bolts, nuts and washers, complete all as specified and as directed Engr-in-Charge. | 8 | Each set | 5,200 ₹41,600 | 2,500 ₹20,000 Lowest | 3,650 ₹29,200 | 9,000 ₹72,000 | 3,900 ₹31,200 |
| 5.00 | Supply and filling Pea gravel of Size 2mm to 6mm around the liner assembly from bottom to ground level including continous watering during development, complete all as specified and as directed Engr-in-Charge. | 45 | Cum | 4,800 ₹2,16,000 | 3,200 ₹1,44,000 Lowest | 4,000 ₹1,80,000 | 4,100 ₹1,84,500 | 4,000 ₹1,80,000 |
Tender Value
₹2.8 Cr
EMD Value
₹3.5 L
Closing Date
30 Oct 2025, 6:00 pmClosed
Col Amit Bhardwaj
MES, HQ CWE Jammu PIN-180003
PROVN OF WATER SUPPLY AND AUGMENTATION AT SUNJUWAN MIL STN UNDER GE JAMMU
2025_MES_725049_2
CWE/JP-32/2025-26
Open Tender
Civil Works - Others
Item Rate
270 days
GE Jammu
As per tender docus
9 documents required · 9 mandatory
₹1,000
GE Jammu
₹3.5 L
Yes
3 Dec 2025
9 Oct 2025
1 Nov 2025
9 Oct 2025
30 Oct 2025
23 Oct 2025
9 Oct 2025 - 12 Oct 2025
Drilling of Trail Bore Hole 300mm (12 inch) dia from ground level to 200 meter in any strata by ROTARY METHOD method as per IS : 2800 1979 (revised and amended) below ground level through any kind of strata soils/rocks, disposal of surplus soil within a distance of 100m, well rammming and stablizing of material , transportation of drilling Rig and other T&P required, keeping space for pea gravel packing in and including lowering and extraction of casing pipes of suitable thickness after lowering of designed assemble of EWR pipe, complete all as specified and as directed Engr-in-Charge.
(B) ENGINE INSTRUCTONS PANEL : All relevant information of lubricant, oil pressure, battery charging, ammeter hours meter starting switch (C) FUEL TANK: In built tank of adequate capacity with stop cock drain plug and necessary fuel pipe complete as per manufacture recommendations. (D) ALTERNATOR 58.5 KVA, 415 volts AT NTP, 3 phase, 50 Hz, 415 volts AC supply 0.8 PF at 1500 RPM, this shall be self excited scren protected and dip proof type brushless conforming to relevent IS/BIS code per latest manufacturing schedule. (E) CONTROL PANEL : The standard control shall be built in acoustic enclosures with the following accessories complete wire with suitable size of copper cables:- (i) MCCB of suitable rating with overload ans short curcuit protection. (ii) Digital ammeter (iii) Digital voltmeter. (iv) One set of indication LED lamps RYB and fuse. (v) Frequency meter, RPM meter, Hour, fuel level indicator.
The contractor has to submit the test result/report as per IS:2800(Part-II -1979(with amendment) as following:- (a) Results of the tubewell depth and water level measurements. (b)Results of development and drawdown test are to be given in tabular form as per relevant IS. (c) The vertically test report shall be given as per the relevant IS. (d). The Housing/ Casing pipe shall be inserted only after certificate given by GE for sucessful trial bore hole.
(vi) KWH meter electronic tamper proof digital for 3 phase 415 volts AC unbalanced load of suitable capacity. (vii) Water temperature il pressure guage Note : The gen set must be fixed with label meeting the following requirements (The label shall be durable and legible):- (i) Name and address of the engine manufacturer. (ii) Statement that this engine conforms to the environment protections. (iii) Type and approval certificate number. (iv) Date of manufacture of DG set.
Supplying, assembling including lowering and fixing liner assembly or strainer etc in position (net affective length shall only measured and paid) all as specified below.
Mild steel ERW bevelled end pipe 300mm (12 inch) nominal bore having min 8 mm wall thickness confirming to IS:4270-2001 and all around welded with 03 Nos stiffeners of flat iron 75x8mm, 150 mm long, complete all as specified and as directed Engr-in-Charge.
(b) ENGINE INSTRUCTONS PANEL : All relevant information of lubricant, oil pressure, battery charging, ammeter hours meter, starting switch ( c) FUEL TANK: In built tank of adequate capacity with stop cock drain plug and necessary fuel pipe complete as per manufacturer recommendations. (d) ALTERNATOR 160 KVA, 415 volts AT NTP, 3 phase, 50 Hz, 415 volts AC supply 08 PF at 1500 RPM, this shall be self excited screen protected and drip proof type brushless conforming to relevent IS/BLS code per latest manufactureing schedule. (e) CONTROL PANEL The standard control shall be built in acoustic enclosures with the following accessories complete wire with suitable size of copper cables:- (i) MCCB of suitable rating with overload ans short curcuit protection (ii) Digital ammeter (i)Digital voltmeter. (iv) One set of indication LED lamps RYB and fuse. (v)Frequency meter, RPM meter, Hour, fuel level indicator. (vi)KWH meter electronic tamper proof digital for 3 phase 415 volts AC unbalanced load of siutable capacity (v) Water tempertature oil pressure guage
Mild steel ERW bevelled end pipe 200mm (08 inch) nominal bore having min 8 mm wall thickness confirming to IS:4270-2001 and all around welded with 03 Nos stiffeners of flat iron 75x8mm, 150 mm long, complete all as specified and as directed Engr-in-Charge.
Housing pipe clamps made of MS flat of size 100 mmx 12mm and 750mm long for 300mm (12 inch) bore pipe with suitable bolts, nuts and washers, complete all as specified and as directed Engr-in-Charge.
Mild steel ERW bevelled endslotted housing pipe nominal bore 200mm (12 inch) nominal bore having min 8 mm wall thickness confirming to IS:4270-2001 having slot size of 1.6mm x75mm as per (IS:8110:2000) and all around welded with 03 Nos stiffeners of flat iron 75x8mm, 150 mm long, complete all as specified and as directed Engr-in-Charge.
Supply and fixing Mild Steel Well Cap for (12 inch) 300mm bore made out of mild steel ERW 8mm thick threaded casing pipe, complete all as specified and as directed Engr-in-Charge.
Development of Tube Well by means of pumping by Air compressor of minimum pressure 1400 CFM 350 Psi.(Compressor to be arranged by contractor at his own cost), until sand free and clear water upto 5 PPM is obtained at optimum yield, complete all as specified and as directed Engr-in-Charge:-
(vi) KWH meter electronic tamper proof digital for 3 phase 415 volts AC unbalanced load of suitable capacity. (vii) Water temperature il pressure guage Note : The gen set must be fixed with label meeting the following requirements (The label shall be durable and legible):- (i) Name and address of the engine manufacturer. (ii) Statement that this engine conforms to the environment protections. (iii) Type and approval certificate number. (iv) Date of manufacture of DG set.
Supplying Strata sample box made of Ist class soft wood (Deodar) with glazed shutter and pigeon holes for depth dsample at the interval of every 3 meters and supplying of strata chart duly marked on 3 mm thick laminated sheet of size 4 inch x 3 inch giving complete details of display of installation, complete all as specified and as directed Engr-in-Charge.
Supply and filling Pea gravel of Size 2mm to 6mm around the liner assembly from bottom to ground level including continous watering during development, complete all as specified and as directed Engr-in-Charge.
Flat Iron of size 50 x 6mm as centre guides of required size including welding to casing pipe, complete all as specified and as directed Engr-in-Charge.
Supply and fixing MS 200 mm(08 Inch) bail plug having minimum thickness 8 mm all as per IS: 2800;1991 (With latest amendments), complete all as specified and as directed Engr-in-Charge.
M&L for welding of reducer of MS pipe of thickness 8 mm amd size 300mmx200mm and approximate length 1mtr, complete all as specified and as directed Engr-in-Charge.
Supply and fixing cast iron rising sluice valve both end flanged class PN 1.6 conforming to IS-14846-2000 with iron wheel head and brass spindle including necessary joint with nuts, bolt, washer, rubber or fiber board gasket, etc and testing complete all as specified and as directed complete suitable for the following bore of pipes: -
150 mm (6") dia
300 mm (12") dia
Supply and fixing cast iron non return valve both end flanged including joint with nut, bolt, washers, rubber or fiber board gasket, etc testing complete all as specified and as directed complete suitable for the following bore of pipes: -
(a) 150 mm (6") dia
(b) 300 mm (12") dia
Construction of foundation of Tube well of size 1.0 m x 1.0m having minimum 45 mm thick PCC 1:3:4 type B-1 (using 20mm graded crushed stones aggregate) laid over 75 mm thick PCC 1:3:6 type C-2 with GI pipe 80mm bore medium grade-02 Nos embedded through out the block of suitable length with GI plug and socket fixed on end, complete all as specified and as directed Engr-in-Charge.
Supply and laying mild steel black pipe P/E ISI marked conforming to IS : 1239 PART - 1 (2004) of 150 mm dia bore medium grade ('B' Class) with flanged joints at both ends fixed with rubber or fiber board gaskets with suitable size and number of nuts, bolts, and washers as per site requirement in trenches, on ground or on the support above ground level by continuous welding joints 15mm thick flange joint and testing complete duly painted with two coats of bituminuous paint externally, complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing Common header of cylindrical shape flat closed ends , Cylinder length as 4 mtrs and Dia 600mm closed on both ends , with 07 nos of flanged pipes of 150mm dia inserted on side of cylindrical length as inlets , and 01 No of 300mm dia flanged pipe on other side of cylindrical length as outlet . Cylinder made out of 600mm dia MS pipe heavy grade, complete all as specified and as directed by Engineer-in-Charge.
Material and labour for MS fittings Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugsupto 150 mm bore pipe, complete all as specified and as directed by Engineer-in-Charge.
Material and labour for MS fittings Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugsupto 300 mm bore pipe, complete all as specified and as directed by Engineer-in-Charge.
Material and labour for welding /cutting existing pipe work for CI/DI/MS pipe of dia 150 to 300 mm at tapping point and jointing pipe and fixing the pipe with new pipe of existing di , complete all as specified and as directed by Engineer-in-Charge. Note :- Rates are dumed to be including hiring of T&P required at site.
Supply installation, commissioning and testing of ECO friendly silent diesel engine driven water cooled generating set of capacity 400 KVA, 415 volts, AC supply, 50 Hz, 3 phase, 4 wire, 0.8 PF at NPT, speed 1500 RPM mounted on common base plat with flexible couping and meeting the requirements of IS-4722/BIS, IS 13364 specification with CPCB IV+ approved accoustic enclosures fabricated out of CRCA sheet metal base frame sound proofing of enclosure is done with high quality toam conforming to IS 8183 of 25mm thickness and density 30 Kg/m" complete inclufding PCC foundation is all respect complete as per manufacturer recommendations with following specifications: (a) DIESEL ENGINE : Water cooled diesel engine of adequate capcity at 1500 RPM generally in accordance with latest BIS/IS specification provided with blower fan 12 volts sefl starting including maintenance free battery of suitable capacity, charging dynamo/alternator, air cleaner, diesel /oil filters complete in all respect. The engine shall be capacity shall be capable of taking 10% overload for one hour for every 12 hours of running conforming to the environment (protection act 1986) (29 of 1986) and as amended vide Gazette of india Notifications Part-il Section-II Section-III sub Section (1) sub Section (1) dated 12 Jul 2004
Supply and fixing fully automatic star delta motor starter in sheet steel enclosure type MUG 20 FASD with single phase protection feature and motor rating AC-3 duty, 415 volt, 50 Hz, 3 phase suitable for up to 10 HP motor pump set, complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing 10 sqmm 3 core submersible pump flat cables for submersible pumpset 10 HP capacity, complete all as specified and as directed by Engineer-in-Charge.
Supply , installation , Testing & commissioning of Horizontal split case Centrifugal pumpset with 1900 LPM discharge and 75mtrs head , 60HP/45KW motor , 415 V, complete all as specified and as directed by Engineer-in-Charge.
Supply and laying mild steel black pipe P/E ISI marked conforming to IS 3589 (1981) of 300 mm dia bore,with flanged joints at both ends fixed with rubber or fiber board gaskets with suitable size and number of nuts, bolts, and washers as per site requirement in trenches, on ground or on the support above ground level by continuous welding joints 15mm thick flange joint and testing complete duly painted with two coats of bituminuous paint externally, complete all as specified and as directed by Engineer-in-Charge.
Supply and fix Lifting tripod for Lowering/Lifting of submersible pumps with inbuilt Chain pulley system Loading capacity upto 10 Tonnes height 3 mtrs, complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing MS heavy duty ISI marked column pipe 100mm bore 3 mtr long both ends flanged of flange thickness 10 to 12 mm including pre-built holes of suitable numbers to hold pressure of water and pipes along with rubber or fiber board gaskets with suitable size and number of nuts, bolts and washers, complete all as specified and as directed by Engineer-in-Charge.
Flow Meter 150MM bore
Flow Meter 200MM bore
Flow meter 100MM bore
Flow meter 300MM bore
Surface excavation not exc 30 cm deep and averageing 15 cm deep and getting out in any type of soil, complete all as specified and as directed by Engineer-in-Charge.
Cement concrete type C-2, 1:3:6 (using 40 mm graded crushed stone aggregates) in foundation filling and mass concrete, complete all as specified and as directed by Engineer-in-Charge.
Brick work with old size bricks having crushing strength not less than 75 Kg/Sqm, straight or curved on plan exceeding 6 m mean radius with old size bricks built in cement mortar 1 : 4, complete all as specified and as directed by Engineer-in-Charge.
Hard core of gauge not exceeding 63mm, deposited, spread and levelled in layers not exceeding 15cm thick watered and well rammed to a true surface , complete all as specified and as directed by Engineer-in-Charge.
Material and labour for 75 mm thick cement concrete type C-2, 1:3:6 (40mm graded agg) as in Sub-base , complete all as specified and as directed by Engineer-in-Charge.
Rendering 15 mm thick on fair face of brick work or concrete surface in CM 1:4, finished even and smooth without using extra cement , complete all as specified and as directed by Engineer-in-Charge.
Preparing newly plastered or concrete surfaces of wall and applying two coats of cement based paint over a coat of primer, complete all as specified and as directed by Engineer-in-Charge.
Material and labour for 50 mm thick cement concrete 1:2:4, type B2 (using 40mm graded agg) as in plinth protection finished even and smooth using extra cement.(incl necessary joint filling with mixture of paving bitumen & sand in 1:3), complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection, complete all as specified and as directed by Engineer-in-Charge.
Supply, installation, commissioning and testing Servo controlled Voltage stablizer of capacity 25 KVA confirming to BIS 9815 Part-I 1994 3 phase 50 Hz oil cooled indoor unbalanced type copper wound digital display voltmeter/ammeter type, relay pre smooth and silent operation with first fill of transformer oil (IS 335 of 1993) having specification, designed for input voltage variation between 300 V to 480 V with output voltage stablized at 415 with accuracy plus minus 1% and speed of correction 8 volts per second and 20 volts per second for phase to phase, no load losses less than 0.5%, full load losses less than 2.5% duty cycle continuous 24x7, efficiency more than 95% with protection of overload/short circuit protection, high/low voltage cut off by pass arrangement case of emergency, single phase sequence change protection, complete all as specified and as directed by Engineer-in-Charge.
(b) ENGINE INSTRUCTONS PANEL : All relevant information of lubricant, oil pressure, battery charging, ammeter hours meter, starting switch ( c) FUEL TANK: In built tank of adequate capacity with stop cock drain plug and necessary fuel pipe complete as per manufacturer recommendations. (d) ALTERNATOR 400 KVA, 415 volts AT NTP, 3 phase, 50 Hz, 415 volts AC supply 08 PF at 1500 RPM, this shall be self excited screen protected and drip proof type brushless conforming to relevent IS/BLS code per latest manufactureing schedule. (e) CONTROL PANEL The standard control shall be built in acoustic enclosures with the following accessories complete wire with suitable size of copper cables:- (i) MCCB of suitable rating with overload ans short curcuit protection (ii) Digital ammeter (i)Digital voltmeter. (iv) One set of indication LED lamps RYB and fuse. (v)Frequency meter, RPM meter, Hour, fuel level indicator. (vi)KWH meter electronic tamper proof digital for 3 phase 415 volts AC unbalanced load of siutable capacity (v) Water tempertature oil pressure guage
Supply and fixing of flow meter with modbus protocal,Weather proof with protection against,Over voltage .Including complete mechnical work and piping for flow meter consisting of following Valve size :-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm 4 core, complete all as specified and as directed by Engineer-in-Charge.
Supply,laying and testing cable XLPE insulated,screened ,PVC bedded,galvanized steel strip or wire armored,electric power cables(heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 sqmm 3.5 core , complete all as specified and as directed by Engineer-in-Charge.
Supply,laying and testing cable XLPE insulated,screened ,PVC bedded,galvanized steel strip or wire armored,electric power cables(heavy duty) 1100 volts grade with stranded aluminium conductor of size 150 sqmm 3.5 core , complete all as specified and as directed by Engineer-in-Charge.
Supply,laying and testing cable XLPE insulated,screened ,PVC bedded,galvanized steel strip or wire armored,electric power cables(heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm 4 core, complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches n.exc 1.5 m wide and n.exc 1.5 deep for foundations of poles/stays/cable etc. and getting out in hard/dense soil, complete all as specified and as directed by Engineer-in-Charge.
Returning, filling in earth including spreading levelling watering and well ramming in layers each not exceeding 25 cm thick each layer, complete all as specified and as directed by Engineer-in-Charge.
Removing of surplus soil to a distance not exc 50 metre and depositing where directed at a level not exc 1.5 metre above the starting point, complete all as specified and as directed by Engineer-in-Charge.
Material and labour for sand cushioning with a layer of fine sand (sand for plastering) 8 cm thick before laying of cable and 15 cm thick after laying of cable in trenches, complete all as specified and as directed by Engineer-in-Charge.
Supplying and laying reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm, complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to GI strip 32 x 6 mm (up to 7.5 m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no.3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering and pouring extra Clay Soil of qty not less than one cubic meter into the earth pit and also removal of excavated soil not less than 50 mtr from the earthing place, complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core , complete all as specified and as directed by Engineer-in-Charge.
(B) ENGINE INSTRUCTONS PANEL : All relevant information of lubricant, oil pressure, battery charging, ammeter hours meter starting switch (C) FUEL TANK: In built tank of adequate capacity with stop cock drain plug and necessary fuel pipe complete as per manufacture recommendations. (D) ALTERNATOR 25 KVA, 415 volts AT NTP, 3 phase, 50 Hz, 415 volts AC supply 0.8 PF at 1500 RPM, this shall be self excited scren protected and dip proof type brushless conforming to relevent IS/BLS code per latest manufacturing schedule. (E) CONTROL PANEL : The standard control shall be built in acoustic enclosures with the following accessories complete wire with suitable size of copper cables:- (i) MCCB of suitable rating with overload ans short curcuit protection. (ii) Digital ammeter (iii) Digital voltmeter. (iv) On
(iv) Digital voltmeter (0-430V) Accuracy class 0.5 of size 96 X 96 mm -01 Nos (v) Digital Ammeter (0-100 Amps) Accuracy class 0.5 of size 96X96 mm with suitable size of CT'S-01 Nos (vi) LED Pilot lamp RYB - Set of 3
Supply installation, commissioning and testing of ECO fiendly silent diesel engine driven water cooled generating set of capacity 58.5 KVA, 415 volts. AC supply 50 Hz. 3 phase, 4 wire, 0.8 PF at NPT, speed 150 RPM mounted on common base plain flexible couping and meeting the requirements of IS-4722/BIS, IS 13364 specification with CPCB IV approved accoustic enclosures fabricated out of CRCA sheet metal base frame sound proofing of enclosure is done with high quality foam conforming to IS 8183 of 25mm thickness and density 30 Kg/m" complete inclufding PCC foundation is all respect complete as per manufacturer recommendations with following specifications- (a) DIESSEL ENGINE : Water cooled diesel engine of adequate capcity at 1500 RPM generally in accordance with latest BIS/IS specfication provided with blower fan 12 volts sefl starting including maintenance free battery of suitable capacity, charging dyamo/alternator, air cleaner, diesel /oil filters complete in all respect. The engine shall be capacity shall be capable of taking 10% overtoad for one hour for every 12 hours of running conforming to the environment (protection act 1986) (29 of 1986) and as amended vide Gazette of india Notifications Part-II Section-II Section-III sub Section (1) sub Section (1) dated 12 Jul 2004
Supply, Install, testing and commissioning of Submersible pumpset,electric driven, 415 V , Three phase, suitable for 200mm dia bore well, casing pipe size 300mm of 10 HP (6WHP) capacity , 7.5 KW with head range 77mtrs , 300 LPM, complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing Factory made LT feeder pillar box type AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, cubical indoor type powder coated , CPRI Approved , bottom with detachable plates, front and rear with hinged type double door and locking arrangements, chamber for cable entry and exit, chamber for copper bus bars including aluminium bus bars 4 Nos, 100 amps capacity insulated with colored PVC sleeves, floor mounted on frame of mild steel angle iron 25 x 25 x 5mm, 30Cm above from the ground level duly supported with mild steel angle iron, embedded in Plain Cement Concrete M-10 (1:3:6), type C-1 (using 20mm graded crushed stone aggregates) 300mm below the ground level and required masonry in brick work in cement mortar 1:6 incl offsets all as per manufacturer's instructions and incl suitable insulators and separators, holes drilled for connections, complete all as specified and comprising of the following : (i) MCCB 100 amps adjustable type capacity , 16 KA 4P, 415 V - 01 No ( Incoming) (ii) MCCB 63 amps adjustable type capacity , 16 KA 4P, 415 V - 01 No ( Incoming) (iii) MCB SPN 10 Amps, 10 KA-01 Nos
Supply installation, commissioning and testing of ECO friendly silent diesel engine driven water cooled generating set of capacity 25 KVA, 415 volts. AC supply 50 Hz. 3 phase, 4 wire, 0.8 PF at NPT, speed 150 RPM mounted on common base plain flexible couping and meeting the requirements of IS-4722/BIS, IS 13364 specification with CPCB IV approved accoustic enclosures fabricated out of CRCA sheet metal base frame sound proofing of enclosure is done with high quality foam conforming to IS 8183 of 25mm thickness and density 30 Kg/m" complete inclufding PCC foundation is all respect complete as per manufacturer recommendations with following specifications- (a) DIESSEL ENGINE : Water cooled diesel engine of adequate capcity at 1500 RPM generally in accordance with latest BIS/IS specfication provided with blower fan 12 volts sefl starting including maintenance free battery of suitable capacity, charging dyamo/alternator, air cleaner, diesel /oil filters complete in all respect. The engine shall be capacity shall be capable of taking 10% overtoad for one hour for every 12 hours of running conforming to the environment (protection act 1986) (29 of 1986) and as amended vide Gazette of india Notifications Part-II Section-II Section-III sub Section (1) sub Section (1) dated 12 Jul 2004
Supply installation, commissioning and testing of ECO friendly silent diesel engine driven water cooled generating set of capacity 100 KVA, 415 volts. AC supply 50 Hz. 3 phase, 4 wire, 0.8 PF at NPT, speed 1500 RPM mounted on common base plain flexible couping and meeting the requirements of IS-4722/BIS, IS 13364 specification with CPCB IV approved accoustic enclosures fabricated out of CRCA sheet metal base frame sound proofing of enclosure is done with high quality foam conforming to IS 8183 of 25mm thickness and density 30 Kg/m" complete inclufding PCC foundation is all respect complete as per manufacturer recommendations with following specifications- (a) DIESSEL ENGINE : Water cooled diesel engine of adequate capcity at 1500 RPM generally in accordance with latest BIS/IS specfication provided with blower fan 12 volts sefl starting including maintenance free battery of suitable capacity, charging dyamo/alternator, air cleaner, diesel /oil filters complete in all respect. The engine shall be capacity shall be capable of taking 10% overtoad for one hour for every 12 hours of running conforming to the environment (protection act 1986) (29 of 1986) and as amended vide Gazette of india Notifications Part-II Section-II Section-III sub Section (1) sub Section (1) dated 12 Jul 2004
(B) ENGINE INSTRUCTONS PANEL : All relevant information of lubricant, oil pressure, battery charging, ammeter hours meter starting switch (C) FUEL TANK: In built tank of adequate capacity with stop cock drain plug and necessary fuel pipe complete as per manufacture recommendations. (D) ALTERNAT
OR 100 KVA, 415 volts AT NTP, 3 phase, 50 Hz, 415 volts AC supply 0.8 PF at 1500 RPM, this shall be self excited screen protected and dip proof type brushless conforming to relevent IS/BIS code per latest manufacturing schedule. (E) CONTROL PANEL : The standard control shall be built in acoustic enclosures with the following accessories complete wire with suitable size of copper cables:- (i) MCCB of suitable rating with overload ans short curcuit protection. (ii) Digital ammeter (iii) Digital voltmeter. (iv) One set of indication LED lamps RYB and fuse. (v) Frequency meter, RPM meter, Hour, fuel level indicator.
e set of indication LED lamps RYB and fuse. (v) Frequency meter, RPM meter, Hour, fuel level indicator.
(vi) KWH meter electronic tamper proof digital for 3 phase 415 volts AC unbalanced load of suitable capacity. (vii) Water temperature oil pressure gauge. Note : The gen set must be fixed with label meeting the following requirements (The label shall be durable and legible):- (i) Name and address of the engine manufacturer. (ii) Statement that this engine conforms to the environment protections. (iii) Type and approval certificate number. (iv) Date of manufacture of DG set.
Supply installation, commissioning and testing of ECO friendly silent diesel engine driven water cooled generating set of capacity 160 KVA, 415 volts, AC supply, 50 Hz, 3 phase, 4 wire, 0.8 PF at NPT, speed 1500 RPM mounted on common base plat with flexible couping and meeting the requirements of IS-4722/BIS, IS 13364 specification with CPCB IV+ approved accoustic enclosures fabricated out of CRCA sheet metal base frame sound proofing of enclosure is done with high quality toam conforming to IS 8183 of 25mm thickness and density 30 Kg/m" complete inclufding PCC foundation is all respect complete as per manufacturer recommendations with following specifications: (a) DIESEL ENGINE : Water cooled diesel engine of adequate capcity at 1500 RPM generally in accordance with latest BIS/IS specification provided with blower fan 12 volts sefl starting including maintenance free battery of suitable capacity, charging dynamo/alternator, air cleaner, diesel /oil filters complete in all respect. The engine shall be capacity shall be capable of taking 10% overload for one hour for every 12 hours of running conforming to the environment (protection act 1986) (29 of 1986) and as amended vide Gazette of india Notifications Part-il Section-II Section-III sub Section (1) sub Section (1) dated 12 Jul 2004
Note : The gen set must be fixed with label meeting the following requirements (The label shall be durable and legible):- (i) Name and address of the engine manufacturer. (ii) Statement that this engine conforms to the environment protections. (iii) Type and approval certificate number. (iv) Date of manufacture of DG set.
(vi) KWH meter electronic tamper proof digital for 3 phase 415 volts AC unbalanced load of suitable capacity. (vii) Water temperature oil pressure gauge. Note : The gen set must be fixed with label meeting the following requirements (The label shall be durable and legible):- (i) Name and address of the engine manufacturer. (ii) Statement that this engine conforms to the environment protections. (iii) Type and approval certificate number. (iv) Date of manufacture of DG set.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
Tender32_merged.pdf
Tender Documents • 2.00 MB
BOQ_822309.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .