Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹54.1 L
EMD Value
₹1.1 L
Closing Date
7 Dec 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
CWE NW MUMBAI
CWE NW MUMBAI
REPAIR REP OF LT ELECTRIC CABLES, HT LT CAPACITOR BANK, OVEHAULING OF HT VCB, TRANSFORMER, LT BUS DUCTS, LT ACB, MCCB AND STREET LIGHT FITTING CONNECTED ACCESSORIES AND PAINTING OF ELECTRICAL MACHINES, EQUIPMENTS ALLIED ELECTRIC WORKS AT INHS ASVINI
2026_MES_798166_1
8043/CWE(NW)MUMBAI/E8
Open Tender
Civil Works
Item Rate
270 days
CWE NW MUMBAI
AS PER TENDER
8 documents required · 8 mandatory
₹1,000
Yes
AGE I ASVINI
₹1.1 L
Yes
11 Nov 2026
11 Nov 2026
8 Dec 2026
11 Nov 2026
7 Dec 2026
2 Dec 2026
11 Nov 2026 - 20 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Disconnecting and dismantling the existing indoor type, 11 KV horizontal draw out type VCB trolly of rupturing capacity 250/350 MVA, 400/630/800/1200 Amps from location and repair /overhauling and carrying out with the following all as specified and directed by Engineer-in-Charge.
(Note: spare parts will be measured & paid separately.) (i) Inspecting / overhauling of manual / motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw,motor cut -off limit switch, butter fly swich assembly and apply multi grease lubricant to function smoothly.(ii) Inspecting / overhauling of tripping assembly,earthfault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system. (iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces. (iii) Inspecting / overhauling /cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and apply dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces.(iv) Assembling all items/components parts to the respective position & testing the breaker with High Voltage(DC) and meggering before and after high voltage test complete. | 10 | Each Job | - | - |
| 2 | M & L for painting of HT VCB capacity 250/350MVA,11KV, 400/630/800/1200Amps, with one coat of synthetic enamel paint over a coat of red oxide primer after cleaning, scraping, and filling of cavities for out side surface and in side surface of VCB and all as specified and as directed by Engineer-in-charge. | 10 | Each Job | - | - |
| 3 | M & L for Opening the bus-bar chamber, CT chamber, PT Chamber and Meter chamber of HT 11KV, panel board and carry out following and all as directed and specified by Engineer-in-Charge.
(Note: spare parts shall be measured & paid seperately.) :-(i) Inspecting/cleaning/overhauling of bus bar chamber by checking of bus bars, spout insulators, space heaters and removing dust with vacuum cleaner/Blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying STRIPPEX(A), STRIPPEX(B) and HT tape and test with High Voltage(DC) and meggering before and after high voltage test complete.(ii) Inspecting/cleaning/overhauling of CT/PT chamber by checking of Bus bars, spout insulators, space heaters and checking of wiring system and removing dust with vacuum cleaner/blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying anti tracking paint on CT's and insulators and HT Tape.(iii) Inspecting/cleaning/overhauling metering chamber by checking of entire wiring system, all meters, selector switches, control fuses and removing dust with vacuum cleaner/blower and moisture by hot air blower and checking tightness of wiring system. | 10 | Each Job | - | - |
| 4 | Overhauling, calibration and secondary injection of over current earth fault relays/release on each multiple setting readjustment by artificial load complete all as specified including testing complete. | 10 | Each Job | - | - |
| 5 | Testing of primary injection by artificial load through CT’s, on each multiple setting of over current & earth fault relay, testing polarities, ammeter and selector switch and as directed by Engineer-in-Charge. | 10 | Each Job | - | - |
| 6 | Dismantling, overhauling and testing Potential transformer capacity 11 KV / 110 volts, AC and replacement of worn out spares such as contacts, bushing, control wiring fibre plates, gaskets , transformer oil and applying multi grease to the mechenical parts & dry graphite conductive sealant to contacts etc & re-assembling the same and commissioning complete all as specified and directed by Engineer-in-Charge. (Note : Spare parts and oil will be measured and paid seperately) | 4 | Each Job | 1 | ₹4 |
| 7 | Testing of dielectric strength of transformer oil of indoor type transformer, 11KV/433 volt, filteration of transformer oil by passing through filtration plant to remove moisture, impurities and improving di-electic strength to above 40 KV for 1 minute including new transformer oil for toping up & testing after filtration complete as specified. (Note: Transformer oil will be measured & paid seperately.) | 4,400 | Ltr | - | - |
| 8 | Supply only transformer oil with 50KV di-electric strength for topping up and replacement of old/burnt transformer oil complete all as specified. | 418 | Ltr | - | - |
| 9 | S & F in repair of breather with 500 Grams silica gel of indoor type transformer for 1600KVA, all as specified and directed by Engineer-in-Charge. | 4 | Each | - | - |
| 10 | M & L for Spray Painting of Transformer 1600KVA ,11KV/440Volt capacity, indoor type with two coats of synthetic enamel paint over a coat of red oxide primer after cleaning, scraping, and filling of cavities and all as specified and as directed. | 4 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
8043_Apppx.pdf
Tender Documents • 0.19 MB
8043_Genpages.pdf
Tender Documents • 0.71 MB
8043_makes.pdf
Tender Documents • 0.25 MB
8043_NIT.pdf
Tender Documents • 0.39 MB
8043_PS1.pdf
Tender Documents • 0.14 MB
8043_PS2.pdf
Tender Documents • 0.67 MB
BOQ_895485.xls
BOQ • 12.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .