Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.8 LAccepted-AOC HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹9.0 L+₹21,536 (2.45%)Rejected-Finance TENTUNBARIA GARIA KOLKATA 700084 | KOLKATA | 24 PARAGANAS SOUTH | WEST BENGAL | 700084 | L2 | Rejected-Finance Other than L1 | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Recommended due to incomplete/inadequate documents |
Tender Value
₹9.1 L
EMD Value
₹18,200
Closing Date
2 May 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE, HQ 138 WE
CWE, HQ 138 WE
PROVN OF 02 X STANDALONE CENTRAL HEATING SYSTEM (CHS) IN BLDG NO TO-699 IN THE AOR OF AGE E/M-I UNDER GE 865 EWS
2025_MES_699625_2
138WE/L-144/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 865 EWS
AS PER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹500
GE 865 EWS
₹18,200
12 Jun 2025
11 Apr 2025
9 May 2025
11 Apr 2025
2 May 2025
18 Apr 2025
Amount
Supply and installation testing and commissioning of ductable type standalone oil fired kerosene/ HSD based heating system complete with stainless steel heat exchanger chamber consisting of furnace fabricated out of high temperature resistance stainless steel, automatic burner assembly control panel with sequence controller, photocell, for flame failure. HT Transformer electrode fan assembly with motor temperature controller stainless steel reflector, built in fuel oil piping exhaust chimney all housed in powder coated casing suitable for operation on 50 Hz single phase 230 volt AC Supply capacity 50,000 KCal/ hr with fallowing:- (a) Heat Output - 50000 KCal/Hr. (b) Hot Air Temp - 40 C (c) Temperature Rise - 90 C Max (d) Fuel Consumption - 5.2-5.6 Ltr/Hr (e) Thermal Efficiency - 80-90% (f) Electrical Supply - 220 Volts 50 Hz (g) Temperature Control - Automatic (h) Fuel - Kerosene/ Diesel (j) Burner - Riello/ Ben-tone Make : ECCO Flame/Flameco/Thermex or equivalent
Design, Supply, fixing and testing ducting for hot air blower to room with closed cell elastometric insulation 30 to 40 Kg/Cum density 25 mm thick (nitrite insulation) complete all as specified and as directed. Make- Eurobatex/ Superion/ Aeroflex Note : Insualation material should retain Temp inside (+) 25 degree centigrade and (-) 25 degree centigrade
Supply and fixing sheet metal enclosure for DBs double door when MCB's to be used single pole & neutral 240 Volts 4 Ways complete all as specified and directed by Engr-in-Charge.
Supply and fix MCB SPN 40 Amp 240 Volts AC ISI marked complete all as specified and directed by Engr-in-Charge.
Supply and fix MCB SP 6-32 Amps. 240 Volts 50 HZ complete all as specified and directed by Engr -in-charge
M & L for submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed as required in PVC casing Caping wire size 2x4.0 sq. mm + 1x 4.0 sq. mm earth wire complete all as specified and directed by Engr-in-Charge.
Supply and fixing sheet metal enclosure with 20 Amp 240 V socket plug top and MCBs single pole and neutral enclousre with two pin and earth plug and socket with one single pole 20 Amp MCB complete all as specified and directed by Engr-in-Charge.
Material & labour for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6.0 mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron wire 4 mm as earthing lead (upto terminal point) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 3 of SSR 1991(Part-I) Taking out old unserviceable earthing complete all as specified and directed. NOTE : - The rates for earth work, GI protection pipe, funnel, wire wesh, CI cover, etc shall be deemed to be including in quoted rates.
Supply & fixing tubes light grade of size 50 mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and directed by Engr -in-charge
Supply and laying in trenches or passing through pipe or fixed on surface XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade of size 16 Sq mm 2 Core complete all as specified and directed by Engr in Charge.
M&L for making of foundation for Stanalone CHS of capacity 50000 K cal including installing complete all as specified and directed by Engr-in-Charge.
Western Engineering Co (BID ID -3287537)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .