Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 4 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 5 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹2.0 Cr
Closing Date
15 Jun 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer University of Kashmir
Construction Division
Electrical and allied works for 04-Storeyed Research Hostel at Zakura Campus.
2021_UDJK_125442_1
F(E.Tend)( UCD)KU/13/21
Open Tender
Electrical Works
Item Rate
365 days
Zakura Campus University of Kashmir
As per NIT
6 documents required · 6 mandatory
₹5,500
Registrar University of Kashmir
Exempted
16 Jun 2021
28 May 2021
16 Jun 2021
29 May 2021
15 Jun 2021
29 May 2021
120 days
Amount
Point Wiring
Wiring for light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring fo exhaust fan point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for ceiling fan point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and fixing modular switch/ socket on the existing modular plate & switch box including connections including modular plate etc. as required with 3 pin 5/6 A socket outlet with 2 way 5/6 A switch.(The socket outlet shall be fixed on the Modular place for used fixing light switches on the same lighting switch board).
Wiring for Computer points 230V AC, 2 Nox1 5/10 Ampere socket outlets for light duty power.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required: 6 Module (200mmX75mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required with 3x1No of 3 pin 5/6 A Modular socket outlet.
Supplying and fixing following modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required with : 5/6 A switch Modular.
Wiring for above computer points wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.with 2R X 2.5 sq. mm + 1R X 2.5 sq. mm earth wire. (Note:(4 set of UPS plug shall be looped per circuit to PDB), quote rates excluding circuit wiring and conduict 2Rx4mmsq+1x4R mmsq FRLS insulated Coppor wires multistranded.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.Note :(Two Socket outlets shall be looped to the one single Power circuit to PDB.However 30 out of total 240 No power Socket Outlets are for Geysers one socket outlet shall be connected per circuit to the nearest Power Distribution Board).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and15/16 A modular switch, connections etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required. ( for Water Storage Heaters/Gysers)
Supply and fixing of 50 Litre storage water heaters /Gysers complte in all respects of stnadard make like Racold/Venus/Essel/Bajaj
Circuit Wiring
Wiring for circuit wiring Light /Fan/Exhaust/etc alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required(light point/ fan point/ exhaust fan point/ call bell point) with 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.with 25 mm dia and 2mm thick.
Wiring for circuit wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required with 2 X 4 sq. mm + 1 X 4 sq. mm earth wire( for computer/UPS points to the nearest SDB)
Sub Main Cables
Supplying and Laying of 1.1 KV voltage grade PVC insulated sheated coppor conductor for / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as requiredas per specifications in ductworks,treenches,cable trays,over beds of stand,clamped to the wall with suitable clamps including 40mm dia,2 mmthick PVC conduits from Sub-Distribution boards to Main Indoor LT Pane : 4R X 16 sq. mm + 2 X 6 sq. mm earth wire earth wire earth wire for heating ckt.
Supplying and Laying of 1.1 KV voltage grade PVC insulated sheated coppor conductor for / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as requiredas per specifications in ductworks,treenches,cable trays,over beds of stand,clamped to the wall with suitable clamps including 40mm dia,2 mmthick PVC conduits from Sub-Distribution boards to Main Indoor LT Pane :4R X 10 sq. mm + 2 X 6 sq. mm earth wire earth wire earth wire for heating ckt.
Supplying and Laying of 1.1 KV voltage grade PVC insulated sheated coppor conductor for / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as requiredas per specifications in ductworks,treenches,cable trays,over beds of stand,clamped to the wall with suitable clamps including 40mm dia,2 mmthick PVC conduits from Sub-Distribution boards to Main Indoor LT Panel 2R X 10 sq. mm + 1 X 6 sq. mm earth wire for heating ckt.
Supplying and Laying of 1.1 KV voltage grade PVC insulated sheated coppor conductor for / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as requiredas per specifications in ductworks,treenches,cable trays,over beds of stand,clamped to the wall with suitable clamps including 40mm dia,2 mmthick PVC conduits from Sub-Distribution boards to Main Indoor LT Pane :2 R X 6 sq. mm + 2X 6 sq. mm earth wire earth wire earth wire( for Computer ckt.)
Supplying and Laying of 1.1 KV voltage grade PVC insulated sheated coppor conductor as per specifications in ductworks,treenches,cable trays,over beds of stand,clamped to the wall with suitable clamps including 40mm dia,2 mmthick PVC conduits from Sub-Distribution boards to Main Indoor LT Panel: 4 RX 10 sq. mm + 2R X 6 sq. mm earth wire for heating ckt.2 R X 6sq. mm + 1 X 6sq. mm earth wire. mm earth wire earth wire ( for Lighting ckt.)
cable end termination of the copper conducor single core wires of 1.1KV volatage grade including supplying and fixing of bimetallic crimping lugs 4R X 16 sq. mm + 2 X 6 sq. mm earth wire earth wire
cable end termination of the copper conducor single core wires of 1.1KV volatage grade including supplying and fixing of bimetallic crimping lugs 2 RX 6 sq. mm + 1R X 6 sq. mm earth wire for Computer ckt.
cable end termination of the copper conducor single core wires of 1.1KV volatage grade including supplying and fixing of bimetallic crimping lugs2R X 4 sq. mm + 1 RX 4 sq. mm earth wire for Lighting ckt.
cable end termination of the copper conducor single core wires of 1.1KV volatage grade including supplying and fixing of bimetallic crimping lugs 2R X 10 sq. mm + 1 X 6 sq. mm earth wire for heating ckt. earth wire for Lighting ckt.
Sub Distribution Box/MCB Box
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. with 8 way (4 + 24), Double door.(Power Distribution Boards)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. with 6 way (4 + 18), Double door.(Light Distribution Boards)
Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)-16 Way SPN(for Toilet Blocks)
Supply of approved make powder coated sheet steel encloser SPN MCB DB inclusive of Bus bar, Neutral bar,Earth bar & two earth terminals etc. complete as per IS:13032( exclusive of MCB & isolator )-6 Way Single Door
Supplying and fixing 6A to 10A rating, 240V 10 kA, “C” curve, Single pole miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 16A to 40 A rating, 240V 10 kA, “C” curve, Single pole miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and installing of RCCBs (Residual current circuit breaker with overload and short circuit protection) ISI marked complete as per I.S. standard confirming to IEC:61009-2-1 & IS:12640-2:2001,240/415V 50 Hz with 10 kA short circuit withstand capacity for earth leakage, overload & short circuit protection including connection in existing enclosure in approved manner as per specification.2 pole 32 Amps, 30 mA sensitivity
Supplying and installing of RCCBs (Residual current circuit breaker with overload and short circuit protection) ISI marked complete as per I.S. standard confirming to IEC:61009-2-1 & IS:12640-2:2001,240/415V 50 Hz with 10 kA short circuit withstand capacity for earth leakage, overload & short circuit protection including connection in existing enclosure in approved manner as per specification-4 pole 40 Amps, 30 mA sensitivity.
Supplying and installing of RCCBs (Residual current circuit breaker with overload and short circuit protection) ISI marked complete as per I.S. standard confirming to IEC:61009-2-1 & IS:12640-2:2001,240/415V 50 Hz with 10 kA short circuit withstand capacity for earth leakage, overload & short circuit protection including connection in existing enclosure in approved manner as per specification-4 pole 63 Amps, 30 mA sensitivity
Supplying and fixing 40-63 A rating, 240V 10 kA, “C” curve, Double pole miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Floor LT Service Sub Panel 1-@4 No Floor )
Design, fabrication, Assembling of supply, installation, testing and commissioning of Floor L.T PANEL of cubical main type panel board from high quality 16 SWG 2mm wall thickness CRCA sheet angle/flat iron mounted with hinged lockable front double door for each meter compartment to accomadate with fixing arrangement of energy meter,MCCB,MCB's ,changerover switches along with bus bar ways in separate compartments painted with powder coated conforming to CPWD specification IP-55 .The LT Distribution panel must be free standing ,floor mounting and front execution type suitable for 415 V +/- 3% , 3 phase and neutral ,50 Hz system conforming I.E rules with necessary provision to connect cables of various sizes from the rear bottom side., 50 Hz, 4 wire power supply system.The assembly comprising o fchassis ,famework, and fixed parts of metal casing of the switchgear shallbe provided with separte earthing. terminal.The formation must be compartmentalised in form 3b construction and must be supplied and installed.Note: ( 4 to be installed in 4 Separate Floors,(4 No @ 93 kg each))
Incomer Floor Panels: Supplying of ISI Marked and approved make of Moulded Case Circuit Breaker (MCCB) suitable for 3 phase,4 pole,50 Hz, 415 Volts, AC supply with respective interrupting capacity (KA) at 415 Volts cited against their range standard conforming to IS – 8828 MCCB TP&N with Breaking Capacity 10 KA at 415 V-Current Rating -25 Amps(Lighting)
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 200 A, 25 KA,TP&N MCCB( 4 No for 4 Floor Panels)
Incoming :300A TPN ALU.BUS BAR
Outgoing:Branch circuits Heating:40 A TPN,25 KA MCCB
Heating:63 A TPN,25 KA MCCB
UPS/Computer:50A DP MCB,16KA
Lighting :20-32 DP MCB,16KA
UPS/Computer:40 DP MCB,16KA
Incoming indicating Lights
Incoming voltmeter(0-500V)
Incoming Ammeter(0-800A)
CT for Ammeter with ratio of 300/5
Main Service LT Panel
Incomer Main service Incomer: Supplying of ISI Marked and approved make of Air Circuit Breaker (ACB) with Microprocessor release with LCD screen showing kW, kVA, PF, maximum demand with breaking capacity of 50 kA , 4 pole , 415 Volts conforming to IEC : 60947-2 / IS :13947-II-5800 Amp,manual,fixed
Incoming :1200A TPN ALU.BUS BAR
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. For Main Incomer Heating -I:
MCCB with Breaking Capacity 25 KA at 415 V-Current Rating -500/630 Amps & Adjustable: 80% -100%thermal
For Main Incomer Lighting -II: TPN MCCB with Breaking Capacity 30 KA at 415 V-100 A,30KA,FPMCCB
Supplying of ISI Marked Change over switches in sheet enclosure confirming to IS : 4064 / IS : 13947 (part I & III ) with side handle operated 4 pole with two earthingterminals 100 Amps. 415/500 Volts.(off load )
Outgoing Floor Circuits to Floor Panels Supplying of ISI Marked and approved make of Moulded Case Circuit Breaker (MCCB) suitable for 3 phase,4 pole,50 Hz, 415 Volts, AC supply with respective interrupting capacity (KA) at 415 Volts cited against their range standard conforming to IS – 8828 MCCB TP&N with Breaking Capacity 10 KA at 415 V-Current Rating -25 Amps(Lighting)
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required
200 A, 25 KA,TP&N MCCB( 2 No Floor Panels)
160 A,25 KA, TP&N MCCB(2 No Floor Panels)
125 A,25KA TP&N MCCB(2 No Floor Panels) for outgoing ckt to 40KVA UPS Auxiliary Power Supply.
300A TPN ALU.BUS BAR
Incoming indicating Lights
Incoming voltmeter(0-500V)
Incoming Ammeter(0-500A)
CT for Ammeter with ratio of 600/5 .
Main LT Power Cable Supply of XLPE Insulated power cable (confirming IS-7098 Part-I ) 1100 Volt grade,3½ core/4 core ISI MARKED with Alu. Stranded /solid conductore.3½ CORE ARMOURED
3.5 core cX 500 mm2 Armoured XLPE Aluminum cable
3.5 core cX 240 mm2 Armoured XLPE Aluminum cable
3.5 core cX 35 mm2 Armoured XLPE Aluminum cable
3.5 core cX 50 mm2 Armoured XLPE Aluminum cable
Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in groundincluding excavation, sand cushioning, protective covering andrefilling the trench etc as required
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 500 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required:3½ X 500 sq. mm (82mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required:3½ X 240sq. mm (62mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required:3½ X 50 sq. mm (35mm)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting,jointing etc. in the existing trench, complete as required.90 mm dia (OD-90 mm & ID-76 mm nominal)
CABLE TRAYS Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors,suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required:
200 mm width X 50 mm depth X 1.6 mm thickness
Light Fixtures and Fittings
Supply & fixing Mounting rail / Batten made of CRCA powder coated with suitable lamp holding brackets for LED Tube rod 1200mm Single on wall / ceiling including connection testing etc complete as required.S 20- 24-Watt LED Batten t (T-5 eries),6500K,2400-2500 Lumens, average life of 50 hours along with accsessory assembly or equivelent slim of Philips/Cromption/Osram/Bajaj) complete in all respects.(cool white).
Supplying, erection and testing of approved make electric ceiling fan of complete with standard down rod, canopy, hanging shackle, Aluminium blades, A.C. 230-250 volts including connections with all necessary material complete of approved as required -Ceiling Fan ( ISI )-1400 mm Sweep,80-90W.
Supplying, erecting and testing of approved make Exhaust Fan of 300 mm(12 Inches) 900 rpm with mounting frame, blades AC 230-250 complete connection and including, frame bolt/ Anchor hole fastners etc. complete finished of approved as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but including modular plate etc. as required complete in all respects.(for ceiling fans points)
Supply of energy efficient flood/area lighing with high power LED of 100-120W assembled on single MCPCB, system lumens output with luminous efficacy>100 lm/W. Luminiare having color temp 6500K & 50000 burning hrs life wih minimum @ L70(rated lumen maintenance life of 70% at 50,000 hours).The colour rendering index of LED light should be more than 80. Luminiare comprises of driver, PF= 0.95 & surge protection 3KV. Housing must be made of pressure die cast aluminium and with heat resistant flat glass,should have IP65 protection(Feature of IP 65 :Dust proof and water proof protection). The total light output from Luminarie must be about between 10500-12000 Lumens). IP-66 Note:Note:IEC Compliant for Safety, Performance & EMI Form LED Source Manufacturer & LM79-08 / IS16106 from NABL approved lab. Manufacturer manadatory. including connection wire, testing etc. to complete the job in all respects . Each Lumanrie should be having 2 years Guarantee certificate from manufacturer. Approved make-Philips/GE/ Wipro/Crompton Greaves /Osram/Havells/Bajaj) with BEE Star rating -3 or above.
STRUCTURAL CABLING & CONDUTTING FOR DATA SYSTEM
Supply, Installation testing and commissioning of wall mounting rack, for computer switches complete as mentioned below 6U cabinet 371.30X600X500, wall mounting with power supply and Fan etc :-switch.Make: Val Rack/ Net Rack/ APW )
Supply, installation, testing and commissioning of wall mounted 4U metal rack for housing 8 port ethernet switch etc complete with Tray Mounting Fan + power supply board. Bank's hardware - port switch / patch panel.The cabinet frame shal have minimum depth of 500mm to accomadate 8 port ethernet switch.Make: Val Rack/ Net Rack/ APW )
Supply, installation, testing and commissioning of approved make approved brand (DLink/Cisco/Digilink/Amps ) 32 -port Ethernet Gigabit switch complete in all respects
Supply, installation, testing and commissioning of approved make approved brand (DLink/Cisco/Digilink/Amps ) 32 -port Ethernet Gigabit switch complete in all respects
Supply, installation, testing and commissioning Wireless Acess points/Wi-fi points of Netgear/Cisco./Huwai /Dlink approved make approved brand complete in all respects
Supply, Installation testing and commissioning of patch cord as mentioned below :-CAT 6 RJ45 Patch Cord F/UTP 1 Mtr.
Supply, Installation testing and commissioning of patch cord as mentioned below :-CAT 6 RJ45 Patch Cord F/UTP 2 Mtr.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.(1 run of cable)
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required with25 mm dia ,2mm rhick.
Earthing System
Providing earthing stations at locations as called for Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Lightning Conductor
Providing and fixing of lightning conductor finial, made of 25mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc complete as required
Jointing G.I. tape (with another G I tape, base of the finial or any other metallic object) by riveting / nut bolting sweating and soldering etc. as required
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet oron surface of wall for lightning conductor complete as required.(For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required.(For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
INTELLIGENT FIRE ALARM SYSTEM
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable,600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required-25 mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required-25mm
Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of intelligent addressable smoke detector with built in LED, mounting base complete with all connection etc.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Sabtech Engineering Works
M/S ASHIQ HUSSAIN BHAT
M/s AHKHAN ENTERPRISES
M/S KHAN AND CO.
M/S INTERNATIONAL STORES
Escon Electricals
M/S ZAHID ENTERPRISES
M/S KHATIJA ELECTRICAL AND MECHANICAL ENGINEERING
stage.html
html • 0.03 MB
finance_245880.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .