Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.9 LAccepted-AOC NO 229 ANGAPPAN STREET MITTANAMALAI AVADI IAF CHENNAI 600 055 | CHENNAI | CHENNAI | TAMIL NADU | 600055 | ₹14.9 L | L1 | Accepted-AOC BEING L1 ACCEPTED |
| 2 | L2₹15.3 L+₹35,261 (2.36%)Rejected-AOC | ₹15.3 L+₹35,261 (2.36%) | L2 | Rejected-AOC BEING NOT L1 ACCEPTED |
| 3 | L3₹19.0 L+₹4.0 L (26.9%)Rejected-AOC NO 235 PSK ILLAM SANKARAN NAGAR CHINNAMMAN KOIL STREET AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | ₹19.0 L+₹4.0 L (26.9%) | L3 | Rejected-AOC BEING NOT L1 ACCEPTED |
Tender Value
Refer Docs
EMD Value
₹39,000
Closing Date
13 Sept 2021, 6:00 pmClosed
Garrison Engineer, Avadi
Garrison Engineer, Muthapudupet, Avadi, Chennai 600 055
REPAIRS AND REPLACEMENT OF LT PANEL/ FEEDER PILLAR BOX, SMC BOXES, BUS BAR CHAMBERS, LT POLES, EARTHING, FLOOD LIGHT, MCCB, CHANGE OVER SWITCHES, POST TOP LAMP AND ALLIED SERVICES IN AF TECHNICAL AND AF DOMESTIC AREA UNDER GE AVADI
2021_MES_467927_1
8853
Open Tender
Civil Works
Item Rate
270 days
Garrison Engineer, Muthapudupet, Avadi, Chennai
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer, Avadi
₹39,000
Yes
14 Oct 2021
13 Aug 2021
15 Sept 2021
13 Aug 2021
13 Sept 2021
28 Aug 2021
Amount
Material and Labour for plain cement concrete1:3:6 (20mm graded aggregate), type C1 for coping of pole including demolition of old concreate complete all as specified and as directed.
Material and labour for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts suitable for LT of approved of size 20x15 cm including taking down old unserviceable one complete all as specified and as directed.
Supply ,Fabricate, install, connect, test and commissioning LT panel board, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for each switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old panel and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) 3 Phase Flush Mounting Meter, Class 1 meter, 96 X 96 mm 3 Ph 4W 240V 5A (Multifunction meter) -1No (iii) INCOMING : MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 Nos. (IV) OUTGOING :- (a) MCCB fixed thermal magnetic release type of capacity 100 amps, 4 pole, 36 kA.- 3 Nos. (b) MCCB fixed thermal magnetic release type of capacity 63 amps, 4 pole, 415 Volts, 50 Hz , 16kA, - 1 Nos (c) Three phase contactor with timer for security light of capacity 20 Amps - 01 Nos. Note : All MCCBs shall be front handle operated.
Supply ,Fabricate, install, connect, test and commissioning LT panel board, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for each switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old panel and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) 3 Phase Flush Mounting Meter, Class 1 meter, 96 X 96 mm 3 Ph 4W 240V 5A (Multifunction meter) -1No (iii) INCOMING : MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 Nos. (IV) OUTGOING :- (a) MCCB fixed thermal magnetic release type of capacity 100 amps, 4 pole, 36 kA.- 2 Nos. (b) MCCB fixed thermal magnetic release type of capacity 63 amps, 4 pole, 415 Volts, 50 Hz , 16kA, - 1 Nos (c) Three phase contactor with timer for security light of capacity 20 Amps - 01 Nos. Note : All MCCBs shall be front handle operated.
Supply ,Fabricate, install, connect, test and commissioning Busbar chamber, powder coated, outdoor weather proof type, compartmentalised fabricated with 3 mm thick CRCA steel and suitable sized pressed steel frame work, top with sloping canopy, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit , chamber for aluminium busbars, separate compartment for switch gear, louvers and air vent for natural air flow, holes drilled for connection including suitable angle iron/flat iron frame work/ supports, excavation, earth work, PCC foundation etc., as required with and including following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars including taking down the old busbar chamber and demolition of old plain cement concrete complete all as specified and comprising of the followings:- (i) 4 Nos busbar of equal size of Aluminium conductor with PVC coloured heat shrinkable type sleeves continuous rating of 400 Amps mounted on fibre reinforced insulator.(1set), with LED indication lamps-03 Nos for RYB phases on incoming side. (ii) MCCB fixed thermal magnetic release type of capacity 200 amps, 4 pole, 36 kA.- 1 Nos. Note : MCCB shall be front handle operated.
Repair and welding work the existing panel board door with provision of new door by taking down the old rusted door and provided hinges for door, if necessary and lock arrangement with provision of pad lock with keys and cleaning the welding surfaces by rubbing and polishing with two coat of synthetic enamel paint to match with existing colour all as specified and as directed.
Earthing complete with galvanised steel earth plate eletrode 60xm x 60cm x6 mm thick buried directly in ground (earth plate not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised iron earth strip 25x4mm by means of bolts, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 15mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x6mm and handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering of suitable length placed on top edge of earth plate, charcoal and common salt filling, with fixing arrangement, funnel, wire mesh and earth work in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 meterrs, complete all as per plate No-3, SSR-2009 Part-I and connecting to existing earth test point all as specified or indicated including testing on completion.
Earthing complete with galvanised steel earth plate eletrode 60xm x 60cm x6 mm thick buried directly in ground (earth plate not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised iron earth lead 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 15mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x6mm and handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering of suitable length placed on top edge of earth plate, charcoal and common salt filling, with fixing arrangement, funnel, wire mesh and earth work in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 meterrs, complete all as per plate No-3, SSR-2009 Part-I and connecting to existing earth test point all as specified or indicated including testing on completion.
Material and Labour for preparation of old painted surfaces ,removing dust and other deposited materials by scraping from LT panel inner and outer surface of front and rear doors including all compartment of MCCBs,busbar chamber,cable tray etc with one coat of same existing colour synthetic enamel paint by means of spray gun complete all as specified and as directed.
Material and Labour for preparation of old painted surfaces ,removing dust and other deposited materials by scraping from busbar chamber inner and outer surface of front and rear doors including compartment of MCCB,busbar chamber with one coat of same existing colour synthetic enamel paint by means of spray gun complete all as specified and as directed.
Material and Labour for MCCB 160 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 36 KA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
Material and Labour for MCCB 200 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 36 KA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
Material and Labour for MCCB 250 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 36 KA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
Material and Labour for MCCB 400 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 36 KA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
Material and labour for LED Driver, AC, 85 to 265 Volts range, suitable for 20 watts post top lantern including taking down the old one complete all as specified and as directed.
Material and labour for LED Driver, AC, 85 to 265 Volts range, suitable for 120 watts street light including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED flood light fitting,230 V,AC, 120 W, LED, outdoor type,CCT not less 6000K high pressure die cast aluminium housing ,heat resistance toughened glass with frame IP 66 protection LED lumen efficacy not less then 120 lumen/watt, reflector lenses for uniform light distribution on each LED with driver,lamp, bracket with impact and corrosion resistant including thermal management in multiple optics complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed .
Supply and Fixing of LED post top lantern,230 V,AC, 20 W, LED, outdoor type,360 degree indirect light,CCT not less 6000K high pressure die cast aluminium housing ,heat resistance toughened glass with frame IP 65 protection LED lumen efficacy not less then 120 lumen/watt, reflector lenses for uniform light distribution on each LED with driver,lamp, bracket with impact and corrosion resistant including thermal management in multiple optics complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed .
Supply and Fixing MCB,240V,10KA,'B' curve,single pole,current carrying capacity 5Amps, suitable for fixing in SMC box for control street/flood lights and making connections including taking down the old one complete all as specified and as directed .
Supply and Fixing of pole mounted Sheet Moulded Compound(SMC) Box weather proof type with hinged type door off white color of size 250x250x155 mm comprising of 1 No MCB 6A and suitable size Aluminium busbar 3 rows with terminals,1 No bakelite base neutral link and 01 No earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs complete fixed on pole with suitable clamps, bolts and nuts including taking down the old one complete all as specified and as directed.
Cutting/clearing and removing the vegetation/bush/creepers growth any nature/type around/on the electric panel/feeder pillar box/busbar chamber so as to keep clean the area for easy access to carry out repair/maintenance works in electric panel/feeder pillar box/busbar chamber etc, removing from site and throwing out at a place where directed at distance not exceeding 250mtr away complete all as specified and as directed.
Finding and rectification of electrical fault by checking of external/internal(LT) elect supply feeder, street light feeder,under ground cables using elect tools, equipments and safty devices after arranging elect shut down of feeders from sub station to remove elect faults like tightning of loose connection,removing of any electric short,meggring of cable,excavation of soil for removing of faulty cable on a particular span and relaying of cables after removing of fault, re-tightning of cable lugs etc all as required at site complete all as specified and as directed. Note:- (i) The electrician employed for the purpose will be highly skilled along with one mate and should have all necessary tools and safty devices. (ii) Any major materials used for rectification of faults like Cables,MCB/MCCB of any size/type etc will be measured and paid seperately . (iii) Rate including hiring of fault finding equipments and Earth Work. (iv) Works should be completed with in 03 hrs
Supply and fixing Indicator lamp of any type / model / capacity in LT panels panels including taking down old unserviceable one complete all as specified and as directed.
Supply and fixing Multifunction meter with RS port of any type / model / capacity in LT panels including taking down old unserviceable one complete all as specified and as directed.
M/s Bakiyalakshmi Enterprises
PSK Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .