| 3 | L3₹29.2 L+₹95,775 (3.39%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹29.4 L+₹1.2 L (4.09%)Rejected-Finance | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹30.7 L+₹2.5 L (8.76%)Rejected-Finance | L5 | Rejected-Finance Other than lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
14 Oct 2024, 6:00 pmClosed
GE (AF) E/M CHAKERI KANPUR
GE (AF) E/M CHAKERI KANPUR
REPAIR AND MAINTENANCE OF STREET LIGHTING SYSTEM IN DOMESTIC AREA AT AFS KANPUR
2024_MES_669981_1
8717/E8
Open Tender
Civil Works
Item Rate
270 days
Area under GE(AF) EM Chakeri
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE (AF) E/M CHAKERI
₹60,000
Yes
22 Jan 2025
2 Sept 2024
19 Oct 2024
2 Sept 2024
14 Oct 2024
28 Sept 2024
Amount
Labour only for checking the serviceability of street light fittings including lowering down (except high mast light) if needed and testing of different spares / components / parts of security light fittings of any wattage/capacity of any description and in any position, checking functioning of contactor, MCCBs and their replacement if found to be unserviceable, regular cleaning of dust & dirt deposit due to natural effects, removal of carbon deposits it any or as direction of Engr-in-Charge and replacement of un-serviceable/ damaged /broken part(s) either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in position, connecting to electric supply and its testing on installation complete all as specified and directed by Engineer-in-Charge. Note for item is as under:-
Spare parts/componenets required to make the light fittings serviceable shall be measured and paid for separately under respective item of sch 'A'.
Necessary T&P i.e. ladder, tools etc required for checking and making the light fittings in serviceable conditions, its fixing in position and testing shall be arranged by the contractor at his own cost for checking and fixing of street light fittings/security light fittings of any description on poles / on walls / on pillars etc.
Required screws, insulating tapes, internal wiring wire , gaskets, tape insulation and other minor items excluding the required spares parts for repairing and making the street light fittings/security light fittings in serviceable condition, will be arranged & supplied by the contractor and cost of which is deemed to be included in the rates quoted by the contractor in above respective item.
Taking down unserviceable street/security light fittings of any type,wattage and make from LT/HT poles and transporting from site to MES store yard for repairing in deemed to be includ in this item rate. The defective street light fittings will be repaired only at MES yard/place as directed by Engr-in-Charge.
Supply only LED lights driver 60W , 140 V to 270 V universal driver with built in surge protection with suitable electronic circuit complete all as specified and directed. Note:- Driver shall be of same make as per make of light fitting.
Supply only LED lights driver 90W , 140 V to 270 V universal driver with built in surge protection with suitable electronic circuit complete all as specified and directed. Note:- Driver shall be of same make as per make of light fitting.
Supply only LED lights driver 100/120W , 140 V to 270 V universal driver with built in surge protection with suitable electronic circuit complete all as specified and directed. Note:- Driver shall be of same make as per make of light fitting.
Supply only LED lights driver 250W , 140 V to 270 V universal driver with built in surge protection with suitable electronic circuit complete all as specified and directed. Note:- Driver shall be of same make as per make of light fitting.
Lowering of high mast light assembly from upto 16 Mtr high mast,any type, make and wattage, dismantling, checking parts and components for replacement, if required, and making the light fittings operational to give rated illumination incl. cleaning of glass cover and refixing the same after repair/replacement of defective components complete with necessary electrical connection with by providing 3 core 1.5 Sqmm PVC sheathed multi stranded copper conductor cable of required length complete all as specified and directed. Note :-Spare parts/components to be replaced shall be measured and paid for separately under respective item no. 7, 8 & 9of sch 'A'. The cost of greasing of pully, roller, bearing and gear including refixing of rope clamps, adjustment of lock, leaver etc shall be deemed to include the quoted rate.
Supply only trailing cable 4 Sqmm, 5 core copper conductor EPR insulated PCP sheathed cable having current carrying capacity 30 Amp complete all as directed by Engr-in-Charge.
Supply only trailing cable connector and terminal box complete all as specified and directed. Make and Model as per existing.
Supply only high mast 3 phase, 440 volt integral motor remote control switch with one No MCB 4 pole, 63 Amp complete all as directed by Engr-in-Charge. Make :- As per existing.
M&L repair, welding of High Mast feeder pillar box front/ rear door and locking arrengement including paint patch work making good as per existing colour and as directed by Engr-in-Charge.
Supply and fix in repair LED bulb 15 Watt suitable for Garden light / Post top lantern complete all as specified and directed
Supply and fix in repair LED bulb 9 watt, for Garden light/ Post Top, as directed
Supply and fixing Batten holder for retrofit universal type as directed by Engineer -in - charge
M&L for street light timer including testing and commissioning of Astronomical Switch for outdoor lighting automation using space grade sensors, micro controller suitable for outdoor use IP 55 having features Automatic Switching ON at Sunset, Automatic Switching OFF at dawn, No clock setting and time settings wide operating voltage range, high voltage trip and auto reset having specification 230 Volts, 50 Hz load of 12 KW with all connected accessories 3 phase complete all as specified and directed. Note: The power contactors and MCBs (Input-Output) should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade thermoplastic polycorbonate enclosure suitable for 3 phase load of 12 KW all as directed by Engineer in Charge.
Supply & Fixing in replacement of Power Timer contactor, 03 pole, 32 Amps complete all as directed by Engr-in-Charge
Supply & Fixing in replacement of Power Timer contactor, 03 pole, 40 Amps complete all as directed by Engr-in-Charge
Supply & Fixing in replacement of Power Timer contactor, 03 pole, 63 Amps complete all as directed by Engr-in-Charge
S&F in replacement MCB 10 KA, C curve, 230 Volts rupturing capacity of the rating SP 6-32 Amps complete all as directed by Engr-in-Charge
S&F in replacement MCB 10 KA, C curve, 230 Volts rupturing capacity of the rating TPN 32-40 Amps complete all as directed by Engr-in-Charge
S&F in replacement MCB 10 KA, C curve, 230 Volts rupturing capacity of the rating TPN 63 Amps complete all as directed by Engr-in-Charge
S&F pole box for street light dust and vermin proof make Sintex model GSJB 3020 complete with aluminum bus bar 04 nos. of capacity 200 amps on epoxy insulators including one MCB SP C series 06 amps 10 KA capacity for security light connection including suitable clamps & suitable size brass chrome plated glands-02 nos at bottom for cable entry and exit complete all as specified and directed. Note:- All cable connections shall be made with using suitable cable lugs.
S & F in replacement street light junction box (225x295x122mm) comprising two nos aluminium bus bars of suitable size mounted on epoxy insulators with holes for incoming and outgoing cables, cable gland suitable for pole mounted outdoor type having IP-66 protection complete with FI clamp 40 x 4mm with nuts, bolts & washers including provision for inserting copper wires complete all as directed by Engr-in-Charge. Note:- All cable connections shall be made with using suitable cable lugs
Supply only for 2 core PVC insulated copper conductor cable of size 1.0 sqmm 1100 volt grade (For street light connection from looping box) all as specified
M&L in replacement of post top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distirbution, spun aluminium landscape luminaire with high power LED as light source light Fitting with LED 40 Watts including and accessories complete incuding cable connector, PCC work & all type of fixing arrengement all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement for Integral LED 7.5 watt, red / yellow aviation light luminaires comprising aluminium housing, with polycabonate enclosure, 302 LED are provided complete all as specified and directed by Engineer-in-Charge.
Supply and fixing Energy saving & Enviroment friendly LED street light fittings made out of pressure die cast anodized alluminium housing having capacity 60 watt with high efficiency polycarbonate UV stablized cover with integrated lens to ensure asymmetrical light and overall IP protection IP 65 or better complete all as specified & directed by Engineer in Charge.
Supply and fixing Energy saving & Enviroment friendly LED Building Security light fittings made out of pressure die cast anodized alluminium housing having capacity 45 watt with high efficiency polycarbonate UV stablized cover with integrated lens to ensure asymmetrical light and overall IP protection IP 65 or better complete all as specified & directed by Engineer in Charge.
All as per item no. 27 here in before but LED Street light fitting of 90 watt
All as per item no. 27 here in before but LED flood light fitting of 100 watt
All as per item no. 27 here in before but LED flood light fitting of 120 watt
All as per item no. 27 here in before but LED flood light fitting of 150 watt
M&L in replacement for mounting bracket made out of galvanized iron medium grade of 40 mm bore of pipe bended into required shape and size of 0.90 mtr including necessary Flat iron clamps made out of 25x4mm flat iron, nuts, bolts & washers suitable for steel tublar pole/on wall and painting of clamps, brackets etc complete including taking out old unserviceable brackets as directed
M&L in replacement of Garden light Fitting Integral Bollards decorative luminaire energy saving environmental friendly, long life aesthetically designed aluminium landscape luminaire diffused lighting with high power LED as light source 13W, 4000K(500mm) and accessories complete incuding cable connector, MS shunken box & bakelite sheet of size 7"x4", PCC work & all type of fixing arrengement all as specified and directed by Engineer-in-Charge.
M&L in replacement for service cable of PVC insulated unsheathed weather proof twin core aluminium solid conductor 6 Sqmm for street light service cable all as specified and directed.
All as per item no. 34 here in before but 10 Sqmm--ditto--
Taking down/ getting out carefully old serviceable/ unserviceable LT under ground cable of size 10 sqmm, 2 core to 50 sqmm, 3.5/4 core, from trench/ floor or fixed on walls or laid in duct/ pipe, any size and core, kept in safe custody for reuse and re-laying the same serviceable cable after fault rectification in existing position with supply & fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at site complete all as specified and directed by Engineer-in-Charge. Note : Earth work (Excavation, returning filling, removal, sand, brick will be measured under respective item of BOQ)
Supply & Laying jointing, testing and commissioning LT XLPE insulated armoured LT 1100 volt grades heavy duty with aluminium stranded conductor cable ,sizes 35 Sqmm, 3.5 core ,passing through pipes, induct, on poles, in trenches etc including taking down complete all as specified and directed by Engineer in Charge. Note:- The rate of termination and connecting of cable glands including provinding suitable size and nos of lugs by crimping as directed and specified shall be deemed to be included in the item rate.
All as per item no. 37 here in before but cable of size 25 Sqmm, 3.5 core
All as per item no. 37 here in before but cable of size 16 Sqmm, 4 core
All as per item no. 37 here in before but cable of size 16 Sqmm, 2 core
All as per item no. 37 here in before but cable of size 10 Sqmm, 4 core
All as per item no. 37 here in before but cable of size 10 Sqmm, 2 core
All as per item no. 37 here in before but cable of size 4 Sqmm, 2 core
Excavation in trenches in soft/loose soil n. exc. 1.5 meter wide and n. exc. 1.5 mtr depth and getting out, including trimming the sides and forming bottom surface to required levels for fixing pole/stay assembly and laying/taking out cables complete all as specified and directed.
Returning, filling trenches including spreading, levelling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed.
Removing of excavated material (soil) to a distance n. exc. 50 Mtr and dispositing where directed at a level n. exc. 1.50 Mtr above the starting point complete as directed.
M & L for dry, ganga river Sand, cushioning to UG cables (8cm deep before laying of cable and 15 cm deep over the cable) complete all as directed by Engineer in Charge. Note :- Punned thickness only will be considered for payment.
M & L Bricks for protection cover to under ground cable (with old size sub class ‘B’ bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed by Engineer in Charge.
M&L for cutting of PCC/Hard standing/WBM road for passing of LT cable and making good with same existing specifications complete all as specified and directed by Engr-in-charge
Supply & fixing or laying galvanised steel tubing medium grade 40 mm bore (ISI marked) for protection of under ground cable on poles/ walls under road crossing etc of following sizes including dismantling and taking down existing pipe all as directed by Engineer in Charge.
M & L for boring in any type of soil under road 60cm below the top surface of road complete for passing through 40mm to 50mm dia GI pipe and filling earth after laying of pipe including disposal of surplus soil complete all as specified and directed. NOTE :- Pipe will be measured and paid for separatily. Any damage to existing cables of any type will made good by the tenderer without any extra payment.
M&L for preparation of exposed steel surface of steel tubuler pole (9 mtr long) by scrapping, cleaning and painting by one coat of aluminium paint after preparation , including primer of the steel surfaces including painting to pole with two coat blue & white paint in strap alternatively all round the poles and writing pole No. Hight of the strap shall be as per standard and Nos of strap shall be 05 Nos. Note: Pole number shall be recored in MB for payment purpose.
Triming of tree branches any type & size to clean the route of HT/LT over head lines arround the 3 Mtr from the external conductors including removing the cut branches from site and depositing at places all as directed by Engr in Charge.Note : One span from pole to pole distance not exceeding 35 & 45 Mtrs of LT & HT shall be considered as one unit.
S&F in replacement of MCCB ,4pole, 415 Volt grade, AC 63amp 25KA and Ics =100% of Icu with adjustable thermal release including taking down old unserviceable MCCBs all as directed by Engineer in Charge.
All as per item no. 54 here in before but MCCB, 4 pole, 415 V, 125 Amp
All as per item no. 54 here in before but MCCB, 4 pole, 415 V, 160 Amp, 36KA
Supply & fixing in replacement, LT Steel tubular swaged poles/ cemented poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31 (9.0 metres long) all as specified and directed by Engineer in Charge. Note :- 1. Rate quoted by contractor deemed to be inclusive of required excavation work and painting strips in blue and white colour upto height as per standard. 2. PCC and foundation shall be measured and paid seperately under seperate items 3. Old LT steel pole if retrieved , shall be deposited to MES store
M&L for plain cement concrete (1:3:6) Type C2 using 40 mm graded stone aggregate complete all as specified and as directed by Engineer- in -Charge.
M&L for cement concrete 1:2:4 Type B 2 using 40 mm graded stone aggregate complete all as specified and as directed by Engineer- in -Charge.(For LT pole foundation base, coping new and demolished one)
Supply, fixing, installation and testing LT pannel out door (Kiosk type) type, wheather & vermin proof MS sheet housing 3.15mm thick, double door front & rear openable type mounted on 50 X 50 X 6mm to cover all corner and standing legs (min 75cm) of angle iron work, with coloured horizontal Tinned aluminium bus bar 4 pole, mounted on insulators of rating 200 Amps, one MCCB, 4 pole 100 Amps, 25 KA 415 volts at incoming supply. The panel size not less than 600x450x300mm with cable gland, duly powder coated, locking arrengement complete and with and including grouting in PCC block of suitable size all as directed by Engr-in-Charge.
M&L for cutting of crawles along the electric pole of any type and height around the 2 Mtr from the pole including removing the crawler from site and depositing at places all as directed by Engr in Charge.
S&F rigid non metallic medium white / ivory PVC conduit medium grade ISI marked of size not less than 20 mm dia all as directed by Engineer-in-Charge. (For protection of PVC cable ) Note : PVC pipe shall be clamped over LT pole with suitable size iron clamp and clamp will be measured and paid under respective item of structural steel work
M&L for clamps and bore covers from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and including two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
M&L for earthing complete with galvanised MS earth plate of size 600 x 600 x 6mm thick burried directly in ground not less than 2.25 Mtr below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150mm in layers, connected by GI earth wire 4 mm thick, soldered and revetted to earth plate. GI earth strip will be protected by using 40mm bore GI pipe (light grade) from test point to main board. The earthing includes PCC pit chamber in PCC (1:2:4) type B1 using 20mm graded stone aggregate, RCC pit cover in PCC (1:2:4) type B0 using 12.5mm graded stone aggregate, and frame, watering pipe 20mm bore, funnel with wire mess with necessary earth work including disposal of surplus soil to a distance not less than 50 Mtr etc complete all as specified and shown in electrical plate No 3 of SSR Part-I (2009). Note : - Rate quoted by contractor deemed to be inclusive of Earth conductor upto 7.5 RM
santosh electronics (BID ID -3131750)
SAKSHAM SUPPLIERS BUILDERS (BID ID -3131694)
VEE KAY ENTERPRISES (BID ID -3138688)
M/s A S Electrical (BID ID -3137628)
A.B.Enterprises (BID ID -3130541)
PAWAN COOL CORPORATION (BID ID -3120413)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .