LT Electrical and Allied Works at Third and fourth floor Secure Cluster room at C-DAC Pune
2021_DIT_632267_1
CDACP/LB/Secure Cluster-Elect/2021/24-2190
Open Tender
Electrical Works
Works
45 days
Pune
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
CDAC
Exempted
Pune
8 Jun 2023
3 Jun 2021
22 Jun 2021
3 Jun 2021
22 Jun 2021
17 Jun 2021
3 Jun 2021 - 9 Jun 2021
10 Jun 2021
Amount
LT Electrical and & Allied Works
Suply and installation of 4-way, TPN, Metal type, with Plain / Transperant Door (As approved by client / consultant / architect), UPS Power Distribution Board (UPSDB-outgoing) (for desks), surface / flush mounted on wall, interconnected wiring complete with earthing lugs, including DB wiring dressing with ferruling, termination of circuits with ping type copper lugs, blank plates, etc. housing following switchgears : (Schneider / Hager / Siemens / Legrand make as approved by client / consultant)-Server Room a) 1 no., 63A, TPN MCB, "C/D" curve type as incomer b) 12 nos, 16/20/32A, SP, MCB, "C/D" curve type as outgoings Full Set as above
Supply & Installation of 20/32A, DP, MCB, box with 20A, metal clad / modular plug-socket including power circuit of (2x4 + 1x2.5) sq. mm FRLS copper flexible wires directly taken from the relevant DB through PVC conduits for room A/C including all necessary hardware & accessories, etc. (Schneider / Hager / Legrand / Siemens / L&T make)
CABELS / MAINS Supply & Installation of 1100V grade armoured cable having sector / circular shaped aluminium / copper conductor PVC insulated cores, laid up, PVC tape wrappe d inner sheathed, GI strip / wire armoured and overall extruded PVC sheathed confirming to IS: 1554, laid on wall / ceiling using GI clamps & spacers as per route shown at site and further as directed by Consultant at site in the following sizes :- (Make - Polycab / Finolex / RR / Havells) NOTE :- All Armoured cables shall be provided with temporary labelling at every 5mtrs & then finally with metal indentification tags showing the size & the location from/to the respective Panel / DB, at both the ends.
4C x 10 Sq.mm Copper Armoured cable with 2 runs of 12 SWG GI bare wire
4C x 6 Sq.mm Copper Armoured cable with 2 runs of 12 SWG GI bare wire
3C x 4 Sq.mm Copper Armoured cable with 2 runs of 12 SWG GI bare wire
WORKSTATION UPS POWER WIRING Supply & Installation of concealed / ressessed / surface light point / fan point / call bell point wiring using 600V FRLS grade 3R (P+N+E) x 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B color code) pulled through heavy gauge PVC conduits laid concealed over false ceiling or in wall chases or on the ceiling in case of an open ceiling including 3R (P+N+E) x 2.5 Sq.mm circuit wires from the relevant DB and also including 2.5 sqmm green color copper earth wire and approved make modular type switch plate, switches, MS concealed back box, etc. as required & as approved by the consultant. (Each circuit shall not feed more than 8 points OR 800 watts as per following configuration.) (The item rate shall include Lighting / Raw / UPS Power Circuit wiring from relevent DB to the switch board with 3Rx2.5 Sq.mm FRLS wires & from switch board to next switch board OR to the first light point / primary point / full point) NOTE :- 1. Only FRLS grade conductor wire shall be used; 2. Conduit carrying circuit wiring should not carry point wiring and Conduit carrying point wiring should not carry submain/circuit wiring; 3. Flexible conduits & Elbows are not allowed; 4. The wires from ceiling junction to light points / light fixture shall be drawn in flexible PVC conduit with adptor & cover for junction box & crimp type lugs at both the ends alongwith necessary hardware & accessories, etc. as required; 5. Proper ferrules, lugs, must be used in all cabling and wiring on both load / source end; 6. Each switch board must be provided with respective ferrules representing the respective DB, Phase & Circuit numbers; 7. Looping of Neutral / Earth wire between two seperate Primary / Full Points is strictly not allowed; 8. Looping of Neutral / Earth wire between two seperate circuits on similar or other phase is strictly not allowed; 9. Ferulling / numbering / taggning to wires with circuit number & db name for all lighting & raw / ups power shall be strictly followed at both DB & switch board / switch socket boards ends.
Supply & Installation of point wiring for UPS or stabilized power plug points on workstations / table for computers using 3C X 2.5 Sqmm FRLS grade copper conductor PVC sheathed white color flexible cable pulled through already laid floor raceways and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin sockets above table top/bottom & 1 No., 15A Switch above table top/Bottom, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green color only. (Maximum 4 no.s desks served by one circiut from DB)
TRENCHING /Floor Raceways -Supply and laying Raceways / Conduits (for under floor trenches / On trays) on existing flooring. Raceways / conduits shall be fixed to the flooring with GI clamps for finished levels as per the site conditions or through partitions with all accessories. The rate shall include preparation of trenches of required sizes by carefully removing the malwa on existing floor for laying Raceways/conduits for power, data, telephone cables etc. The depth of the trenches shall be at least 2 inches from the finished floor level or upto RCC of the slab. The rate shall include the cost of the Raceways/conduits. The rate shall also include the activity of clearing the debris generated from the preparation of trenches.
300 x 40 x 1.6mm thick Aluminium Raceways
150 x 40 x 1.6mm thick Aluminium Raceways
Supply & Installation of floor junction boxes without top cover for above raceways, of following sizes, fabricated out of M.S. sheets, fully powder coated with provision for removable M.S. / S.S. screwed cover plates on all four sides for blocking the entry into the junction box. All the junction boxes to be (with stud) 'properly earth - bonded with the raceways pipe using 12 SWG Copper bare wire as directed at site.
Junction Box of size (200mm x 200mm x 50mm x 2.5mm thick)
Junction Box of size (350mm x 350mm x 50mm x 2.5mm thick)
Supply & Installation of suitable sizes 2mm thick removable cover plate screwed on all four sides of M.S. sheet, fully powder coated, for blocking the entry into the floor junction box for following sizes of junction boxes with rounded corners as per the instruction given & sample approved by the client / architect / consultant at site. Cover plate shall have required no.s of 1' dia knockouts for flexible conduit outlets as per the requirement.
for Junction Box of size (200mm x 200mm x 50mm x 2.5mm thick)
Junction Box of size (350mm x 350mm x 50mm x 2.5mm thick)
Supplying & fixing of 2mm thick G.I. Perforated type cable Trays of Asian /Profab Engieers approved make. The cable tray shall be fixed to the ceiling / wall with MS angle support with 35mmx2mm thick GI slotted 'C' channel patti at an interval of 1 meter or the MS angle iron fabricated support depending upon the location. The rate shall include the cost of Supports, hardware & accessories, etc. complete as required.
Cable Tray :- 75 mm wide x 50 mm height x 2mm thick.
DATA NETWORKING- Supply & Installation of Data point including approved make Cat - 6 UTP cable through already laid trenches / conduits, RJ45 information outlet, dual type face plate, PVC back box etc. with Termination, Testing and Documentation of UTP Points complete as required.
Supply & installation of 24 Port 10/100 Mbps Unmanage switch
Supply & installation of 24 port jack panel in existing network rack
Supply of mounting patch cord (7 feet')
Supply of mounting patch cord (3 feet')
Supply & Installation of 15 U floor/wall mounted network rack including all necessary hardware, accessories, etc.(MP Room)
Supply & Installation of 12 U wall mounted network rack including all necessary hardware, accessories, etc.(Kaveri Room)
SITC of LC to LC Duplex MMF, OM3 (50/125μm) Fibre Patch cord of 30 mts
SITC of LC to LC Duplex MMF, OM3 (50/125μm) Fibre Patch cord of 90 mts
VOICE & TELEPHONE NETWORKING - Supply & Installation of Telephone /Voice point including approved make Cat - 6 UTP cable through already laid trenches / conduits, RJ45 information outlet, in single face plate, in workstation partion wall etc. with Termination, Testing and Documentation of UTP Points complete as required.
Supply, installation, testing and commissioning of indoor type telephone Main Distribution Frame (MDF) / Box with suitable S.S. frame for mounting tag module, cable, wires and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc.to be provided in the box for :-
Supply & Installation of 100 pair MDF with Krone module including all hardware & accessoried , etc. complete as required.
Supply & Laying of 20 pair telephone cable through heavy guage pvc conduit including all necessary hardware & accessories, etc.
ACCESS Control System- SITC of Biometric cum card reader system Access Control Panel with onboard TCP/IP, Supports Standard Wiegand Reader with Metal Enclosure & inbuilt Power Supply (provision for 2 hr Battery Backup, )
SITC of proximity Cards ( Blank)
SITC of Electromagnetic Lock (600 Lbs) suitable for DOUBLE LEAF Door with door position sensor & necessary accessories
SITC of Door Sensor
SITC of cat 6 cable with 25 mm PVC Conduit for laying cables(Conduit Make- Modi/equivalent)
CCTV- Supply,installation,testing & commissioning of IP Dome Camera 2MP H.265 Make:-Hikvision,CP Plus or equivalent
SITC of Cat 6 cable D LINK or equivalent in flexible /rigid conduit
SITC of 16 Channel NVR H.265 with 4 TB harddisk 80 MBPS bandwidth minimum with 2x8 PORT POE Switch Network , 10/100Mbps RJ45 ports, 1, 100M Ethernet Port Network ProtocolIEEE802.3,802.3u,802.3x, 802.3af, 802.3at.
Associated Floor Civil Work -Breaking of existing vitrified tiles and clearing Mortar up to slab level to make path for laying Raceways.
Providing and laying vitrified floor tiles matching with existing tiles having water absorptions less than 0.08% and confirming to IS: 15622 of approved make in all colors and shades, laid on adequate thick cement mortar 1:4 (1 cement: 4 coarse sand) including grouting the joints with white cement and matching pigments etc. complete.Size of Tile 60 x 60 cm
UNICAN CONTROLS AND AUTOMATION PVT LTD
Keshavpriya Infrastructures
INFINITY ENGINEERING COMPANY
vcube electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .