Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 CrAccepted-AOC | ₹2.2 Cr | L1 | Accepted-AOC AOC |
| 2 | L2₹2.5 Cr+₹25.2 L (11.2%)Rejected-AOC | ₹2.5 Cr+₹25.2 L (11.2%) | L2 | Rejected-AOC Rejected being Other Than lowest |
| 3 | L3₹3.0 Cr+₹71.9 L (32.0%)Rejected-AOC V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | ₹3.0 Cr+₹71.9 L (32.0%) | L3 | Rejected-AOC Rejected being Other Than lowest |
| 4 | L4₹3.2 Cr+₹91.8 L (40.8%)Rejected-AOC | ₹3.2 Cr+₹91.8 L (40.8%) | L4 | Rejected-AOC Rejected being Other Than lowest |
Tender Value
₹2.4 Cr
EMD Value
₹3.1 L
Closing Date
15 Feb 2020, 6:00 pmClosed
Chef Engineer
HQ CE 31 Zone PIN 914 631
CONSTRUCTION OF LEFT OVER WORK OF SEWAGE TREATMENT PLANT (STP) FOR CENTRAL SEWAGE SCHEME FOR OTM ACCN AT JAK LI RC AT OLD AIR FIELD, SRINAGAR
2020_MES_315784_1
CONSTRUCTION OF LEFT OVER WORK OF SEWAGE TREATMENT
Open Tender
Civil Works
Lump-sum
730 days
Old Air Field Srinagar
Ref NIT
8 documents required · 8 mandatory
₹2,000
GE 970 EWS
₹3.1 L
Yes
19 Mar 2020
18 Jan 2020
17 Feb 2020
18 Jan 2020
15 Feb 2020
5 Feb 2020
22 Jan 2020 - 27 Jan 2020
27 Jan 2020
Amount
Sch 'A' Part-I (Bldg Work) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Design, Supply, Installation, Testing and Commissioning of Sewage Treatment Plant based on Moving Bed Bio-reactor (MBBR) attached growth technology to include entire civil and electromechanical works for complete functioning of STP along with requisite electrical control panels, all interconnecting pipes, cables and wires related to plant of capacity 350 m3/day. The waste water coming out of plant is to be recycled for horticulture, MT wash etc including all connected civil works complete all as specified in Sch "A' Note No 24 complete all as mentioned in relavent clauses elsewhere.
Construction of service station comprising pump house cum DG set room, Lab room, store room & duty room with toilet with permanent specification in RCC framed constr in M-25 design mix, earth quake resistant, complete all as specified and shown on drawings.
Total amount of Sch 'A' Part-II (Sec-I) ( Ext Water Supply) carried forward from pre-priced Schedule.
Sch 'A' Part-II Sec-II (Ext Water Supply) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Ductile iron pipe 100mm class K-7 ISI marked suitable for tyton joint joint in any length laid in trenches, complete all as specified and directed. Note :- Cost of rubber tyton joints is included in overall quoted rate.
Ductile iron pipe 80mm class K-7 ISI marked suitable for rubber gasket joint in any length laid in trenches, complete all as specified and directed. Note :- Cost of rubber tyton joints is included in overall quoted rate.
Ductile iron fittings ISI marked suitable for DI pipes of class K-7 viz, bends, tapers any type (straight bend increasing, decreasing or double socket etc) Tee pieces single branch Y junction, double branch cross, collars, caps and plug, tail pieces etc for 80 mm , 100 mm , 150 mm dia pipe complete including provn of rubber tyten joints all as specified and directed. Note for Item No 6 to 8 :- (i) DI fittings shall be of same make as DI pipe class K-7 or as per make recommended by manufacturer of pipe , ISI marked & including provision of rubber TYTON joints. (ii) Make of DI pipe shall be LANCO/Jindal/TATA.
Supply & fixing cast iron foot valve, Conforming to IS- 4038, flanged type complete with rubber gaskets including nuts, bolts, washer etc of size 100 mm dia.
Valve pit of size 90 cm x 90 cm x 90 cm (internal dimensions) ,stone/ brick construction, including all necessary excavation and earth work in any type of soil, returning, filling in disposal of surplus spoil to distance not exceeding 50 m and depositing where directed, PCC in foundation of the mix (1:2:4) type D-2, stone masonry in cement mortar (1:4) rendering 12 mm thick in cement mortar (1:4) internally, finished even and fair and flush pointing to external surface as the work proceeds in the same mortar. Mild steel angle iron 40 x 40 x 6mm frame MS sheet cover 3.15 mm thick with handle and locking arrangement, painting all the exposed MS work with two coats of synthetic enamel paint of the that as approved by the GE over a coat of red oxide primer and painting all the MS work embedded in PCC with two coats of black bituminous paint complete all as specified and shown on drawing.
Supply, Installation and testing of electric driven centrifugal pumping set, 3 phase 415 volts of cap 15 HP 40 mtr delivery head and 6 mtr sunction head with minimum 6m suction head with bronze impeller coupled with electric motor including PCC foundation pumping set will be installed on MS channel 100 mm size duly grouted in PCC with suitable size of nuts, bolts for vibration free pumping set complete all as specified and directed . Note :- Rate shall be inclusive of PCC foundation, MS channel & MS nuts & bolts).
Supply and fixing Cast iron air valves with two air outlet 150mm dia bore ( ISI Marked ) including all jointing material such as rubber gaskets nuts, bolts and washers etc, complete all as specified and directed.
Supply, install, testing and commissioning of CPRI approved LT panel board, indoor type, with front and back door openable type fitted with nuts, botls and washers fitted with knob and hinges, floor mounted, fabricated out of 2.00 mm thick MS sheet, LT panel shall be totally enclosed weather proof and vermin proof with front and rear opening with IP-65 protection as per IS-8623 duly powder coated incl connection, RYB, insulated with different colour code and sleeved insulator complete pre-wired and cable connection with copper conductor wire upto copper bus bar complete with frame for mounting of panel 45 cm above the ground level, made out of 50 x 50 x6 mm thick MS channel and grouting by providing PCC 1:3:6 type C-1, using 20 mm grade crushed stone aggregate including all incoming and outgoing cable connection with suitable size of copper lugs/gland complete all as specified and also comprising of the following:- (a) MCCB 63 Amps 25 KA four pole 415 Volts - 01 No (b) MCCB TP 32 Amps, 25 KA - 02 Nos (c) MCB DP 32 Amps, 10 KA - 01 Nos (d) Indicators RYB - 01 Set (e) Copper strip bus bars sleeve insulated 200 Amps capacity TPN mounted on epoxy insulators - 01 Set (f) Digital voltmeter 0-500 V range 96 x 96 Sqmm size with In built VSS - 01 No (g) Digital ammeter 0-100 A range 96 x 96 Sqmm size with CTs and In built ASS -02 Nos (h) Internal wiring of the panel board with single core copper cable PVC insulated of suitable size and control fuses. (j) Fully Automatic Star -Delta Starter of Cap-15 HP ,Three Phase,415 volts with single phase preventer complete.-02Nos. Make-HAVELLS/SIEMENS/ L&T. (k) Cable entry glands and two Nos earthing terminals.
Total amount of Sch 'A' Part-III Sec-I (Internal Electric Supply) carried forward from pre-priced Schedule.
Sch 'A' Part-III Sec-II (Internal Electric Supply) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
LED light fitting 1x10 Watt bulkhead luminaries with LED 10 Watt with lamp holder, etc complete with all accessories and including connecting up with three core flexible copper conductor cable with of size 1.0 Sqmm of 230 Volts, 50 Hz. Complete all as specified. Cat part No SLEBH 10 W Make Surya or equivalent.
Ceiling fan of size 1200 mm having (BEE 5 Star rating) sweep complete and connecting up including provision of three core 1.0 Sqmm copper conductors cables from ceiling rose/connector to Fan. Cat part No ES-50 5 White/Ivory of make Havells or equivalent in Bajaj/CG.
Exhaust fan ventilating type of plastic body of size 250 mm sweep complete with all accessories and including connecting up with three core twisted flexible copper conductor cable of size 1.0 Sqmm of 230V, 50 Hz of Cat part No DXWHT/BLK Make Havells or equivalent in Bajaj/CG.
18 W LED tube(4 ft) having minimum 2000 lumens with extruded engineering plastic housing polycarbonate diffuser, G-13 polycarbonate end cover, the LED with 120 degree vie angel>120 lumen/watt, lumen maintenance 70% at 50000 hrs colour temperature of 5000-6500 K<70 colour rendering the driver must be integralAPFC and constant current type having THD<20% and power factor>0.9 with reverse polarity protection and open circuit protection. Make : Surya Model No SLE TL DS 18 PC including 1x18 watt LED box type fixture suitable for 18 W LED tube comprising of pre coated MS box complete with all accessories Make : Surya Model No SUB 118 T8 LED or equivalent in Bajaj/Havells/Philips.
MCB SP 240 V, 50 Hz, 10 KA of rating (0.5-5 Amp) made from moulded self exinguishing thermostate plastic and suitable for C curve Cat Part No. CSMBS1C5 of make: C&S or equivalent in Havels/Legrand.
Single pole MCB 6 to 32 Amps 240 V, 50 Hz AC made from moduled self exitinguising thermostate plastic and suitable for 'c' curve, 10 KA breaking capacity. C&S Cat part No CSMBS1C6-32 or equivalent in legrand/hager/seimens.
Single pole & Neutral MCB 40 Amps 240 V, 50 Hz AC made from moduled self exitinguising thermostat plastic and suitable for 'c' curve, 10 KA breainig capacity. C&S Cat part No. CSMBS1C40 or equivalent in legrand/hager/seimens.
9W LED with base having minimum 720 lumens input voltage 220 - 240 V, AC-50 Hz PF>0.9, colour temp - 6500K, CRI > 70. Make:- Surya or Equavalent in CG/Philips.
Total amount of Sch 'A' Part-IV Sec-I (Ext Electrification) carried forward from pre-priced Schedule.
Sch 'A' Part-IV Sec-II (Ext Electrification) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply, fixing, testing and commissioning energy saving integral LED street light luminary comprising of epoxy powder coated housing enclosed with glass cover in frame and consisting of 60 watt LED lamps mounted on MCPCB suitable for 32mm OD pipe, ingress protection IP-66LXN, suitable for LED 60 Watt including all standard accessories as per design of manufacturer. Make Make Surya cat part No. SLEUL60W IP 66 LXN
Supplying and fixing brackets for street light fittings made out of 40 mm dia GI pipe Light grade, bent to shape 1.5 mtr long fixed to pole, wall including provision of two sets of clamps made out of flat iron of size 50 x 6 mm including provision of bolts, nuts and washers complete all as specified and directed.
Supply and fixing pole junction box sheet moulded compound (SMC) type with hinged door and locking arrangement of size 300x250x150mm comprising of Aluminum bas bar 63 Amps two Nos, one No SP MCB single pole of capacity 05 to30 Amps 240 volts 9 KA and single core PVC FRLS single core copper conductor 2.5 Sqmm for connection from junction box to street light complete , including MS clamps fabricated from 25x3mm MS flat iron, nuts , bots etc for mounting all as specified and as directed.
M&L in door LT Cubical panel board Indoor Type , front and rear opening with dust proof vermin proof made of 2.00 mm thick CRCA sheet steel factory made . CPRI approved suitable for operation on 415 volts ,50 HZ, AC supply conforming to IP-65,including suitable size of four pole aluminum bus bar complete with frame for mounting of panel 45 cm above the ground level ,made out of 50x50x6mm thick and grouting by providing PCC 1:3:6 type C-1,using 20mm grade crushed stone aggregate and painting with spray painting with seven tank process by using superior quality paint including provision of the following item :- (a) MCCB 4 pole adjustable and thermal magnetic setting, 125 Amp, 415 Volts, 35 KA - 01 No (incoming) (b) MCCB 3 pole Fixed type,63 Amp, 415 V, 25 KA - 03 Nos (outgoing) (c) MCB 2 pole,32 Amps, 230 V, 10 KA - 01 Nos (outgoing) (d) On Load changeover switch, 125 Amps, 415 V, 4 pole - 01 Nos (e) Copper bus bars sleeve insulated 200 Amps capacity TPN mounted on epoxy insulators - 01 Set (f) LED indicator lamp RYB (Set of 3) - 01 Set (g) Digital voltmeter 0-500 V range 96x96 Sqmm size with inbuilt VSS - 01 No (h) Digital ammeter 0-200 Amps range 96 x 96 Sqmm size with CTs and in built ASS- 01 No (j) Internal wiring of the panel board with single core copper cable PVC insulated of suitable size and control fuses. (k) Cable entry glands and two Nos earthling terminals. (l) Interconnection of bus bar and MCCB with suitable size of copper cable and fixing material and color coat including PVC sleeves etc.
Supply. Installation, testing and commissioning of diesel engine driven generating set to give out put 100 KVA or nearest higher size at 415 volts, AC supply 3 phase 50 Hz four wire directly coupled to diesel engine water cooled with radiator mounted on common base plate complete with inbuilt tank of capacity as per manufacturers specifications vibration damper and other accessories all specified and comprising of as per Particular Specification Clause No 26.
Supply and fixing Rubber Matting ISI marked 12mm thick of 1 x2M size to cover the area in front of in door control panels and LT equipments complete all as specified and directed by Engr-in-Charge.
Total amount of Sch 'A' Part-V (Sewage Lines) carried forward from pre-priced Schedule.
Total amount of Sch 'A' Part-VI (Protective Work) carried forward from pre-priced Schedule.
Total amount of Sch 'A' Part-VII (Fencing/Gate/Compound Wall Works) carried forward from pre-priced Schedule.
Total amount of Sch 'A' Part-VIII (Internal Water Supply) carried forward from pre-priced Schedule.
Total amount of Sch 'A' Part-IX (Excavation and Earth Work for Site Clearance) carried forward from pre-priced Schedule.
Sch 'A' Part-X (Manning and Operation of STP) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Manning & operation of STP of capacity 350 Cum/day and all associated connected accessories at JAK LI centre, Old Air Field Srinagar to keep installations in functional condition in three shift per day (each shift 08 hrs)including sunday and holidays i.e from 0800 Hrs to 1600 hrs, 1600 hrs to 2400 hrs & 2400 hrs to 0800 hrs including maintaining log sheets and other periodical, maintenance record complete all as specified and directed by employing qualified staff/Engr-in-charge :- (a) 03 Nos. of Operator-cum-technician per day i.e One operator cum technician per shift of 08 hours. (b) 01 No. of helper in three shift (each shift 08 hrs.) i.e0800 hrs to 1600 hrs, 1600 hrs to 2400 hrs and 2400 hrs to 0800 hrs. (c) One no safaiwala (sweeper) in general shift (0800 hrs to 1600 hrs). (d) Mechanic required for day to day maint incl oiling and greasing and replacement of defective parts as per manufacturer instructions. No extra cost shall be given by the Deptt. However fuel/electricity and water if reqd by the contractor shall be provided by the Deptt on free supply basis.
Ser Item No 38 Contd.... NOTE-(A) SCOPE OF WORK - the manning and operation schedule mentioned above includes the following- (a) Removing of materials arrested at bar screen. (b)Removing of oil floating at surface. (c) Change over from one blower to other blower as per requirement. (d) Cleaning of air filter of blower regualarly on requirement basis. (e) Applying grease to all motor blower periodically including supplying of suitable quantity of grease (f) Draining of sludge from MBBR reactor once in a month. (g) Removing of sludge from tube settler depending upon actual load. (h) maintaining of log book for record of operation of plants including cost of stationary. (j) Back wash of dual media filter and activated carbon filter weekly or on required basis. (k) Cleaning of inlet and outlet mesh box of MBBR reactor weekly (l) Draining of burnt out lubricant oil and refilling of appropriate lubricant oil in air blower after 2000-2500 Hrs of operation incl cost of lubricant.
Ser Item No 38 Contd.... (B) The contractors quoted rates for the above item shall also be deemed to include the cost of following : (a) Maintenance of internal and external area of plant. (b) Watch and ward and care of Govt assets and equipment of the plant. (c) Maintennce of the saftey and security measure of the plant. (d) Keeping the installation neat and tidy. (e) In case of failure of main electric supply, Generator electric supply shall be used by the operator on the requirement basis. (f) All material brought at site for use shall be entered in MB for record purpose duly supported with releveant purchase voucher and test (g) Disposal of treated sewage/sludge as directed by the Engr-in-Charge.
M/s Hafizullah Beigh
Electromech Engineers
RYSA INFRATECH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .