Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.7 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹37.9 L+₹1.2 L (3.31%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹41.4 L+₹4.8 L (13.0%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹42.7 L
EMD Value
₹85,400
Closing Date
23 Mar 2022, 6:00 pmClosed
GE BHOPAL
GE BHOPAL BAIRAGARH BHOPAL
PROVN OF WIRING AND ELECT CONNECTION ALONGWITH ALLIED ACCESSORIES FOR OFFRS MD ACCN AS AUTH AT SI LINES AND BAIRAGARH
2022_MES_510282_1
8855/E8
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
BHOPAL
AS PER TENDER DOCUMENT
7 documents required · 7 mandatory
₹500
Yes
GE BHOPAL
₹85,400
Yes
8 Apr 2022
24 Feb 2022
25 Mar 2022
24 Feb 2022
23 Mar 2022
10 Mar 2022
Amount
M&L for sub main wiring with approved colour coding as per IS (Red, Black and Green for single phase circuits) with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 6.0 sqmm nominal cross section area and drawing into rigid non metallic PVC conduit, ISI marked, medium grade, inclusive of all fittings such as tees, bends, junction boxes, elbows, saddles, pipe hooks, couples, lock outs, etc. in concealed wiring system by cutting of walls (brick or stone) and making good disturbed surfaces of wall in CM 1:3 and PVC insulated stranded copper conductor of 6.0 sqmm nominal cross section area as earth wire complete all as specified and directed. [Make of Cable : Polycab/ Plaza/ Havells/KEI/V-MARC as approved by GE] Note : (i) Wiring to be done as per approved colour code in IE rule. (ii) Two runs of 6.0 sqmm cable, one run of 6.0 sqmm cable of earth continuity conductor & PVC conduit pipe shall be measured as one unit length.
S&F in replacement sheet metal earth plug & socket, single pole and neutral with and including 1no. single pole MCB 20 Amps 240 volts complete all as specified and directed. [Make:-Legrand Cat No. 607841 or equivalent in L&T/C&S/Havells as approved by GE].
S&F in repairs MCB SP, 240 volts, 10 KA breaking capacity, 'C' curve, of capacity 20 amps including connection with suitable size aluminium / copper lugs complete all as specified and directed. [MAKE:(L&T)/ Siemens/ Legrand/Havells/ Schinder as approved by GE]
S&F in repair sheet metal enclosure for MCB, DB, SPN , 240 Volts, 200 Amps rated busbar, 4 way double door enclosure made up of CRCA sheet, RAL 9003 powder coated, IP 43, including wooden rectangle board of first quality of suitable size for mounting of DB box, complete all as specified and directed. [MAKE:(L&T)/ Siemens/ Legrand/Havells/ Schinder as approved by GE]] NOTE:- MCB shall be measured and paid separately.
S&F in repairs MCB SPN suitable for 240 volts, AC supply 40 Amps, 10 KA breaking capacity, 'C' Curve, including connection with suitable size aluminium/copper lugs, complete all as specified and directed. [MAKE:(L&T)/ Siemens/ Legrand/Havells/ Schinder as approved by GE]]
Supply and Fixing 1100 Volts grade, heavy duty cable, PVC insulated aluminium conductor of size 2 core 10 sqmm stranded, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable flat or circular, complete all as specified and directed.
M&L for sub main wiring with approved colour coding as per IS (Red, Black and Green for single phase circuits) with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 4.0 sqmm nominal cross section area and drawing into rigid non metallic PVC conduit of size 25mm, ISI marked, medium grade, inclusive of all fittings including PVC insulated unsheathed 4 sqmm cable with mulitstranded copper conductor green PVC insulated as continuous earth conductor cable connected to earth dolly, complete all as specified and directed.
M&L for point wiring with 2.50 sqmm (nominal area) FRLS PVC insulated, unsheathed, multi-stranded copper conductor cable, 1100 volts grade, IS 694 marked with valid CML No. drawn in & including non metallic rigid PVC conduit, concealed ISI marked with valid CML No (IS -9537-1983 for conduits and IS- 3419-1976 for conduit accessories) medium grade not less than 20mm diameter with all conduit accessories in concealed wiring system by cutting of walls (brick or stone) and making good disturbed surface of wall in CM 1:3 with mild steel / pressed steel sunken boxes (with earth dolly) duly painted with two coats od anti corrosive paint/ aluminium paint over a coat of red oxide primer externally, covered with 3mm thick laminated hylum sheet cover for fixing of switches, sockets etc, including one run of PVC insulated multi stranded copper conductor 2 sqmm nominal cross sectional area single core FRLS cable as earth continuity wire connected to common earth dolly, complete all as specified and directed. Note : Wiring to be done as per approved colour code in IE rule.
S&F Switch socket combination universal multipurpose 2 in 1, 3 pin type 6/16 Amps flush type, 230 volt AC complete all as specified and directed. MAKE:-ANCHOR (PENTA series) or equivalent in LEADER/ CRABTREE/LEGRAND/HAVELLS as approved by GE
S&F in repair sheet metal enclosure for MCB, DB, SPN , 240 Volts, 200 Amps rated busbar, 8 way double door enclosure made up of CRCA sheet, RAL 9003 powder coated, IP 43, including wooden rectangle board of first quality of suitable size for mounting of DB box, complete all as specified and directed. [MAKE:(L&T)/ Siemens/ Legrand/Havells/ Schinder as approved by GE]] NOTE:- MCB shall be measured and paid separately.
S&F RCBO 30 mA, 40 Amps, SPN complete all as specified and directed. [MAKE:(L&T)/ Siemens/ Legrand/Havells/ Schinder as approved by GE]]
S&F MCB SP, 240 volts, 10 KA breaking capacity, 'B' curve, of capacity 6 to 32 amps including connection with suitable size aluminium / copper lugs complete all as specified and directed. [MAKE:(L&T)/ Siemens/ Legrand/Havells/ Schinder as approved by GE]]
M&L for Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exc 10cm girth complete all as specified and directed.
M/S RAKESH TRADERS
M/s AKG Engineers & Contractors
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .