Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.8 LAccepted-AOC 00 HAIDARPUR JAMALPUR ROAD SADAR JAUNPUR UTTAR PRADESH 222001 | JAUNPUR | UTTAR PRADESH | 222001 | ₹32.8 L Quoted ₹34.5 L | L1 | Accepted-AOC L1 bidder |
| 2 | L2₹48.9 L+₹14.4 L (41.7%)Rejected-Finance NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | ₹48.9 L+₹14.4 L (41.7%) | L2 | Rejected-Finance Other than L1 bidder |
| 3 | L3₹54.3 L+₹19.8 L (57.3%)Rejected-Finance POST MISAMARI DIST SONITPUR ASSAM 784 506 | SONITPUR | ASSAM | 784506 | ₹54.3 L+₹19.8 L (57.3%) | L3 | Rejected-Finance Other than L1 bidder |
Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
1 May 2023, 6:00 pmClosed
CWE Shillong
HQ CWE Shillong, SE Falls, Shillong - 793011
REPAIR TO HT EXTERNAL ELECTRIC INSTALLATION, UG ELECTRIC SUPPLY LINE, DISTRIBUTION TRANSFORMER AND OTHER ALLIED SERVICES UNDER GE NARANGI
2023_MES_587410_1
8644/NAR/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Narangi
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE Narangi
₹99,000
Yes
11 May 2023
29 Mar 2023
2 May 2023
29 Mar 2023
1 May 2023
12 Apr 2023
Amount
Material and labour for filtration and dehydration of transformer oil of distribution transformer indoor/outdoor type of 11/0.433 KV, 63 KVA to 500 KVA and Power transformer of 33/11 KV, 2.5 MVA minimum three cycle to achieve di electric strength of 50 KV at 2.5 mm gap as per relevant IS with portable centrifuging filtration plant, testing of the oil break down voltage before filtration and after filtration complete all as specified and directed. Note: (i) Centrifuging Machine with all T&P & testing machine of oil required for dehydration shall be arranged by contractor and will be deemed to be included in quoted rate. (ii) Oil required for topping up the transformer will be measured & paid separately.
Supply only transformer oil HV grade as per IS 335 of 1993 Part II having di-electric strength of not less than 30 KV at various locations complete all as specified and directed.
Material and labour for taking out old unserviceable defective HV bushings on site from outdoor/indoor type distribution transformers of 11/0.433 kV and 63 KVA to 500 KVA and Supply and fix porcelain bushing with heat resistant gasket complete all as specified and directed.
Material and labour for taking out old unserviceable defective LV bushings on site from outdoor/indoor type distribution transformers of 11/0.433 kV and 63 KVA to 160 KVA and Supply and fix porcelain bushing with heat resistant gasket complete all as specified and directed.
Material and labour for taking out old unserviceable defective LV bushings on site from outdoor/indoor type distribution transformers of 11/0.433 kV and 200 KVA to 500 KVA and Supply and fix porcelain bushing with heat resistant gasket complete all as specified and directed.
Supply and fix in repair of brass terminal stud, both end threaded complete with double nuts & washers including distance piece both sides and heat resistant gasket suitable for HV side 11000 volts grade for 63 KVA to 750 KVA capacity of outdoor/indoor type transformer complete all as specified and directed.
Supply and fix in repair of brass terminal stud both end threaded complete with double nuts & washers including distance piece both sides and heat resistant gasket suitable for LV side 415 volts grade for 63 KVA to 160 KVA capacity of outdoor/indoor type transformer complete all as specified and directed.
Supply and fix in repair of brass terminal stud both end threaded complete with double nuts & washers including distance piece both sides and heat resistant gasket suitable for LV side 415 volts grade for 200 KVA to 500 KVA capacity of outdoor/indoor type transformer complete all as specified and directed.
Material and labour for servicing/overhauling, calibration and de-carbonising of 11 kV (panel with breaker + Relay) and setting of Relay parameters VCB of capacity 630 Amps, indoor type, taking shut down from MRS and disconnecting incoming & out going cables, control cables from VCB and replacement of un-serviceable spares, greasing of fixed and moving assembly in VCB chamber, spring charging mechanism including de-carbonising the VCB panel and check serviceability all as specified and directed. Note:- (i) Spare parts/components required for replacement of above shall be measured and paid separately. The spares must be compatible with existing model and suitable for existing VCB. Make and model shall be got approved from Engr-in-Charge before placing order. (ii) Unit rate quoted against this item shall also include labour required for fixing of replaced items. (iii) For item No. 10 to 29 fixing charge of items are considered in item no. 9.00 here-in-before.
Supply only feeder protection numerical relay with features of earth fault, phase fault, over current and fault recording facility complete all as specified and directed
Supply only isolating contact 800A set of 6, complete all as specified and directed.
Supply only Vacuum Interrupter compatible with existing model complete all as specified and as directed.
Supply only Closing Coil 110VDC, complete all as specified and as directed.
Supply only Tripping Coil 110DC, complete all as specified and as directed.
Supply only Master trip relay compatible with existing model, complete all as specified and directed.
Supply only digital VAF, PF meter with RS 485 port of accuracy CI 1 including electrical connection compatible with existing model all as specified and directed.
Supply only breaker control switches (Trip-neutral-close) suitable for existing VCB Panel complete all as specified and directed.
Supply only Indicator lamp 110V DC/240 V AC of colour green/ yellow/ red/ white/ Amber/ Blue, complete all as specified and directed.
Supply only Breaker Auxiliary Switch 6 NO + 6 NC, complete all as specified and directed.
Supply only Closing Coil Box Assembly, complete all as specified and directed.
Supply only Trip Coil Box Assembly, complete all as specified and directed.
Supply only Auxiliary Switch Drive Assembly, complete all as specified and directed.
Supply only Charging Paw, complete all as specified and directed.
Supply only Buffer for spring all as specified and directed.
Supply only Epoxy Insulator all as specified and directed.
Supply only Fix R Phase Bus Bar Spout, complete all as specified and directed.
Supply only Y Phase Bus Bar Spout, complete all as specified and directed.
Supply only Fix B Phase Bus Bar Spout, complete all as specified and directed.
Supply only Fix Circuit Spout, complete all as specified and directed.
Supply and fixing of 110V AC input and 30V DC Power pack source for 11 KV VCB Panel with inbuilt battery including all electrical connection and taking down old unserviceable one all as specified and directed.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 95 sqmm including taking down unserviceable one, complete all as specified and directed.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 95 sqmm including taking down unserviceable one, complete all as specified and directed.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 95 sqmm including taking down unserviceable one, complete all as specified and directed.
Material and labour for detecting of fault in 11KV (E) HT cable of any size (within 1-3 km length), 3 core laid in trenches/ducts with the help of electronic fault locating machine comprising of surge generator pulse, echo fault locator with high frequency distance calculator etc and exposing the cable fault, removal of deteriorated portion of cable, treating the cable including making it ready for jointing work complete all as specified and directed. Note:- (i) The quoted rate shall deemed to include for the cost of earthwork excavation as required. (ii) Cable if replaced & Jointing kit shall be measured and paid separately.
Supply and fix gang operated air break switch mechanically operated on insulator and steel frame, with operating mechanism worked from ground level, with 9 Nos insulator tilting type for current rating 200 Amps, 11000 Volt including taking down old unserviceable one complete all as specified and directed.
Supply and fix Expulsion type drop out fuse with all accessories fixed on HT pole rating 200Amps suitable for 11kV, 3 pole with two Nos insulator per pole including dismantling old unserviceable one complete all as specified and directed.
Supply and fix lightning arrester, expulsion type complete with all fitting distribution class, discharge capacity 65 Kilo Amp 11000 Volts rating including dismantling old unserviceable lightning arrester complete all as specified and directed.
Supply and fix in repair single phase indoor type current transformer suitable for 11 KV, 50Hz, having effectively earthed neutral system, single core single ratio dry type epoxy resin cast, copper wound primary type, of CT Ratio 100-50/5-5A with rated burden 10VA and accuracy class 1 or better and conforming to IS 2705 (Part-I & II) amended upto date with Short Circuit Rating 13.1 KA for 1.0 second all as specified and directed.
Supply and fix in repair drawout type three phase indoor type potential transformer with sheet enclosure suitable for 11 kV/110V, 50Hz, dry type epoxy resin cast type with rated burden 200VA/Phase and accuracy class 1 or better and conforming to IS 2705 (Part-I & II) amended upto date all as specified and directed.
Taking out saturated silica gel from existing breather and Supply and replace silica gel in breather of transformer complete all as specified and directed.
Supply and fix in repair silica gel breather 250gm capacity made up of aluminum top, transparent centre portion made of polycarbonate, filled with silica gel suitable for transformer of capacity 100 KVA to 250 KVA complete all as specified an directed.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cable, etc. not exceeding 10 Sqm on plan and not exceeding 1.5m in depth and getting out in soft/loose soil all as specified and directed.
Returning filling including spreading, leveling, watering and well ramming layers not exceeding 25 cm thick for any type of soil all as specified and directed.
Removing surplus soil to a distance not exceeding 50m and depositing at level not exceeding 1.5m above the starting point all as specified and directed.
Supply and spread clean dry river sand in cable trenches as in cable cushioning all as specified and directed.
Supply and laying un-reinforced precast concrete cable cover class HV type-1 of flat size 300mm x 180mm x 40 mm complete in trenches all as specified and directed.
Supply, laying, testing & commissioning XLPE HT UG insulated (Earthed) cable laid in trenches/or fixed on pole etc. with screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with stranded aluminum conductor, 11000 Volt grade, cross sectional area 95 Sqmm, 3 Core conforming to IS-7098 (Part-II)-1985 laid in trenches/ wall/ ducts/ poles including taking down unserviceable one complete all as specified and directed. Note:- Excavation & earth work will be measured and paid separately.
Material and labour for GI pipe light grade 80mm bore with all fittings to be laid in trenches or in floors, including taking down rusted one complete all as specified and directed.
Material and labour for isolating 11KV HT overhead supply from the substation and earth complete system properly, disconnecting complete electric system of the transformer from HT and LT side including earthing strips, removing transformer and taking out from substation or taking down from 2/4 pole structure, lifting arrangements, transporting to authorized service centre/work shop for repair and back to the installation after repair including installing, commissioning and testing of the capacity upto 63 KVA complete all as specified and directed.
All as per Serial item No 49.00 above but of 100KVA to 200KVA complete all as specified and directed.
All as per Serial item No 49.00 here-in-before but of 250KVA to 400KVA complete all as specified and directed.
All as per Serial item No 49.00 here-in-before but of 500KVA to 750KVA complete all as specified and directed. Note: Necessary T&P shall be arranged by the contractor. The rate of T&P is included in above quoted rate.
Draining out the complete transformer oil and keeping in safe custody in clean and dry containers for reuse. Opening the top cover of the transformer, disconnecting and taking out complete core assembly and dismantling it for checking the serviceability of the coil winding, checking the condition of the body, cleaning the tank and remove sludge/dirt, cleaning the coils limbs, re-fixing of core, core assy, tap changer assy, HT/LT winding connection, terminal studs of HT/LT sides and reassembling of transformer after repairs, refitting the transformer coil including improvement of insulation resistance value within desired level by heating or any other method to required level to the entire satisfaction of Engr-in-Charge upto 63KVA complete all as specified and directed.
All as per Serial item No 53.00 above but of 100KVA to 200KVA complete all as specified and directed.
All as per Serial item No 53.00 here-in-before but of 250KVA to 400KVA complete all as specified and directed.
All as per Serial item No 53.00 here-in-before but of 500KVA to 750KVA complete all as specified and directed.
Supply only primary /secondary (HV/LV side)) aluminum winding coils of existing type size and gauge and in weight complete including wrapping with paper insulation for transformer of 50 kVA to 750 kVA complete all as specified and directed.
Supply only primary (HV side) copper winding coils of existing type size and gauge and in weight including wrapping with paper insulation for transformer of 63KVA to 750 kVA complete all as specified and directed.
All as per serial item No 58.00 here-in-before but for secondary (LT side) complete all as specified and directed. Note for Item No. 57.00 to 59.00:- Actual weight of the each coil shall be measured and paid. Fitting charges of formed coil included in item 53 to 56 here-in-before.
Supply and fixing in replacement new off load tap changer assembly, making connection and testing of the transformer of capacity 50kVA to 200kVA complete all as specified and directed.
All as per serial item No 60.00 above but of 250KVA to 400KVA complete all as specified and directed.
All as per serial item No 60.00 here-in-before but of 500KVA to 750KVA complete all as specified and directed.
Material and labour for replacement of Brown Rubberized Cork Sheet Gasket of 6mm thick for transformer tank all as specified and directed.
Material and labour in repair earthing complete with copper earth plate electrode 600mm x 600mm x 3mm thick buried directly in ground (Earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below ground level connected to copper strip 20 x 3 mm as earth lead by means of bolts nuts, check nuts and washers of brass and as shown in electrical plate No 3 connected to earth test point, copper earth strip protected with and including GI pipe 40mm bore for earth strip protection ‘light grade', Gl pipe 20mm bore ‘Medium grade' for watering including necessary excavation any type of soil, RCC chamber cover plate, wire mess, funnel, etc complete and necessary testing on completion all as specified and directed.
Material and labour in repair earthing complete with galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly in ground (Earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below ground level connected to galvanised earth lead by means of bolts nuts, check nuts and washers of galvanised iron or steel using GI strip 32 X 6mm as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earth test point all as specified or indicated including GI pipe 40mm bore for earth strip protection 'light grade', GI pipe 20mm bore 'Medium grade' for watering including necessary excavation any type of soil, RCC chamber cover plate, wire mess, funnel, etc complete and testing on completion as specified and directed.
Dismantling unserviceable cross arms, clamps etc complete all as specified and directed.
Material and labour for Cross arm, bracing, support, clamp, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps, nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminum paint complete all as specified and directed.
Material and labour in repair for air break isolating switch 3 insulator for each phase (isolator for 33KV) vertical double stack central rotating type with earth blade hot dip galvanised complete with operating rod and handle all as specified and directed.
Material and labour for fabrication of display board for earth pit Nos, location and periodical test results for lightening arrester earthing, made of MS sheet 4.0 mm thick sheet, rectangular welding on 12 mm dia rod of height from ground level 30 cm including fixing in PCC 1:2:4 with 20cm X 20cm X 20cm (below ground level) grade aggregate foundation. Dimension of board shall be 30cm X 25cm. The instruction shall be written on black painted board with white letters not less than 2” size for all type of boards including taking down rusted one complete all as specified and directed. Note:- All necessary MS sheet, aluminum screws and PCC works etc are deemed to be included in the rate quoted by the bidder.
Supply and fix in repair for thermoplastic (polycarbonate) junction box for test point without terminal block of dimension 130mmx130mmx77mm IP 66 halogen free and weather proof including four hexagonal anticorrosive screws for outdoor installation all as specified and directed.
Material and labour in repair for Test point terminal block made of gun metal or phosphorus bronze size 75mmx75mmx25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head screws for fixing strips to test point including necessary fixing arrangement to fix test point terminal block to test point junction box all as specified and directed.
Supply and fix in repair PVC covered aluminum strip 25 x 3.15mm with "V" type porcelain insulator or DMC insulator of suitable size and fixing with GI screws etc. for down conductors above ground complete all as specified and directed.
Supply and fix in repair pre-moulded elbow boots for transformer bushing made of non- tracking EPDM rubber suitable of 12kV and 95sqmm 3 core cable complete all as specified and directed.
Material and labour for painting of steel tubular HT poles including cross arms, clamps, back plates etc. in situ with one under coat and one finishing coat of aluminum paint after cleaning /preparation of surfaces including making white and black stripes 30 cm wide 5 Nos with two coats of synthetic enamel paint and marking of pole No., Substation No., etc. complete all as specified and directed.
Material and labour for taking down the unserviceable RMU 4 way servicing of complete parts of RMU, lubrication of mechanical parts, adjustment and calibration of complete relays etc and checking complete parts, repairs to control wiring with single core copper conductors of existing size as required at site (RMU of make Schneider) for satisfactory running and replacement of defective spare parts and reassembling the same re-connecting all HT & AC/DC connections complete in functional order including testing on existing load complete all as specified and directed. Note:- The necessary spare parts involving in repair except control wiring shall be measured and paid separately under respective item.
Supply only 14SWG CRC sheet cover for bushing compartment along with coated paint and stainless steel nut-bolt, washer etc complete all as specified and directed.
Supply only operating handle for RMU all as specified and directed.
Supply only Feeder protection self powered numerical relay with features of earth fault, phase fault, over current and fault recording facility complete all as specified and directed. (Compatible with existing RMU)
PURBANCHAL BUILDERS
RC Madan
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .