| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.5 LAccepted-AOC | L1 | Accepted-AOC Lowest of Quoted Rates | |
| 2 | L2₹27.0 L+₹49,987.10 (1.89%)Rejected-Finance | L2 | Rejected-Finance High Rates | |
| 3 | L3₹27.2 L+₹74,112.10 (2.80%)Rejected-Finance | L3 | Rejected-Finance High Rates | |
| 4 | L4₹28.1 L+₹1.6 L (6.10%)Rejected-Finance 10 2 NARAYAN BAG INDORE M P | L4 | Rejected-Finance High Rates | |
| 5 | L5₹28.4 L+₹2.0 L (7.38%)Rejected-Finance | L5 | Rejected-Finance High Rates |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
26 Sept 2020, 6:00 pmClosed
GE (MCTE) MHOW
GE (MCTE) MHOW MP 453441
MISCELLANEOUS E/M INSTALLATION WORKS AND RENEWAL OF OLD EARTHING AND OTHER CONNECTED WORK UNDER GE MCTE MHOW
2020_MES_373217_1
GE(MCTE)/MHOW/21(T) OF 2020-21
Open Tender
Electrical and Maintenance Works
Works
180 days
GE (MCTE) MHOW
AS PER TENDER DOCUMENT
8 documents required · 8 mandatory
₹500
Yes
GE (MCTE) MHOW
₹70,000
Yes
13 Oct 2020
29 Aug 2020
28 Sept 2020
29 Aug 2020
26 Sept 2020
13 Sept 2020
Amount
Disconnection of electric connection from DG set of any description and in any position, for servicing, taking out & removing unserviceable/defective parts/spares, cleaning, servicing, oiling and greasing of necessary parts, refixing the serviceable parts in position after servicing, replacement of unserviceable parts including draining-out of existing engine oil and filling new engine oil of same grade and filters, refixing of all accessories and testing on full load complete all as specified and directed for following capacity of DG sets :-
(a) 30 KVA to 63 KVA 3 phase 50 Hz
(b) 100 KVA to 180 KVA 3 phase 50 HZ
(c) 200 KVA, 3 phase 50 HZ
NOTE for Srl item No 1.00 : (i) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under relevent items of Sch 'A’ as Supply only to the extent covered under the relevent supply only items here-in- after but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers, locking nuts, small springs, screws/gaskets/ packing /studs etc. (ii) Engine oil shall be drained out carefully, collected by the contractor in his own suitable containers and stored properly for checking serviceability including cleaning of oil sump by pouring kerosene oil all as directed by the Engineer-in-Charge. (iii) Fresh engine oil replaced for DG sets shall be supply and filling by the contractor and shall be measured and paid separately under relevent item of Sch ‘A’ . However, cost of filling is deemed to be included under the rates quoted by the contractor for above item.
Supply only the following parts of DG set of cap 30 KVA :-
(a) Fuel filter element. Make : BOCH / MICO
(b) Oil Filter element . Make : BOCH / MICO
(c) Air Filter . Make : KIRLOSKAR/ FILGOLD
(d) By pass filter . Make : BOCH / MICO
(e) Fan belt . Make : FARAL / KIRLOSKAR
(f) Radiator hose pipe of suitable size. Make : KIRLOSKAR
Supply only the following parts of DG set of 100 KVA to 160 KVA capacity :-
(a) Fuel filter element. Make : BOCH / MICO
(b) Oil Filter element . Make : BOCH / MICO
(c) Air Filter . Make : KIRLOSKAR/ FILGOLD
(d) By pass filter . Make : BOCH / MICO
(e) Fan belt . Make : FARAL / KIRLOSKAR
(f) Radiator hose pipe of suitable size .Make : KIRLOSKAR
(g) V-belt BX-40 . Make : FIMEX/ FARAL
(h)V-belt AVX 3/1562 . Make : FIMEX/ FARAL
Supply only the following parts of DG set of 200 KVA capacity:-
(a) Fuel filter element . Make : BOCH / MICO
(b) Oil Filter element . Make : BOCH / MICO
(c) Air Filter . Make : KIRLOSKAR/ FILGOLD
(d) By pass filter . Make : BOCH / MICO
(e) Fan belt . Make : FARAL / KIRLOSKAR
(f) Radiator hose pipe of suitable size . Make : KIRLOSKAR
Supply and filling coolant for DG set of any capacity all as specified and directed. Make : GULF / MICO /Castrol
Supply and filling engine oil of DG set of grade 20 W 40. Make :- Servo, Veedol & elf
Checking/Servicing of DG Set battery 12 volt, 92/ 180 AH cleaning of battery terminals by hot water and applying petrolium jelly over battery terminals, water level checking including topping up with distilled water complete all as specified and directed ( Note - Bettery terminal, Battery cable and distilled water will be measured and paid separatly)
Supply and fixing following items for battery 92/180 AH 12 Volts :-
(a) Heavy duty brass battery terminal
(b) Battery lead 70 Sqmm multistandard, single core, copper conductor
(c) Distilled Water of approved make
Taking down radiator assy of DG set of capacity 30 KVA to 63 KVA from engine mounting by opening water hose and nut bolt cleaning of radiator inside and out side with anti rust solution, checking the radiator by filling water and repairing for any leakage by brazing the radiator and ensure for no leakage Re- fixing the radiator at place including transportation for repair to workshop or site all as directed.
Dismantling the fuel injection pump from engine block of DG set of 30 KVA to 63 KVA disconnecting all fuel inlet and outlet lines, disconnecting the drive for carrying out repairs/ replacements including calibration, re assambling of FIP and fixing back in position after repair / replacement of unserviceable parts all as directed. Note :- 1. Calibration of FIP complete shall be got done from manufacturer authorized dealer / workshop to entire satisfaction of Engineer- in- charge. 2. Shifting and loading/Unloading of FIP and transporting for repair in workshop at Indore city from MCTE Area Mhow is including in deemed rate.
Taking down unserviceable self starter 12 Volts for DG sets, servicing and replacement of old carbon brushes, bearing and contact blades etc and refixing after servicing and replacement of unsv parts. (NOTE : Bearing of alternator will be measured and paid separately)
Taking down unserviceable self starter 24 Volts for DG sets, serviceing and replacement of old carbon brushes, bearing and contact blades etc and refixing after servicing and replacement of unsv parts. (NOTE : Bearing of alternator will be measured and paid separately).
Taking down unserviceable alternator suitable for 12 Volts for DG sets, serviceing and replacement of old carbon brushes, bearing and contact blades etc and refixing after servicing and replacement of unsv parts. (NOTE : Bearing of alternator will be measured and paid separately)
Taking down unserviceable alternator suitable for 24 Volts for DG sets, serviceing and replacement of old carbon brushes, bearing and contact blades etc and refixing after servicing and replacement of unsv parts. (NOTE : Bearing of alternator will be measured and paid separately)
Dismantling the fuel injection pump from engine block of DG set of 100 KVA to 180 KVA disconnecting all fuel inlet and outlet lines, disconnecting the drive for carrying out repairs/ replacements including calibration, re assambling of FIP and fixing back in position after repair / replacement of unserviceable parts all as directed. Note :- 1. Calibration of FIP complete shall be got done from manufacturer authorized dealer / workshop to entire satisfaction of Engineer- in- charge. 2. Shifting and loading/Unloading of FIP and transporting for repair in workshop at Indore city from MCTE Area Mhow is including in deemed rate.
Supply and fixing following unserviceable parts of 100 KVA to 180 KVA capacity are as under :-
(a) Nozzle plunger Make : BOCH Cat part No. 63104
(b) Delivery valves. Make : BOCH
(c) Injector holder with washers. Make : BOCH
(d) Injector . Make : BOCH
(e) FIP packing Kit. Make : BOCH
(f) Bearing number 30203 or suitable matching number Make : NBC/SKF
(g) Bearing number 6203 or suitable matching number Make : NBC/SKF
Repair/replacement of engine control panel UNSV parts as under :-
(a) Oil Pressure Gauge as per approved Make
(b) Oil Temprature Gauge as per approved Make
(c) Hours meter as per approved Make
(d) Ampere meter as per approved Make
(e) Volt meter as per approved Make
(f) Key starter as per approved Make
Taking down radiator assembly from engine mounting by opening water hoses & nut bolt, Cleaning of radiator from inside and outside with anti rust solution, Checking the radiator by filling water and repairing for any leakage by brazing the radiator and ensure for no leakage. refixing the radiator at place including water hoses and replacement of following parts for 100 KVA to 180 KVA capacity DG set (Kirlosker) Note:- Unserviceable parts shall be measured and paid seperately under respective items. Transportation cost included in unit quoted rate.
Disconnecting / taking down unserviceable alternator armature from DG set 100 to 180 KVA capacity and transport to civil workshop by civil vehicle opening the same and taking out by cutting burnt winding wire complete rewinding with super enamelled copper winding wire of existing gauge, insulating material, warnishing, finishing and connecting at its position, testing & commissioning of DG set to the entire satisfaction of Engr-in-Charge
Taking down old turbo charger assembly from engine mounting by opening nut, bolt and transporting to civil workshop for repairing,cleaning and servicing from inside and outside with anti rust solution, checking the same and repairing for any leakage by brazing the turbo charger and ensure for no leakage. Refixing the turbo charger at same place of 30 KVA to 63 KVA capacity DG set. Note:- Transportation cost included in unit quoted rate.
All as above item No 20 but 100 KVA to 180 KVA capacity DG set.
All as above item No 20 but 200 KVA capacity DG set.
Taking down old unserviceable PVC coolant makeup bottle of cap 3.5 Ltr suitable for 30 KVA DG set.
Taking down old unserviceable PVC coolant makeup bottle of cap 6.5 Ltr suitable for 100 KVA to 180 KVA DG set
Taking down old unserviceable and replace with new self starter suitable for 100 KVA to 180 KVA DG Set, 24 Volts. Make : Lucas/ Auto/ LAK.
Taking down old unserviceable water temp sensor and replace with new suitable for DG set of cap 30 KVA to 180 KVA as per sample.
Taking down old unserviceable oil temp sensor and replace with new suitable for DG set of cap 30 KVA to 180 KVA as per sample.
Supply and fixing of rear bearing of alternator capacity 200 KVA DG Set.
S&F in replacement of DG Set battery 12 volt, 180 AH as existing for 100/160/200 KVA DG set capacity. Make : Exide
S&F in replacement of existing AVR (Automatic Voltage Regulator) unit to match the existing AVR unit suitable for 100 to 200KVA DG Set including taking down of old one.
M&L of earthing complete with GI steel earth plate electrode 60cm x 60cmx6.0mm thick barried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 mtrs below level ground, connected to GI strip 32x6mm by means of nuts, bolts checks nuts and washers made of GI earth wire protected by GI pipe 40mm bore, medium grade and connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1 using 20mm graded aggregate, pre-cast RCC (1:2:4) type-B, over slab 30cmx30cmx10cm with one lifting handle made of 8mm dia MS bar funnel wire mesh, 20mm bore GI or steel pipe medium grade for watering, charcoal or coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical plate No 3 of MES schedule Part-I and testing after completion.
M&L for cable jointing kit for 1.1 KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core LT XLPE armoured aluminium conductor cable of size 16 to 50 sqmm. Make : 3 M/ Denson/M-Seal.
M&L for cable jointing kit for 1.1 KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core LT XLPE armoured aluminium conductor cable of size 70 to 240 sqmm. Make : 3 M/ Denson/M-Seal.
S&F in replacement of ON Load Change over switch of 100 Amps capacity 415 Volts, incl sheet metal enclosure as per the existing switch including taking out old unserviceable one. Make: C&S/ Indo Asian / Hevells or equivalent.
All as per Srl item No 35.00 above but 200 Amps capacity.
Excavation in trenches not exc. 1.5m wide and not exc 1.5m deep in any type of soil for cables and getting out complete all as specified and directed.
All as per Srl item No 38.00 above, but depth exc 1.5m and not exc 3.0m deep.
Returning filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in any type of soil complete all as specified and directed.
Removing of surplus excavated material (soil) to a distance not exc 50m and depositing where directed at a level not exc 1.50m above the starting point complete all as specified and directed.
M&L for filling approved fine river sand in trenches as cable cushion to the full width of excavated trench , under and over cable complete all as specified and as directed. Note : Punned thickness of sand shall be measured
M&L for bricks slightly over burnt (kiln burnt) , modular bricks , best quality, locally available , laid flat, dry, laid in trenches along the length of cable transvarsally with width equal to length of brick for cable protection all as specified and as directed.
S&F, in replacement of GI tubing, light grade, 100 mm bore pipe laid in trenches/duct or in road crossing or fixed to wall/poles for protection of cable incl taking out old pipe of any grade complete all as specified and directed.
All as per Srl item No 44.00 above but 80 mm bore pipe.
All as per Srl item No 44.00 above but 50 mm bore pipe.
All as per Srl item No 44.00 above but 40 mm bore pipe.
Supply and spreading graded stone aggregate of size 40 mm in transformer/RMU/TOP-I yard uniformally to any depth and levelling complete all as specified and directed.
S&F, in repair for MS structrual steel work as in cross arms, bracings, supports, clamps and back plates etc fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for fixing insulators and painting with aluminium paint in two coats over one coat of red oxide zinc chrome primer complete including taking down old unserviceable old one all as specified and directed.
M&L for painting to old chain link fencing and steel sections post with two coats aluminum paint over a coat of aluminium red-oxide complete including preparation of old steel or iron surfaces all as specfied and directed.
S&F in replacement of 1100 volts grade duty cable with PVC insulated aluminium conductor served with an inner sherthing of PVC tape overall PVC sheathed cable size 4 mm twin core flat/circular cable including dismantling of old cable.
All as per item above but 6 Sqmm 2 core
Supply & Laying XLPE insulated, armoured, electric cable with aluminium conductor, 1100 volts grade, laid in trenches, fixed on poles / walls or passing through pipes including provision of necessary lugs and glands & making necessary connection complete all as specified and directed, of the following size:-
(a) 10 Sqmm 2 core.
(b) 16 Sqmm 2 core
(c ) 16 sqmm 4 core
(d) 25 Sqmm 3.5 core
(e) 35 Sqmm 3.5 core
(f) 50 Sqmm 3.5 core
(g) 70 Sqmm 3.5 core
(h) 95 Sqmm 3.5 core
(j) 120 Sqmm 3.5 core
(k) 150 Sqmm 3.5 core
(l) 185 Sqmm 3.5 core
(m) 240 Sqmm 3.5 core
Supply and fixing in repair/replace of MCCB, 63 Amp, 3 Pole, 415 V, 16 KA, rupturing capacity, thermomagnetic fixed type complete all as specified and directed including taking down old unserviceable MCCB any make as specified and directed. Make :- Indo Asian/Havells/Legrand/ABB/L&T
All as above but for 100 Amps, 16 KA.
All as above but for 125 Amps, 16 KA.
All as above but 160 Amps breaking capacity 16 KA rating with thermal relay.
All as above but 200 Amps capacity 25 KA rating with thermal relay.
All as above but 250 Amps capacity 36 KA rating with thermal relay.
All as above but 320 Amps capacity 36 KA rating with thermal relay.
All as above but 400 Amps capacity 36 KA rating with thermal relay.
Supply and fixing MCCB, 63 Amp, 4 Pole, 415 V, 16 KA, rupturing capacity, thermomagnetic fixed type complete all as specified and directed including taking down old unserviceable MCCB any make as specified and directed. Make :- Indo Asian/Havells/Legrand/ABB/L&T
S&F inverter, 900VA, suitable to operate on 100 to 290 volts, AC, 50 Hz with battery 180AH (minimum backup for 5 hours on 300 watt load) and mounted cabinet complete all as specified and directed. Make : Microtek. Make of Battery : Exide
S&F in repairs/replacement of Automatic Street Light control switch for 3 phase load of 5 KW, using Infrared Sensor based NATURE SWITCH for automatic switching of street lights. Nature Switch operation should be based on Natural Light Lux level. Required illuminance level for switching ON is ≤ 30 Lux and for switching OFF ≥ 10 Lux. The sensor should also have part night operation facility of min. 4 hrs to max. 12 hrs. The Sensor along with 03 Nos contactors each of 20 to 25 Amps capacity, Incoming MCBs and Outgoing MCBs of 20-25 Amps (03 Nos) and auto manual operation (Senser by Pass), size of circuit wiring should be multistranded FRLS min size of 10 Sqmm should be enclosed in a pole/wall mounted enclosure made of rust proof, Electric shock Proof, Termite proof and FR grade SMc Junction box conforming to IP54 and model Swadeep 02EC5KW3P complete all as specified and directed. (Make : Nature Switch - Kakatiya Energy systems/Bajaj/Healer (ii) Contactor - BCH/L&T/Schneider (iii) MCB -L&T/ Schneider/HAGER
All as per item No-29 above but for single phase model 02EC5kW1P including Sensor along with 01 Nos contactors 25 to 40 Amps capacity, Incoming MCBs and Outgoing MCBs of 25 to 40 Amps (01 Nos). (Make : Nature Switch - Kakatiya Energy systems/Bajaj/Healer (ii) Contactor - BCH/L&T/Schneider (iii) MCB -L&T/ Schneider/HAGER
S&F in replacement of Single phase Timer Contactor 16 Amps capacity as specified and directed including taking down old one. Make : L&T (MU Series)/Schneider/Legrand
S&F in replacement of Single phase Timer Contactor 25 Amps capacity as specified and directed including taking down old one. Make : L&T (MU Series)/Schneider/Legrand
S&F in replacement of Three phase Timer Contactor 16 Amps per phase capacity as specified and directed including taking down old one. Make : L&T (MU Series)/Schneider/Legrand
S&F in replacement of Three phase Timer Contactor 25 Amps per phase capacity as specified and directed including taking down old one. Make : L&T (MU Series)/Schneider/Legrand
S&F Timer switch with sensor alongwith pre-dawn switching off timer, 4-8 Hrs (nature switch) three phase, confirms to IP 64 degree of protection all as specified and directed. Make- Kakatiya Energy Systems Ltd. Model No - Nature switch-02
Supply and fixing in repair/replacement of Power Contactors AC1 315 Amps and AC3 225 Amps, 4 pole as per existing including dismantling of old one. Make : TC LC1FDP 2254A or equivalent to make L&T/Indoasian
Supply and fixing in repair/replacement of Power Contactors, power contact 4 Nos, rating AC1 250A and AC3 150 Amps, 4 pole as per existing including dismantling of old one. Make : TC LC1FDP 2254A or equivalent to make L&T/Indoasian
Supply and fixing CT ratio 150/5 for power factor correction unit.
Supply and fixing CT ratio 100/5 for power factor correction unit.
Supply and fixing in repair MCCB confirming to IS 13947(Part II) IEC 947 415V, 3 phase 50 HZ 4 pole 125 Amps breaking capacity 25 KA including taking down old one. Make - Indoasian/Havells/ L&T/HPL/Legrand.
All as above but for 250 Amps, 25 KA.
All as above but for 350 Amps, 35 KA.
All as above but for 400 Amps, 35 KA.
Supply and fixing in replacement of MCB, Single Pole 10-32 Amps, B Series, rapturing capacity 10 KA, 240 volts AC, including dismantling of old one. Make : Legrand/ABB/C&S/Havells/Indoasian
Supply and fixing in replacement of MCB, SPN 10-32 Amps, B Series, rapturing capacity 10 KA, 240 volts AC, including dismantling of old one. Make : Legrand/ABB/C&S/Havells/Indoasian
Supply and fixing in replacement of MCB, Triple Pole 20-32 Amps, C Curved, rapturing capacity 10 KA, 240/415 volts AC, including dismantling of old one. Make : Legrand/ABB/C&S/Havells/Indoasian
Supply and fixing in replacement of MCB, Four Pole 32 Amps, C Curved, rapturing capacity 10 KA, 240/415 volts AC, including dismantling of old one. Make : Legrand/ABB/C&S/Havells/Indoasian
Supply and fixing in replacement MCB, Four Pole 40 Amps capacity C Curved, rapturing capacity 10 KA including dismantling of old one. Make : Legrand/ABB/C&S/Havells/Indoasian
Supply and fixing in replacement MCB, Four Pole 63 Amps capacity C Curved, rapturing capacity 10 KA including dismantling of old one. Make : Legrand/ABB/C&S/Havells/Indoasian
Supply and fixing in replacement of sheet moulding compound (SMC) junction box, suitable for terminating 2 Nos 4 x 10/16 Sqmm UG cable, two way connector one nos, including dismantling of old one. Make : Sintex/Finolex/Universal.
Supply and fixing in replacement of Bus bar Chamber with sheet metal enclosure and 04 nos of Aluminium bus bar 200 amps capacity and 415 volts including dismantlting of old bus bar. Make : BENLO/Legrand/C&S/Havells
S&F angle iron fencing post or struts including cutting top to shape as directed, drilling holes, notching for wire etc. flat iron fillets (for securing wire mesh etc) including all necessary drilling bolting or riverting etc and similar work conforming to FE 290 grade complete all as specified and as directed.
Supply only Chain link MS galvanised fencing, any size, complete all as specified and as directed.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire.
S&F in replacement of OFF Load Change over switch of 100 Amps capacity 415 Volts, 4 pole, incl sheet metal enclosure as per the existing switch including taking out old unserviceable one. Make : Indoasian Cat part No OFFPO100/L&T/Havells/BENLO
S&F in replacement of Spreaders pole, Frame F2 & F3 for fixing of MCCB at existing panel including dismantling of old one.
S&F in replacement of Spreaders 4 pole, Frame F2 & F3 for fixing of MCCB at existing panel including dismantling of old one.
S&F in replacement of HRC fuse links & Bases, Bolted type, 35 to 63 Amps, including dismantling of old one.
S&F in replacement of fuse base for din type HRC fuses links , rating 6 to 160 Amps, including dismantling of old one.
SAHYOG ELECTRIC
Ms Kailash Chandra Babulal
S.S. Engineers
Vinayak Trading House
MODI CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .