Loading…
Loading…
Tender Value
₹57.6 L
EMD Value
₹1.1 L
Closing Date
31 Aug 2026, 6:00 pm6d left
HQ CWE (U) Delhi Cantt-110010
HQ CWE (U) Delhi Cantt-110010
REPAIR AND MAINT OF 33 KV AHR R GRID INCLUDING 33 KV GIS AND 11 KV AIS PANEL REPAIR AND MAINT OF 8/10 MVA POWER TRANSFORMER 11 KV RMUS AND CONNECTED ITEMS UNDER AGE (SLDC) ELECTRIC SUPPLY UNDER GE (U) ELECT SUPPLY DELHI CANTT-10
2026_MES_782617_1
CWE(U)/D-10/2026-27
Open Tender
Civil Works
Works
180 days
HQ CWE (U) Delhi Cantt-110010
As per tender documents
9 documents required · 9 mandatory
₹1,000
GE (U) Elect Supply
₹1.1 L
Yes
4 Aug 2026
4 Aug 2026
7 Sept 2026
4 Aug 2026
31 Aug 2026
25 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 33 KV HT cables of different sizes from both ends, removal of fault, Re-connections and testing of cables after removal of fault complete all as specified and directed.
Note-: (a) 33 KV HT & 11 KV HT cable & joints shall be measured and paid for seperately under respective items of schedule.
(b) Retrieved old serviceable cable cover will be laid in trenches for cable protection. If extra PCC cover and sand required at site shall be measured and paid separately under respective items of BOQs.
(c) Excavation and earth work will be measured and paid for seperately under respective items of schedule. | 15 | Each job | - | - |
| 2 | Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 400 Sqmm 3 Core complete all as specified and directed. | 10 | Each | - | - |
| 3 | Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 400 Sqmm 3 Core complete all as specified and directed. | 4 | Each | - | - |
| 4 | Material and labour for emergency maintenance work of 33 KV HT underground lines by deploying skilled electricians and labours at faulty site having team of minimum 6 persons and transportation including hydraulic machine and other tools and plant required at site for fault rectification per call complete all as specified and directed.
Note:- Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdown . In case the rep or contractor shall not come to the site of breakdown and start attending breakdown within 1.00 hour a penalty of Rs 1000/- per fault per hour will be imposed over contractor and will be deduct from his dues. | 11 | Each Job | - | - |
| 5 | Material & labour for repair /overhauling of OLTC ( On load tap changer ) of 33KV/11KV Power transformer of capacities 8/10 MVA at site by carried out following work of CG make :-
(a) Opening of top plate of OLTC.
(b) Draining out of transformers oil from the OLTC.
(c) Stoping of leakage of oil from main shaft of OLTC including renewal of oil seal and all gasket of OLTC.
(d) Checking /servicing of moving and fixed contact of OLTC and resistence test of contact.
(e) Flushing of OLTC assembly with hot new oil and removing of sludge.
(f) Filling of new transformer oil in OLTC .
(g) Tightening of all tapping leads and connections.
(h) Refixing of top plate of OLTC in original position after overhauling.
(i) Electrical testing of manual/auto operation of OLTC.
Note :- Transformer oil as required shall be measured and paid separately under respective item No 44 here-in -after as supply only. | 2 | Each Job | - | - |
| 6 | Material and labour for servicing /testing of 33 KV GIS control panel including indoor CT, PT and relays system in control panel of indoor SF 6 Gas Circuit Breaker of capacity 1250 Amps and rating 36 KV by the authorised agency. The complete as details mentioned as under:-
(a) Details of servicing of breaker :-
(i) Checking of Closing/Tripping coil assembly
(ii) Adjustment of mechanism if required.
(iii) Clean the circuit breaker to remove dust and dirt.
(iv) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(v) Check for rust and wear.
(vi) Checking of spring charge mechanism
(vii) Visual check for rust and deformation.
(viii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(ix) Check for loosened connections, rust, damaged lead wires.
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil.
(xii) renewal of Dashpot/shock absorbers .
(xiii) renewal of carbon brush of spring charging motor
(xiv) Cleaning of porcelain bushing
(xv) Checking of limit switch | 6 | Each Job | - | - |
| 6.01 | (b) The following test shall be carried out:-
(i) Primary Injection Test of outdoor CT / PT
(ii) Closing & Opening Timing Test for all three poles.
(iii) IR Test with megger in open and closed condition.
(iv) Contact resistance test for all three poles
(v) Closing coil resistance
(vi) Tripping coil resistance.
(c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :-
(i) Over current and earth fault relay
(ii) Line diffrential relay
(d) Testing of followig Aux relay:-
(i) DC Supply supervision relay.
(ii) Trip Circuit suprvision relay
(ii) SF 6 gas pressure low.
(iii) PT Fuse failure relay
(iv) Master trip relay
(v) Under voltage relay
(vi) Over voltage relay | - | - | - | - |
| 7 | Material and labour for servicing /testing of transformer breaker/control panel including outdoor CT, PT and relays in control panel of indoor 33 KV GIS breakder Panel of capacity 1250 Amps and rating 33 KV complete as details mentioned as under:-
(a) Details of servicing of breker :-
(i) Checking of oil level in each pole
(ii) Checking of visible oil leaks
(iii) Cleaning of porcelain bushings
(iv) Checking of oil leakage from oil dash pot in operating mechanism
(v) Checking of contact burning
(vi) Cleaning and lubricating
(vii) Checking/tightening of all electrical terminals and earth terminals and earth connections.
(viii) Checking of auxiliary switch
(ix) Checking of limit switches and friction clutch.
(x) Checking of closing/tripping coils
(xi) Checking of spring chargingmechanism
(xii) Adjustment of mechanism if required.
(xiii) Check for rust and wear.
(xiv) Visual check for rust and deformation.
(xv) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(xvi) Check for loosened connections, rust, damaged lead wires.
(xvii) Checking of control circuit & tighten the connections if any.
(xviii) renewal of Dashpot/shock absorbers .
(xix) renewal of carbon brush of spring charging motor | 2 | Each Job | - | - |
| 8 | Material and labour for epoxy coating on CT, PT, insulators in 11 KV VCB panels complete all as specified and directed. | 12 | Each Job | - | - |
| 9 | Material and labour for servicing /testing of breaker/control panel including CT, PT and relays in control panel of VCB of capacity 1250/800/630 Amps and rating 11 KV complete as details mentioned as under:-
(a) Details of servicing of breaker :-
(i) Adjustment of mechanism if required.
(ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth.
(iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(iv) Check for rust and wear.
(v) Check Spring Tension and pitting of the Cluster Contacts.
(vi) Visual check for rust and deformation.
(vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(viii) Check for loosened connections, rust, damaged lead wires.
(ix) Check whether the contacts are damaged by arcing.
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil.
(xii) Checking of Jaw Contacts Conditions and repair/adjust.
(xiii) renew the jaw contacts,If required.
(xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish.
(xv) renewal of Dashpot/shock absorbers .
(xvi) renewal of carbon brush of spring charging motor | 14 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.46 MB
BOQ_876816.xls
BOQ • 0.70 MB
TPD10.pdf
Tender Documents • 1.56 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].