Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.0 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED BEING L1 BIDDER | |
| 2 | L2₹21.9 L+₹2.9 L (15.5%)Rejected-AOC 93 618 A MOHANTA PARA WARD NO 19 PO DIST JALPAIGURI PIN 735101 | JALPAIGURI | WEST BENGAL | 735101 | L2 | Rejected-AOC HIGHER BID VALUE | |
| 3 | L3₹22.1 L+₹3.1 L (16.5%)Rejected-AOC | L3 | Rejected-AOC HIGHER BID VALUE | |
| 4 | L4₹22.5 L+₹3.5 L (18.6%)Rejected-AOC | L4 | Rejected-AOC HIGHER BID VALUE | |
| 5 | L5₹22.6 L+₹3.7 L (19.3%)Rejected-AOC | L5 | Rejected-AOC HIGHER BID VALUE |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
31 Dec 2022, 6:00 pmClosed
CWE PANAGARH
HQ CWE PANAGARH, MES, PO - PANAGARH, DIST - BURDWAN, WB, PIN - 713420
REPAIR / MAINT AND IMPROVEMENTOF EARTHINGAND LIGHTENING CONDUCTOR OF ZONE 01 TO 13 UNDER GE PANAGARH
2022_MES_567062_1
8832/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
PANAGARH
Pl refer Tender Documents
7 documents required · 7 mandatory
₹500
GE PANAGARH
₹80,000
Yes
18 Jan 2023
2 Dec 2022
2 Jan 2023
2 Dec 2022
31 Dec 2022
17 Dec 2022
Amount
Materials and Labour for earthing with galvanised earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less rhan 2.25 m deep below normal ground level) with top edge of plate not less than 1.5 m below normal ground level, the earth plate surrounded by alternative layer of charcoal dust and salt with thickness of 150 mm to a packed thickness of 150 mm on all sides with and including necessary excavation earth work returing filling in and removal of surplus soil upto 50 m including galvanised iron Strip 25x4 mm bolted and reverted to earth plate at one end and connected to continuous GI strip encased in and including 40 mm dia GI light grade protection pipe, 20 mm dia medium grade watering pipe with all fittings from top edge of earth plate upto 2400 mm above ground level fixed and including 25x 3 mm GI clamp bolts nuts and washer, funnel, wiremesh, PCC (1:3:6) type C1 earthing pit, 75 mm thick RCC cover slab reinforced with 8 mm dia TMT bar 100 c/c both ways including taking out old unserviceable earthing, complete all as specified and as directed. Note :- (i) If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. (ii) Testing to be carried out by the contractor, entered in the eath testing register, prepared and to be maintained by the contractor & submited to department. (iii) T&P and testing instrument(Earth tester) to be provided by the contractor at own cost. (iv) Quoted rate shall be deemed to include the cost of GI Strip upto a distance of 7.5 metres from the earth plate. Strip required beyond the length shall be measured and paid separately
Materials and Labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized steel earth lead wire 4 mm dia by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board, main control board as directed and including necessary excavation earth work returing filling in and removal of surplus soil upto 50 mtr, including 15 mm dia GI medium grade protection pipe, 20 mm dia medium grade watering pipe with all fittings from top edge of earth plate upto 2400 mm above ground level fixed and including 25x 3 mm GI clamp bolts nuts and washer, funnel, wiremesh, PCC (1:3:6) type C1 earthing pit, 75 mm thick RCC cover slab reinforced with 8 mm dia TMT bar 100 c/c both ways complete all as specified and as directed including taking out old unserviceable earthing complete. Note :- (i) If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. (ii) Testing to be carried out by the contractor, entered in the eath testing register, prepared and to be maintained by the contractor & submited to department. (iii) T&P and testing instrument(Earth tester) to be provided by the contractor at own cost. (iv) Quoted rate shall be deemed to include the cost of GI wire and protection pipe upto a distance of 7.5 metres from the earth plate. Strip required beyond the length shall be measured and paid separately
M&L for Chemical copper bonded electrode pipe earthing complete set consist of 40 mm dia ISI marked GI Pipe 2.0 m long with copper strip 25x3 mm encased in and inner space of pipe is filled with highly conductive corrosion resistant chemicals completely sealed, buried directly in ground (earth pit not less than 2.25 m deep below the normal ground level) filling chemical ground enrichment material minimum 25 kg surrounding pipe and mixed properly with water, connected to earth test point including 40 mm dia GI light grade pipe for protection of earth strip and testing complete all as specified and directed by Engr-in-Charge including necessary excavation earth work returing filling in and removal of surplus soil upto 50 mtr including Copper strip 25x3 mm bolted and reverted to copper bonded elctrode pipe at one end and connected to continuous copper strip encased in and including 40 mm dia GI light grade protection pipe, including 25x 3 mm GI clamp bolts nuts and washer, PCC (1:3:6) type C1 earthing pit, 75 mm thick RCC cover slab reinforced with 8 mm dia TMT bar 100 c/c both ways including testing on completion after taking out old unserviceable earthing, complete all as specified and as directed Note :- (i) If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. (ii) Testing to be carried out by the contractor, entered in the eath testing register, prepared and to be maintained by the contractor & submited to department. (iii) T&P and testing instrument(Earth tester) to be provided by the contractor at own cost. (iv) Quoted rate shall be deemed to include the cost of Copper Strip upto a distance of 7.5 metres from the earth plate. Strip required beyond the length shall be measured and paid separately.
Materials and Labour for Chemical GI bonded electrode pipe earthing complete set consist of 50 mm dia ISI marked GI Pipe 2.0 m long with GI strip 32x6 mm encased in and inner space of pipe is filled with highly conductive corrosion resistant chemicals completely sealed, buried directly in ground (earth pit not less than 2.25 m deep below the normal ground level) filling chemical ground enrichment material minimum 25 kg surrounding pipe and mixed properly with water, connected to earth test point including 50 mm dia GI light grade pipe for protection of earth strip and testing complete all as specified and directed by Engr-in-Charge including necessary excavation earth work returing filling in and removal of surplus soil upto 50 mtr including GI strip 32x6 mm bolted and reverted to GI bonded elctrode pipe at one end and connected to continuous GI strip encased in and including 50 mm dia GI light grade protection pipe, including 25x 3 mm GI clamp bolts nuts and washer, PCC (1:3:6) type C1 earthing pit, 75 mm thick RCC cover slab reinforced with 8 mm dia TMT bar 100 c/c both ways completeall as specified and as directed including testing on completion. Note :- (i) If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. (ii) Testing to be carried out by the contractor, entered in the eath testing register, prepared and to be maintained by the contractor & submited to department. (iii) T&P and testing instrument(Earth tester) to be provided by the contractor at own cost. (iv) Quoted rate shall be deemed to include the cost of GI Strip upto a distance of 7.5 metres from the earth plate. Strip required beyond the length shall be measured and paid separately.
Materials and Labour for earthing with copper earth plate electrode 600 x 600 x 3.15 mm thick burried directly in ground (earth pit not less rhan 2.25 m deep below normal ground level) with top edge of plate not less than 1.5 meter below normal ground level, the earth plate surrounded by alternative layer of charcoal dust and salt with thickness of 150 mm to a packed thickness of 150 mm on all sides with and including necessary excavation earth work returing filling in and removal of surplus soil upto 50 mtr including copper strip 20x3 mm bolted and reverted to earth plate at one end and connected to continuous copper strip encased in and including 40 mm dia GI medium grade protection pipe, 20 mm dia medium grade watering pipe with all fittings from top edge of earth plate upto 2400 mm above ground level fixed and including 25x 3 mm GI clamp bolts nuts and washer, funnel, wiremesh, PCC (1:3:6) type C1 earthing pit, 75 mm thick RCC cover slab reinforced with 8 mm dia TMT bar 100 c/c both ways completeall as specified and as directed including testing on completion taking out old unserviceable earthing complete. Note :- (i) If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. (ii) Testing to be carried out by the contractor, entered in the eath testing register, prepared and to be maintained by the contractor & submited to department. (iii) T&P and testing instrument(Earth tester) to be provided by the contractor at own cost. (iv) Quoted rate shall be deemed to include the cost of Copper Strip upto a distance of 7.5 metres from the earth plate. Strip required beyond the length shall be measured and paid separately. (v) The earthing pit should be provided with proper earth pit and pit cover.
Materials and Labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 20x3 copper strip using porcelain clit/post insulators including taking out old u/s copper strip, complete all as specified and as directed.
Materials and Labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 25x4 galvanised iron strip using porcelain clit/post insulators including taking out old u/s galvanised iron strip, complete all as specified and as directed.
Materials and Labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 32x6 galvanised iron strip using porcelain clit/post insulators including taking out old u/s galvanised iron strip, complete all as specified and as directed.
Materials and Labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 25 x 3 mm alumunium strip using porcelain clit/post insulators including taking out old u/s alumunium strip, complete all as specified and as directed.
Supply and fixing GI tubing, 40 mm bore, light grade with all fittings laid in trenches or fixed to wall including taking down of existing pipes and removal from site, complete all as specified and as directed.
Supply and Fix test point terminal block made of gun metal or phosphorous bronze, size 75 X 75 X 25 mm , drilled and screwed including 3 Nos. 8 mm dia. 25 mm long hexagonal head screws including MS box 2 mm thick of suitable size for protection of test point terminal including taking out old u/s test point terminal box, complete all as specified and as directed.
Supply and fix Air termination, single pointed, aluminium rod 12mm dia and 300mm long fixed on aluminium strip for earth conductivity to ground including taking out old u/s air termination rod, complete all as directed by Engineer- in- Charge.
Checking earth resistance value of existing all type of earthing ( in restricted and unrestricted area) from each earth test point and making data sheet as per direction of Engr-in charge. Note: Earth resistance tester and other arrangement for testing are included in the cost of above job.
Supply and fix High density polythelene pipes (HDPE) 40mm dia for insulation of earth strip from building at entry points incl taking out old u/s HDPE pipes, complete all as specified and as directed.
Supply and fix white porcelain ceramic insulator with nut, bolt and washers for fixing earthing strip on wall/ceiling/roof incl taking out old unserviceable porcelain ceramic insulator ,complete all as specified and as directed.
Supply and fix white porcelain ceramic insulator with Glue paste for fixing of earthing strip on wall/ceiling/roof ,incl taking out old unserviceable porcelain ceramic insulator ,complete all as specified and directed.
Supply and fix in repair's FRP earth pit cover heavy duty of minimum size 13 inch for Earthing chamber, complete all as specified and as directed by Engr-in-charge.
Supply and fix in repair's Flame proof weather proof LED tube light fittings fixture 1 x 18 W, 4'ft long, complete all as speicfied and as directed.
Supply and fix in repair's Switch flame proof rotary type with termination box in LM6, 16A, double pole 230 V flameproof, weather proof, 16 Amp, single pole ON/OFF, complete all as speicfied and as directed
Supply and fix in repair's flameproof exhaust fan single phase with louvers, 230 Volt , 50 Hz of size 300 mm sweep, complete all as speicfied and as directed.
Schedule of credit
SOMIK DAS
M/S SAIMON ENGINEERING
S S ENTERPRISE
ANSH CONSTRUCTION
UNITED BUILDERS
R. D. Industrial
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .