Tender Value
₹55.0 Cr
EMD Value
₹1.1 Cr
Closing Date
19 Jun 2026, 3:00 pm
KAPIL DEV
Hisar PHED No. 1
CONSTRUCTION OF STP MPS AND IPS LAYING OF SEWERAGE NETWORK AND CONSTRUCTION OF MANHOLES AT VILLAGE KAIMRI. CONSTRUCTION OF R/W PUMPING STATION, 3rd WATER WORKS, PROP. BOOSTING STATION, UPGRADATION OF 2nd WATER WORKS AND LAYING THE PIPE LINE
2026_HRY_527544_1
20266E7E56A7 BAC5 4F16 AB04 475BC0C910FB564PUH
Open Tender
Civil Works
790 days
KAIMRI KAIMRI
CONSTRUCTION OF STP MPS AND IPS LAYING OF SEWERAGE NETWORK AND CONSTRUCTION OF MANHOLES AT VILLAGE KAIMRI. CONSTRUCTION OF R/W PUMPING STATION, 3rd WATER WORKS, PROP. BOOSTING STATION, UPGRADATION OF 2nd WATER WORKS AND LAYING THE PIPE LINE
2 documents required · 2 mandatory
₹20,000
₹1.1 Cr
Yes
8 Jun 2026
8 Jun 2026
19 Jun 2026
8 Jun 2026
19 Jun 2026
8 Jun 2026
8 Jun 2026 - 19 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | WTP: Design and construction of 1.50 MLD capacity automated PLC controlled water treatment plant including providing and laying the DI / CI pipes, specials, sluice valves from inlet chamber of WTP to inter connecting piping network in WTP (The cost of these DI / CI pipes, valves and specials shall also be included in the rates quoted by the contractor) along with inlet chamber, Alum dozing, Flash mixing, Clariflocculator, filter box, over head Reservoir for back wash and waste water tank with suitable size pumping sets and panel boards, air scour equipment, chemical house with chlorination equipments, all other civil, mechanical, electric installations complete in all respects as per specifications (make of Sluice valves / NRV: IVC / VAG / Kirlosker)
1.50 MLD Capacity | 1 | Job | - | - |
| 2 | WTP: Design and construction of 2.00 MLD capacity automated PLC controlled water treatment plant including providing and laying the DI / CI pipes, specials, sluice valves from inlet chamber of WTP to inter connecting piping network in WTP (The cost of these DI / CI pipes, valves and specials shall also be included in the rates quoted by the contractor) along with inlet chamber, Alum dozing, Flash mixing, Clariflocculator, filter box, over head Reservoir for back wash and waste water tank with suitable size pumping sets and panel boards, air scour equipment, chemical house with chlorination equipments, all other civil, mechanical, electric installations complete in all respects as per specifications (make of Sluice valves / NRV: IVC / VAG / Kirlosker)
2.00 MLD Capacity | 1 | Job | - | - |
| 3 | 1. STP (SEWAGE TREATMENT PLANT): 2.00 MLD: Design, construction, erection, testing and commissioning of 2.00 MLD capacity Sewage Treatment Plant based on Sequential Batch Reactor (SBR) including Electrical, Mechanical, Piping and Instrumentation work with PLC and SCADA arrangement for STP integrated with MPS including furniture and laboratory equipments as per detail and specifications mentioned in attached additional documents along with following provisions:
1.1 1 High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 4 No. LED suitable size, outdoor type energy efficient lamps on each pole , 2 LED outdoor light with 6 m. high GI pole along road / path including all accessories complete in all respect.
1.2 Supply and fixing of 1 No. 3.65 m wide SS 304 main Gate along with1.25 m. wide wicket gate at STP to the entire satisfaction of Engineer-in-charge. (Total weight not less than 500 kg).
1.3 CC TV CAMERAS: Providing and Installing 6 CCTV Cameras (4 Cameras for STP and 2 Camera at MPS-1) within 96 hours of signing the agreement along with 120 days recording (DVR), 48 inch LED Screen, 16 Channel DVR at STP and MPS Site with connectors, cables, poles and power supply with online real-time output facility. The cameras at MPS and STP shall be synchronized at STP site complete in all respect.
PTZ speed dome 360 degree 50X zoom camera, CP Plus Internet Protocol minimum 5 MP WDR, Night vision color mode, IR range up to 150 m. CCTV Cameras should be installed and commissioned before starting of the work.Make: Sony / Canon / Panasonic / Samsung
1.4 EWQMS (Effluent water quality monitoring system): Supply, Installation, Testing, Commissioning, Operation and Comprehensive Annual Maintenance of effluent quality monitoring system at 2.00 MLD capacity STP for online (continuous) measurement of PH, Total Suspended Solids (TSS), Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (spectral measurement in the UV-VIS range 200-720 mm) performing reagent and chemical free analysis with automatic cleaning of censor, signal cables and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB and PHED, TUV approved complete in all respect as per Central Pollution Control Board (CPCB) guidelines for online continuous monitoring system for effluents.
1.4.1 Multi-parameter measuring converter, for connecting up to 18 intelligent sensors Scope including 8 analog inputs / outputs (4 inputs and 4 outputs) (0/4-20Ma), wide- range power supply Optical COD/BOD and TSS probe with spectral processing of the UV-VIS range, for measurement in the outlet / effluent of 2.00 MLD capacity STP with integrated with automatic cleaning complete in all respect.
1.4.2 Robust digital pH/ORP sensor for pH/ORP electrodes, with built-in pre-amplifier and temperature sensor with Automatic Temperature Compensation (ATC) Cable length 100 Meter (minimum) complete in all respect.
1.4.3 Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to the intelligent Sensor Net system. Cable length 100 meter (minimum) complete in all respect.
1.4.4 Data transfer to CPCB, HSPCB and PHED servers complete in all respect.
1.4.5 Providing GSM 3G, 4G modem with mobile network connectivity including network including complete in all respect.
1.5 Conveyance of treated effluent from cholorine contact tank to effluent collection tank through suitable size DI K9 pipe along with cost of pipe, sluice valves, specials, material and labour complete in all respect. | 1 | Job | - | - |
| 4 | 1 MPS (MAIN PUMPING STATION): Design, construction and commissioning of MPS for 2.00 MLD average flow with peak factor 3 including RCC Inlet chamber, screening chamber, wet well sump complete in all respect as per detail and specifications mentioned in attached additional documents along with following provisions:
1.1 Providing, fixing and commissioning of 5 non clog sewage submersible pumping sets as per IS marked ie. 1 of 3800, 2 of 1300 and 2 of 700 LPM having minimum head of 35 m along with making all arrangement including sluice valves, Non return valves, specials, flanged individual and common delivery pipes, suitable size LT panel boards and suitable size cable from LT panel to pumps, all safety devices, automatic capacitor bank, complete in all respect as per specification mentioned in attached additional documents.
1.2 Conveyance of raw sewage from MPS to inlet chamber of STP through rising main line. ng with cost of DI pipe, sluice valves, specials, material and labour complete in all respect.
1.3 Suitable size (as per design) K9 DI pipe at MPS for interconnecting the structures including welding and screwing of flanges, ISI marked D.I. fittings, sluice valves, non returning valves as per requirements even for bye-pass arrangements complete in all respect
1.4 Suitable size (as per design and requirement) Gear Operated Sluice Gate with SS Spindle (SS 410) and seats (SS 304) for screens and partition of tank as per design.
1.5 Supply and installation of 1 mechanical and 1 manual coarse screen (SS 304) suitable for 2.00 MLD average flow with peak factor of 3.0 complete in all respect.
1.6 All the pumping machinery, panel board, Level sensor etc shall be controlled by PLC and SCADA and shall be synchronized with PLC panels at MPS and STP site through broadband internet facility.
1.7 2 No. High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 6 No. LED suitable size, outdoor type energy efficient lamps on each pole, 20 no. LED outdoor light with 7 m. high GI pole along road / path including all accessories complete in all respect.
1.8 Raw sewage will be available near boundary wall within the premises of proposed MPS but the conveyance of sewage from this terminal point to the inlet chamber of MPS through DI K9 pipe of suitable diameter as per design is included in the Turnkey contract. The Level of the MPS / STP will be as per bed level of existing incoming sewer at MPS. | 1 | Job | - | - |
| 5 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd
10 Sqmm size | 60 | Per Meter | - | - |
| 6 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
150 mm nominal diameter | 4 | No. | - | - |
| 7 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
200 mm nominal diameter | 6 | No. | - | - |
| 8 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
250 mm nominal diameter | 2 | No. | - | - |
| 9 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
300 mm nominal diameter | 2 | No. | - | - |
| 10 | Providing, fixing, lointing, testing of Mechanical joints complete with rubber gaskit, Galvanized nuts and bolts including labor, tranportaion ets up to the site.
350 mm nominal diameter | 2 | No. | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.07 MB
BOQ_606532.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid