EXECUTIVE ENGINEER (EM) M 10
GREATER KAILASH, PART-I, NEW DELHI
Replacement of LT Panel sub distribution boards at Bottling Plant Greater Kailash-I (AC-50).
2022_DJB_222941_3
NIT No. 5/EE(EM)M-10/(22-23)
Open Tender
Electrical Work/ Equipment
Works
30 days
EXECUTIVE ENGINEER (EM) M 10
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
₹5,900
Yes
8 Jun 2022
25 May 2022
31 May 2022
25 May 2022
31 May 2022
25 May 2022
LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1200MM x900x250mm. Having following components of approved make. 1. MCCB 415V, FP 3phase 4 Pole, Breaking capacity 10KA 50Hz, 200Amp with spreader & Handle - Make L&T/Siemens -1 No. 2. MCCB 415V, TP+ NL 3phase 3 Pole, Breaking capacity 10KA 50Hz, 63Amp with hopper. - Make L&T/Siemens-3 Nos 3. MCB 4 pole 63Amp. Make L&T/Havells-3 Nos 4. MCB 4 pole 32Amp. Make L&T/Havells-3 Nos 5. Digital Amp./ VAF Meter including CT’s Make AE/L&T – 1 No. 6. Indicating Lamp RYB -1 Set 7. Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard ware’s complete in all respect.- 1 Job
LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated, wall mounted type, dust & vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipment of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminated with a ferule crimped to the wire, size 600MM x650x250mm. Having following components of approved make. 1. MCCB 415V, FP 3 phase 4Pole, Breaking capacity 10KA 50Hz, 100Amp with spreader & Handle - Make L&T/Siemens -1 No. 2. MCB 4 pole 40Amp. Make L&T/Havells-2 Nos 3. MCB 4 pole 32Amp. Make L&T/Havells-2 Nos 4. MCB 2 pole 32Amp. Make L&T/Havells-4Nos 5. Digital Amp./ VAF Meter including CT’s Make AE/L&T – 1 No. 6. Indicating Lamp RYB -1 Set 7. Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard ware’s complete in all respect.- 1 Job
LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated , wall mounted type, dust & vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1000MM x900x250mm. Having following components of approved make. 1. MCCB 415V, FP 3phase 4Pole, Breaking capacity 10KA 50Hz, 160Amp with spreader & Handle - Make L&T/Siemens -1 No. 2. MCCB 415V, TP+ NL 3phase 3Pole, Breaking capacity 10KA 50Hz, 63Amp with hopper. - Make L&T/Siemens -2 No. 3. MCB 4 pole 63Amp. Make L&T/Havells-2 Nos 4. MCB 4 pole 32Amp. Make L&T/Havells-2 Nos 5. Digital Amp./ VAF Meter including CT’s Make AE/L&T – 1 No. 6. Indicating Lamp RYB -1 Set 7. Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard ware’s complete in all respect.- 1 Job
Testing & commissioning of panel, as per required parameters with relevant IS .testing of the panel prior to switching on as follow 1. Continuity and earth testing 2. Meggaring of all equipment’s for phase to phase, neutral to body, neutral to earth and phase to earth. 3. Checking for all tightness of nut and bolts 4. Alignments of doors etc. 5. Interlocking tests. All function tests
Premier Engineering Company
MITTAL TRADING COMPANY
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .