Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.2 LAccepted-Finance BOOTH NO 15 SHOPPING COMPLEX URBAN ESTATE PHASE II JALANDHAR CITY PIN 144022 | JALANDHAR | PUNJAB | 144022 | L1 | Accepted-Finance Lowest and reasonable bid | |
| 2 | L2₹33.4 L+₹4.3 L (14.6%)Rejected-Finance | L2 | Rejected-Finance Other than the lowest bid | |
| 3 | L3₹33.5 L+₹4.3 L (14.8%)Rejected-Finance 5B FF NAND VIHAR AZAD NAGAR NEAR GODARA PETROL PUMP HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | L3 | Rejected-Finance Other than the lowest bid | |
| 4 | L4₹35.2 L+₹6.1 L (20.8%)Rejected-Finance 25 25 SADAR BAZAR JALANDHAR CANTT | JALANDHAR | JALANDHAR | PUNJAB | L4 | Rejected-Finance Other than the lowest bid | |
| 5 | L5₹36.7 L+₹7.5 L (25.8%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | L5 | Rejected-Finance Other than the lowest bid |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
20 Feb 2024, 6:00 pmClosed
GARRISON ENGINEER (WEST)
KABIR ROAD JALANDHAR CANTT
DAY TO DAY MAINT OF INTERNAL ELECTRIFICATION JCO/OR MD ACCN AT KK VIHAR, BHAGAT ROAD FAFA, RT LINE AND VAJRA COMPLEX UNDER GE (W) JRC
2024_MES_639201_1
GE/JAL(W)-72/2023-24
Open Tender
Civil Works
Item Rate
270 days
JALANDHAR CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GARRISON ENGINEER (WEST)
₹80,000
Yes
28 Feb 2024
25 Jan 2024
27 Feb 2024
25 Jan 2024
20 Feb 2024
8 Feb 2024
Amount
Attending of complaints from 0900 hrs to 1700 hrs by deploying electrician along with helpers for checking of existing electrical items including carrying out repairs such as tightening of loose electric connections, nuts, bolts, screws, repair/ replacement of switches, sockets, switch boards ceiling fans/exhaust fan, DB wiring etc as required to make the item functional and to ensure contiunous electric supply complete as specified and directed by Engr-in-Charge. Note: (a) Replacement of electric fitting shall be mesured and paid for seperately under respective items (b) Rate quoted deemed to be inclusive of T&P etc. (c) The saftey and insurance of persons/helper engaged in Execution shall be responsibility of contractor. (d) As the Nos of complaints shall be on required basis the financial effect to this is deemed to be included in the rate quoted.
Taking down carefully aluminium / copper point wiring (light / fan / socket or power) while not disturbing existing conduit complete including fitting such as switches, ceiling roses, socket, light fittings, regulators etc complete and making good disturbed surfaces of walls and floors .
Taking down sub main wiring of two single core PVC cable PVC insulated 4 / 6 sqmm including conduit or wooden batten and remove from the site of work and making good the disturbed surfaces of wall or floor etc. as directed by Engineer-in-Charge.
Taking down main switch / DB and making good the disturbed surface as directed by Engineer-In-Charge.
M&L for point wiring with PVC insulated, unsheathed cable single core multistranded copper conductor FRLS cable 1.5 sqmm size, 1100V grade, drawn into existing PVC rigid concealed conduit medium grade (ISI marked) including PVC unsheathed cable single core copper FRLS conductor 1.5 Sqmm as continuous earth wire and including pressed MS sheet sunken box 1.6 mm thick with 3 mm thick laminated bakelite sheet all as specified. a) One light / fan / call bell point controlled by one, one way switch.
All as per Ser item No 5.00 above but for 5 amps socket on independent board
All as per Ser item No 5.00 above but for 5 amps socket on same board
M&L for point wiring with PVC insulated, unsheathed cable single core multistranded copper conductor FRLS cable 1.5 sqmm size, 1100V grade, drawn into and including PVC rigid concealed conduit medium grade (ISI marked) including PVC unsheathed cable single core copper FRLS conductor 1.5 Sqmm as continuous earth wire and including pressed MS sheet sunken box 1.6 mm thick with 3 mm thick laminated bakelite sheet one light / fan / call bell point controlled by one, one way switch.all as specified. a) One light / fan / call bell point controlled by one, one way switch.
All as per Ser item No 8.00 above but for 5 amps socket on independent board
All as per Ser item No 8.00 above but for 5 amps socket on same board
All as per Ser item No 8.00 above but with 2.5 sq mm cable for 15 amps switch socket combination outlet on independent board complete all as specified and directed.
All as per Ser item No 8.00 above but with 2.5 sqmm multistranded copper multistranded conductor FRLS cable with 2.5 sqmm earth wire for one 6 pin socket outlet 15 amps on independent board
Supply & fixing switch piano flush type single pole one way 5 Amps all as specified.
All as per Ser item No 13.00 above but single pole 5 Amps two way all as specified.
Supply & fixing switch piano flush type single pole 15 Amps.
Supply & fixing socket outlet 5 Amp flush button type all as specified.
All as per Ser item No 16.00 above but 6 pin 5/15 Amps multi type.
Supply & fixing switch piano single pole bell push all as specified.
Supply & fixing ceiling roses surfaces bakelite two three terminals 65 x 50 mm all as specified.
Supply & fixing lamp holder PVC, insulated body with back plate suitable for batten fittings including LED lamp 9W all as specified.
Supply & fixing bell electric (dingdong) 230 volt, SP
Supply and fix in repair modular fan regulator step type 240 V, 120 W , 2 modules all as as per existing make & model/ as per sample .
Supply and fix ceiling fan regulator Electronic rotary Step type single phase A/C 230 volts all complete as specified and directed.
Supply & fixing decorative wall light fixture made up of polycarbonate, with suitable LED Bulb .
S & F 6.5 W LED Bulk Head fitting and connecting electricity using PVC insulated and overall sheathed flexible copper conductor of size 0.75mm 3 core complete all as specified and directed
S&F in replacement LED lights fitting 1 x 20W, 220V, Box type with driver, holder including LED tubelight connecting up with electricity to celling rose using PVC insulated and overall sheathed flexible copper conductor of size 0.75mm 3 core complete all as specified and directed.
S& F in replacement LED tube set (fitting) 20 W use and through type with internal surge protection device of 4 KV with voltage band 140-280V with LED rod with fixture box type and making electrical connection to ceiling rose all as directed
Supply & Fixing LED Bulb 9 Watts.
Supply & Fixing LED Bulb 12 Watts.
Supply & fixing in replacement LED street light fitting 35W including LED lamp pressure die cast aluminum IP66 with surge protection device of 10KV, IK7 LED 6500K and connecting electrical to ceiling rose using PVC insulated and overall sheathed flexible copper conductor of size 0.75mm 3 core complete all as specified and directed including bracket and fixing clamps etc.
Supply & Fixing MCB single pole , 240 volts, 6 to 32 Amps in the existing DBs.
Supply & Fixing MCB, 240 volts, 32-63 Amp Amps SPN .
Supply & fixing MCB DB SPN with 200 amps rated Bus Bar double door IP protection suitable for MCBs 8 way all as specified and directed by Engr-in-Charge.
Supply & fixing MCCB 4 pole of capacity 100 Amps with breaking capacity 16 Kilo Amps including all electrical connections and fixing arrangment all as specified and directed by Engineer -in-Charge
Supply & fixing MCCB 3 pole of capacity 63 Amps with breaking capacity 16 Kilo Amps including all electrical connections and fixing arrangment all as specified and directed by Engineer -in-Charge
S & F distribution board VTPN, double door, 6 way 440 Volts with sheet metal enclosure 200 Amps busbar suitable for fixing MCCB as incommer.
S/F MCB TPN 100 Amps 415 volts.
M&L for concealed conduit sub main wiring of 2 run of single core multi stranded FRLS PVC insulated and unsheathed copper conductor as per IS-694 FR cable red and black colour of size 6 sqmm 1100 volts grade with 6.0 sqmm multi strand copper conductor PVC insulated and unsheathed cable in green colour earth continuity wire connected to common earth dolly in PVC pipe including cutting chasing complete with all accessories as specified and directed. Note: Two runs of cable 6.0 Sqmm, one run of cable 6 Sqmm and one run of PVC conduit will be measured as one unit RM.
M&L for submain wiring with two RUNS of single core 4 sqmm for main wire and one run of single core 4 sqmm as earth wire of stranded FRLS copper conductor PVC insulated unsheathed cables drawn through and including concealed conduits in wall and necessary cutting and chassing for rigid PVC conduit ISI marked not less than 20 mm dia and all accessories complete all as specified & directed. Note: Two runs of cable 4.0 Sqmm, one run of cable 4 Sqmm and one run of PVC conduit will be measured as one unit RM.
Supply & fix bakelite Hylem sheet 3mm thick of size 10"x12" superior quality, including cutting of sheet to fix switch socket & regulator, including unscrewing the existing switch, socket, regulator and refixing the same on new sheet with new machine screw complete all as specified and directed.
All as per Ser item No 40.00 above but size 7"x5" complete all as specified and directed.
M&L for fixing MS sunken box of 1.6 mm thick of box sizes of size 10" x 12" and making good to wall.
M&L for fixing MS sunken box of 1.6 mm thick of box sizes of size 7" x 5" and making good to wall.
Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less 1.5 mtr deep below normal ground level connected to GI earth wire 4 mm dia connected to earth plate by means of nut, bolts, check nut & washer of galvanized iron or of steel, GI earth wire will be protected by 15 mm dia GI pipe light grade', watering pipe 20 mm dia GI 'light grade', GI wire meshed funnel, alternate layer of char coal and salt on all side to earth plate upto thickness of 150 mm, filling of black cotton soil in earth pit upto ground level, PCC chamber recessed for and including RCC cover including all necessary excavation and earth work, earth wire connected to O/H continuous earth wire on pole, testing the earthing after complete all as specified and directed.
GULSHAN SINGH GHAI AND SON
SUN MANN ENGINEERS
CHOUDHARY AND SONS
UNITED ENGINEERING CORPORATION
FRIENDS ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .