Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.8 LAccepted-AOC NEAR PUMP HOUSE ROAD NEAR RED ROSE SCHOOL BABINA CANTT JHANSI DISTT UP 284401 | JHANSI | UTTAR PRADESH | 284001 | L1 | Accepted-AOC Being a L1 bidder | |
| 2 | L2₹25.6 L+₹3.2 L (14.2%)Rejected-Finance C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | L2 | Rejected-Finance Other than
lowest
bidder | |
| 3 | L3₹26.2 L+₹3.8 L (17.0%)Rejected-Finance 640 MAIN ROAD BABINA CANTT JHANSI UP 284401 | JHANSI | JHANSI | UP | 284401 | L3 | Rejected-Finance Other than
lowest
bidder |
Tender Value
₹27 L
EMD Value
₹54,000
Closing Date
25 Mar 2023, 6:00 pmClosed
GE BABINA
GE BABINA CANTT 284401
REPAIR/REPLACEMENT OF UNSERVICEABLE SUMMER APPLIANCES LIKE DESERT COOLER, REFRIGERATOR, AIR CONDITIONERS, DEEP FREEZERS, WATER COOLER AND CONNECTED ITEMS UNDER GE BABINA
2023_MES_582896_1
8114/E8
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
GE BABINA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE BABINA
₹54,000
Yes
8 Apr 2023
24 Feb 2023
27 Mar 2023
24 Feb 2023
25 Mar 2023
11 Mar 2023
Amount
M&L for complete Servicing of split AC up to 2 Ton capacity ,any make any model at various locations comprising of all the installed machineries and accessories such as Rotary/Reciprocating type compressor, condenser,air filter,liquid line filter ,capallary tube,expension valve and other electrical components complete including checking of any leakage in system and repairing, greasing/ lubricating of moving parts, fan motors complete all as specified and directed . Note ( A) : (i) All servicing and repairs works shall be carried out by authorised service centre/at workshop of manufacturer/Make , Proof of the same will be submitted to the GE . (ii) The replacement of defective/ nonfuctional parts such as PVC air filter, relay, capacitor, thermostat, contactor, gas drier filter and other connected items etc, shall be measured and paid separately under relevant item of BOQ . (iii) Quoted rate shall include transportation charges .Note B: The unit rate includes the following works . (i) Checking of gas leakage in complete system.Gas and gas charging shall be measured and paid separately. (ii) Checking the refrigeration system and ensuring healthy condition of the Air conditioner. (iii) Cleaning of the indoor & out door unit by cleaning of dust from condenser,air filter, cooling coils, by water pressure pump .
All as per item No:01 but servicing of Window AC up to 2 Ton Capacity
S & F in replacement hermetical sealed gas compressor,ISI Marked suitable for 1.5 Ton capacity split type Air Conditioner of any make , suitable for working on 230 V , 50 Hz as per existing make and model including necessary welding/bracing work to existing refrigerant pipes complete all as specified & directed.
All as per item No 3 but Compressor suitable for 1.5 Ton Window type Air Conditioner.
All as per item No 3 but compressor suitable for 2.0 Ton Window Air Conditioner
All as per item No 3 but compressor suitable for 2.0 Ton Split type Air Conditioner
S & F in replacement of starting capacitor of 80-90 MFD ,230 V, 50Hz complete all as specified and directed. Make –Epcos/Annpurna/Indfoss/Havells/ABB
All as per item No :7 but starting capacitor of 100-120 MFD , 230 V, 50Hz capacity.
S & F in replacement of running capacitor of 40 to 45 MFD capacity ,230V 50Hz suitable for 1.5 Ton AC complete all as specified and directed. Make –Epcos/Annpurna/Indfoss/Havells/ABB
All as per item No :9 but running capacitor of 50 to 60 MFD , 230 V,50Hz capacity.
S & F in Replacement two pole Contactor up to 30 Amp capacity 230 V,50Hz suitable for split type AC complete all as specified and directed. Make- L&T/Havells / BCH / Siemens / ABB
S & F in Replacement of Box type starting relay assembly for window/split type air conditioners of any make / capacity complete all as specified and directed.Make- Technomech / Classic /Annapurna.
S & F in Replacement of gas drier filter two way/One way for window type AC of any make & capacity complete all as specified and directed.
S & F in Replacement PVC air filter suitable for window/split type AC of any make & capacity.
S & F in Replacement of insulation foam covering of copper tubbing suction line from out door unit to indoor unit with suitable method of split type AC duly covered and tightened complete all specified and directed .
Dismantling blower/Condenser fan motor of window type AC of 1.5/2.0 TR capacity and Supply and fixing new fan motor alongwith fan of existing make and size and refixing in position, connecting and testing on load all as specified and directed . Make : Crompton/Voltas//GE/Carrier/Samsung
All as per Item No 16 but for split air conditioner of 1.5 /2.0TR capacity.
S & F in replacement of electronic circuit (PCB) Original / Assembled (External type) complete including controlling unit i.e. (remote) all as per existing system and suitable for 1.5/2.0 TR capacity split type / window AC compatible with all AC's Brands in original position as per specified and directed.
S & F in replacement of thermostat suitable for 1.5 TR/2.0 TR capacity Window AC/split AC Make :- Indofoss or equivalent as approved by accepting Officer/GE
S&F in replacement of internal wiring Kit suitable for 1.5/2.0TR window air conditioner complete all as specified and directed.
All as per item No 20 but wiring Kit suitable for 1.5/2.0 TR split type air conditioner.
S & F in replacement copper pipe ½” dia, wall thickness 0.032 mm including insulation complete all as specified & as directed.
All as per item No: 22 but copper pipe 1/4" dia, wall thickness 0.030 mm .
All as per item No: 22 but copper pipe 5/8" dia, wall thickness 0.035 mm .
All as per item No : 22 but copper pipe 3/8" dia, wall thickness 0.035 mm .
S & F in replacement of blower motor for 1.5/2 ton split type AC indoor unit as per existing shape and capacity complete all as specified and directed.
S & F in replacement of rubber bush for blower motor, set of two, suitable for window/split type AC of any make and capacity as per sample complete all as specified and directed.
S & F in replacement of louver blades synchronous motor/swing motor for 1.5/2 ton window/split type AC indoor unit of any make and capacity as per sample complete all as specified and directed.
S & F in replacement of electronic display assembly suitable for window/split type air conditioner of any make and capacity as per the sample complete all as specified and directed.
S & F in replacement of drain pipe up to 20 mm dia and up to 6 mtr length including draining pan/drip port suitable for split type air conditioner indoor unit of any make and capacity complete all as specified and directed.
S & F in replacement of blower fan blade suitable for window/split type AC of any make and capacity as per sample complete all as specified and directed.
S & F in replacement of front grill suitable for window type air conditioners 1.5/2.0TR as per sample complete all as specified and directed.
S & F in replacement of temperature sensor assembly for window/split type air conditioner 1.5/2.0 TR as per sample complete all as specified and directed.
S&F in replacement of thermostat switch for 1.5 / 2 ton window/split type AC as per sample complete all as specified and directed.
S & F in replacement of PVC insulated and sheathed multistranded copper conductor cable 3 core of size 4 sqmm dia complete all as specified and directed.
M&L for gas charging with R22/R-32 refrigerant up to required quantity to window / split type AC 1.5 / 2 Ton capacity on any make / model including flushing of gas,oil charging, necessary welding and bracing works, checking of leakage and testing on full load complete all as specified and directed Note:- No extra payment will be given to contractor to top up the gas in case of leakage from air conditioner.
All as per item No:36 but Refrigerant gas R 410
S & F in replacement of 2 way/3 way valve set of two suitable for split type AC out door unit of any make/capacity complete all as specified and directed.
S& F in replacement of sheet metal enclosure with two pin socket, chain plug cover with one MCB SP of 20-30 Amp capacity with alignment 10 KA ‘C’ series complete all as specified and as directed.
Supply and fix in replacement, 1100 Volts grade heavy duty cable PVC insulated standard aluminium conductor served with inner sheathing of PVC tape & overall PVC sheathed in service connection, one twin core cable flat or circular of size 10 Sq mm to be connected to existing MCB box / Main switches complete all as specified as dircted.
S & F in replacement of Condensor coil unit complete suitable for 1.5/2 Ton window type AC including welding/bracing work etc of existing model & make complete all as specified and as directed.
All as per item No 41 but Condensor coil unit complete suitable for 1.5/2 Ton split type AC out door unit .
S&F in Replacement of Cooling coil unit suitable for 1.5/2.0 Ton window type AC including welding/bracing work etc of existing model & make complete all as specified and directed.
All as per item No:43 but cooling coil suitable for 1.5/2.0 Ton split type AC indoor unit .
M & L for taking down Corroded body base tray etc of window type air conditioners and replacement of body base tray etc out of 18 SWG and other portion with MS sheet 20 SWG including motor mounting frame nuts and bolts suitable size painting and necessary insulation complete for 1.0 / 1.5 / 2.0 Ton capacity Air conditioner all as specified and directed. (Note : For dismantling compressor for body work and reassembling shall be inclusive in quoted rate)
M&L for taking out existing split AC of 1.5/2.0 TR capacity and reinstalled from one location to other using proper handling including making hole of existing wall for drawing copper pipe/cable to connect in-door unit and out door unit including all electric connection,testing complete all as specified and directed.
M&L for taking out existing window AC of 1.5/2.0TR from one location to another using proper handling and making necessary arrangement in existing window sitable for 1.5/2.0 TR window type AC including all electric connection,testing complete all as specified and directed.
M& L for spray painting with one coat of synthetic enamel paint of cream tint on internal & external steel surfaces of window / split type A/Cs complete including preparing the existing painted surfaces and writing SM No, MES No etc complete all as specified and directed.
M&L for Cutting & removing deteriorated sheet steel surfaces of body, chasis, body bottom portions etc, of window type air conditioners any make and capacity and reconstructing body to the exisitng shape and size with PGI sheet of 16 / 20 SWG, necessary welding / bracing work, including all necessary items such as nuts, bolts, washers, drilling holes etc. including applying two coats of synthetic enamel paint using spray gun over a coat of red oxide primer matching with the existing tint & shade complete all as specified and directed.
S & F in Replacement reversible cycle heating unit suitable for split /window type AC 1.5/2 ton capacity including necessary welding /brazing work complete all as specified and directed.
S & F in Replacement of three way switch for reversible cycle heating unit to change AC in (1) heating (2) off (3) cooling mode including making connections with suitable size wire and thimbles etc complete all as specified and directed.
S & F in Replacement of heavy duty air conditioner outdoor unit mounting bracket/stand suitable for 1.5/2.0TR split Type air conditioner as per sample complete all as specified and directed.
Dismantling the old U/S out door unit of split type AC of cap 1.5 Ton and fixing of the new out door unit complete with condensor coil, cooling coil made of copper coil , blower motor with PVC fan blade ,Wiring Kit,two pole contactor,running and starting capaciter of 40 to 45 MFD capacity including provision of fixing existing compressor & charging refrigerant gas R22 of required quantity including testing on full load all as specified & directed.
Dismantling the old U/S in door unit of split type AC of cap 1.5 Ton and fixing of the new in door unit complete with cooling coil made of copper, blower motor,swing motor,electonic PCB,Display unit,temprature sensor,box type relay complete with PVC drum & electronic circuits including testing all as specified & directed.
Dismantling the old U/S out door unit of split type AC of cap 2.0 Ton and fixing of the new out door unit complete with condensor coil, cooling coil made of copper coil , blower motor with PVC fan blade ,Wiring Kit,two pole contactor,running and starting capaciter of 50 to 60 MFD capacity including provision of fixing existing compressor & charging refrigerant gas R22 of required quantity including testing on full load all as specified & directed. Note: Charging of refrigerant gas of required quantity to be measured and paid separately
Dismantling the old U/S in door unit of split type AC of cap 2 Ton and fixing of the new in door unit complete with cooling coil made of copper, blower motor,swing motor,electonic PCB,Display unit,temprature sensor,box type relay complete with PVC drum & electronic circuits including testing all as specified & directed.
Dismantling the old U/S unit of window type AC of cap 2 Ton and fixing of the new unit complete with condensor coil and cooling coil made of copper of suitable size, blower motor with PVC fan blade & PVC drum,,electronic PCB,temprature sensor provision for fixing existing compressor & charging refrigerant gas R22 of required quantity including testing on full load all as specified & directed. Note: Charging of refrigerant gas of required quantity to be measured and paid separately
Dismantling the old U/S unit of window type AC of cap 1.5 Ton and fixing of the new unit complete with condensor coil made of copper of suitable size, cooling coil made of copper of suitable size, blower motor with PVC fan blade & PVC drum,electronic PCB,temprature sensor including provision for fixing of existing compressor & charging refrigerant gas R22 of required quantity including testing on full load all as specified & directed. Note: Charging of refrigerant gas of required quantity to be measured and paid separately
M&L for Tracing out leakage Window/Split Type AC of capacity 1.5/2 TR from suction line, discharge line, evaporation condenser, filter, capilary tube, indoor unit, outdoor unit, suction / delivery line, joints by removing AC from its original Installed location by suitable method including brazing, welding and filing of gas R-22 /R-32/ R-410A in window/Split type AC Following capacity .
S&F in repair Pin/service valve of size 1/2", 1/4", 3/8", 5/8" for window AC and Split AC 1.5/2.0 TR of any make and model complete all as specified and as directed.
M & L for Taking out of existing blower / condenser motor from split /window type AC of 1.5/2.0 TR capacity and Rewinding the same with supper ennamelled copper wire as existing gauge and varnishing complete with 'E' class varnishing incluind replacement of necessary parts regrding motor and reassembling and refixing in same position complete all as specified Note : Copper wire brought for rewinding shall be reccorded in MB wrt Pr Vr/Tax Invoice duly signed by the all concern .
M&L for servicing refrigerator of any make & capacity dismantling and taking out unserviceable parts such as starting relay,OLP, thermostat, gas drier filter, bulb etc including fixing new parts with new nut bolts and washers etc re-assembling the refrigerator after repair and testing complete all as specified and directed. Note:- Spare parts shall be measured and paid separately under respective items.
S&F in replacement starting relay assembly suitable for refrigerator of any make & capacity. Make : Godrej/Whirlpool/LG/Annapurna
S&F in replacement running capacitor 6 MFD sitable for blower motor of any make & capacity refrigerator, Make : Havells/Amcap/Epcos
S&F in replacement over load protector suitable for refrigerator of any make & capacity. Make : Godrej/Whirlpool/LG/Annapurna
S&F in replacement door handle suitable for refrigerator of any make & capacity as specified and directed.
S&F in replacement magnetic rubber door gasket suitable for refrigerator of any make & capacity as specified & directed.
S&F in replacement thermostat switch suitable for refrigerator of any make & capacity. Make : Whirlpool/LG
S&F in replacement bulb for refrigerator/deep freezer 15 Watt 220 volt screw/pin type Make : Bajaj / Omex/Philips
S&F in replacement gas drier filter suitable for refrigerator of any make & capacity complete all as secified and directed.
S&F in replacement liquid line filter suitable for refrigerator of any make & capacity complete all as secified and directed.
S&F in replacement only Ice tray superior quality.
S&F in replacement copper capillary tube size 31 gauge for refrigerator as specified & directed.
S&F in replacement copper capillary tube size 36 gauge . for refrigerator as specified & directed.
S&F in replacement copper capillary tube size 1/4" dia for AC, refrigerator and water coolers as specified & directed.
S&F in replacement PVC stand suitable for refrigerator of any make & capacity.
S&F in replacement evaporator fan motor for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement bimetal thermostat for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement temperature sensor assembly for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement electronic power supply control PCB for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement electronic timer circuit for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement manual timer for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement freezer evaporator assembly for double door/single door refrigerator of any make & capacity as specified and directed.
S&F in replacement PVC freezer door assembly complete with door spring for refrigerator of any make / capacity complete all as specified and as directed.
M&L for gas charging with R-134a/R-600 refrigerant up to required quantity to refrigerator of any make and capacity range 150 to 250 Ltr including flushing of gas,oil charging, necessary welding and bracing works, checking for leakage and testing on full load complete all as specified and as directed. Note:- No extra payment will be given to contractor to top up the gas in case of leakage from refrigerator.
All as per Item No 85 But refrigerator capacity Range 280 to 350 Ltr
M & L for applying a coat of superior quality duco paint of approved tint and shade on the external painted surfaces of refrigerators of any capacity using a spray jet gun including necessary preparation of old painted surfaces including writing of MES No and SM No complete all as specified and directed.
S&F in replacement inverter circuit/card of any make & capacity as specified and directed. Whirlpool/LG/voltas/samsung or equivelent
S&F in replacement ice chamber (Freezer) assembly complete suitable for 280-350 ltrs refrigerator of any make / capacity surrounded by freezer pipes complete all as specified and directed.
All as per item No:89 but ice chamber (Freezer) assembly complete suitable for 150-250 ltrs refrigerator
Supply & fixing condenser coil suitable for 280-350 ltrs refrigerator of any make and capacity including welding /bracing work complete as specified and directed.
All ass per item No:91 but condenser coil suitable for 150-230 ltrs refrigerator
S&F in replacement sealed compressor suitable for 150-250 Ltr capacity ISI Marked for refrigerator of any make and model as per sample suitable for working on 230 V 50Hz including necessary welding/bracing work complete all as specified & directed.
All as per item No:93 but sealed compressor suitable for 280-350 ltr capacity
M&L for Stripping up deep freezer of any make & capacity dismantling and taking out unserviceable parts such as relay,over load, thermostat, gas drier filter, bulb etc including fixing new parts with new nut bolts and washers etc re-assembling the deep freezer after repair and testing complete all as specified and directed. Note:- Spare parts shall be measured and paid separately under respective items
S&F in replacement blower fan 5"x5" size 220 VAC 50/60 Hz 0.1 Amp suitable for deep freezer of any make and capacity complete all as specified and directed.
S&F in replacement blower motor with fan blade including nuts, bolts and clamps etc for deep freezer of any make and capacity complete all as specified and directed.
S&F in replacement over load protector for deep freezer of any make/capacity. Make- Technomech/Classic/Annapurna.
S&F in replacement starting relay assembly suitable for Deeb freezer of any make/capacit. Make- Technomech/Classic/Annapurna.
S&F in replacement liquid line filter suitable for deep freezer of any make & capacity complete all as secified and directed.
S&F in replacement thermostat switch for deep freezer of any make and capacity Make : Renutol / Danfoss
S&F in replacement electronic timer circuit for deep freezer 200-300 ltrs capacity of any make as specified and directed.
M&L for gas charging with R134a refrigerant up to required quantity to deep freezer of any make and capacity including flushing of gas,oil charging, necessary welding and bracing works, checking for leakage and testing on full load complete all as specified and as directed. Note:- No extra payment will be given to contractor to top up the gas in case of leakage from deep freezer.
S&F in replacement condenser coil complete with copper tube and aluminium fins suitable for deep freezer 200-320 ltrs capacity of any make and necessary welding/bracing work complete all as specified and directed.
S&F in replacement sealed compressor new suitable for 200-250 ltr capacity deep freezer of any make and model as per sample including necessary welding / bracing work to existing refrigerant pipes complete all as specified & directed.
All as per item No:105 but sealed compressor suitable for 300/320 ltr capacity deep freezer
M&L for Stripping up water cooler (storage type) of any make & capacity dismantling and taking out unserviceable parts such as starting relay, OLP, thermostat, capacitors, gas drier filter, push cock, floot valve, fan blade etc including fixing new parts with new nut bolts and washers etc re-assembling the water cooler after repairs and testing complete all as specified and as directed.
Taking out and opening carefully blower motor, fan blade of water cooler 40/80 ltrs & 60/120 ltrs & 150 Ltr dismantling, cutting and removing the unserviceable copper winding wire of blower motor and rewinding with super enamelled copper winding wire of existing gauge including replacement of unserviceable bushes/bearings, long nuts, bolts etc and reasembling complete all as specified and directed.
S&F in replacement thermostat switch for water cooler of any make and capacity Make : Renutol / Danfoss
S&F in replacement Starting capacitor 40/60 MFD 250 VAC Make : Make : Havells/Amcap/Epcos
S&F in replacement Starting capacitor 60/80 MFD 250 VAC Make : Make : Havells/Amcap/Epcos
S&F in replacement Box type starting relay assembly suitable for water cooler of any make/capacity. Make- Technomech/Classic/Annapurna.
S&F in replacement starting relay assembly suitable for water cooler of any make/capacit. Make- Technomech/Classic/Annapurna.
S&F in replacement over load protector for water cooler of any make/capacity. Make- Technomech/Classic/Annapurna.
S&F in replacement gas drier filter two way/One way for water cooler of any make & capacity.
S&F in replacement liquid line filter for water cooler of any make & capacity.
S&F in replacement copper capillary tube size 50 No. for water coolers as specified & directed.
S&F in replacement CP push cock / lifting cock (water taps) suitable for 15 mm dia pipe complete all as specified and directed.
S&F in replacement PTMT push cock made of stainless steel having 15 mm dia Make : Prayag / Polytuf
S&F in replacement blower motor 1/10 HP with fan blade including nuts , bolts and clamps etc for any make and capacity of water cooler complete all as specified and directed.
S&F in replacement blower motor 1/35 HP with fan blade including nuts , bolts and clamps etc for any make and capacity of water cooler complete all as specified and directed.
S&F in replacement PVC fan blade for blower motor of any size for water cooler complete all as specified and directed.
S&F in replacement PVC float valve assembly complete for 15 mm dia suitable for water cooler complete all as specified and directed. Make : Prayag / Polytuf
S&F in replacement CP brass nipple 15 mm x 125 mm for water out let pipe all as specified and directed.
S&F in replacement PVC connection 15 mm x 450 mm long for water cooler Make : Prayag / Polytuf
S&F in replacement PVC flexible pipe 32 mm dia for water cooler drain out pipe complete all as specified and directed
S&F in replacement of PVC insulated and sheathed multistranded copper conductor cable 3 core of size 2.5 sqmm dia for external connection of water cooler, Refrigerator & voltage stablizer Make : Havells/ Plaza/Finolex
S&F in replacement condenser coil complete with copper tube and aluminium fins suitable for water cooler 40/80 ltrs, 60/120 ltrs & 150 ltrs capacity of any make with welding/bracing work complete all as specified and directed.
M&L for gas charging with R22/R134a refrigerant up to required quantity of water cooler any make & capacity including flushing of gas,oil charging, including replacement of necessary capilliary copper tube, necessary welding and bracing works, checking of leakage and testing on full load complete all as specified and directed. Note:- No extra payment will be given to contractor to top up the gas in case of leakage from water cooler.
M & L for applying a coat of superior quality duco paint of approved tint and shade on the external painted surfaces of water cooler any make & capacity using a spray jet gun including necessary preparation of old painted surfaces and applying a coat of black synthetic enamel paint to all internal parts such as compressor unit, condensor fan etc, and writing of MES No and SM No complete all as specified and directed.
S&F in replacement hermetical sealed compressor unit suitable for water cooler 40/80 ltrs capacity Make- Emerson copeland Model No. KCN415 LAG/KCJ444HAG or equivalent approved make, suitable for working on 230 V 50Hz including necessary welding/bracing work complete all as specified & directed.
All as per Item No:131 but hermetical sealed compressor unit suitable for water cooler 60/120 ltrs capacity Make- Emerson copeland Model No. HY113 B/S / KCN463HAG or equivalent approved make,
All as per item No:131 hermetical sealed compressor unit suitable for water cooler 150 ltrs capacity Make- Emerson copeland Model No. KCJ513HAE/KCM511CAL or equivalent make.
S&F in replacement of 1100 Volts grade heavy duty cable PVC insulated stranded aluminium conductor served with inner sheathing of PVC tape & overall PVC sheathed in service connection suspended by insulating hanger not more than 1 meter apart including 4 mm GI suspension wire one twin core cable flat or circular of size 6 Sq mm to be connected to existing sheet metal enclosure complete all as specified and as directed.
M&L For Repairs to water cooler body, base frame with legs, door unit, storage tank, FHP motor base etc of any capcity & make by cutting worn out / deteriotrated portions of sheet steel and reconstructing body including providing ventilation grooves, hinges where required and steel storage tank to the exisitng shape and size using PGI sheet of 16 SWG as per the existing, necessary welding / bracing work to match with the existing surface, including all necessary items such as nuts, bolts, washers, drilling holes etc. and applying two coats of synthetic enamel paint on the affected previously painted area using spray gun over a coat of red oxide primer matching with the existing tint & shade complete all as specified and directed.
Repair of automatic voltage stabilizer 5 / 4/ 3 KVA single phase 230 volts 50 Hz of any make by opening the stabilizer and replacement of the defective parts such as main transformer, auto transformer , indicators etc, and reassembling and testing the stabilizer on full load for satisfactory performance complete all as specifeid and directed.
All as per Item No :136 but automatic voltage stabilizer 0.5/ 1/ 2 KVA single phase 230 volts 50 Hz
M&L for cutting and removing existing short circuited windings of 5 / 4 KVA main transformer of voltage stabilizers 160 volts to 260 volts or 140 volts to 270 volts AC single phase and re-winding the same with super enamelled copper winding wire of existing gauge complete all as specifeid and directed.
All as per item No:138 but 3 / 2 KVA main transformer of voltage stabilizers 160 volts to 260 volts or 140 volts to 270 volts AC single phase .
All as per item No :138 but 1/0.5KVA main transformer of voltage stabilizers 160 volts to 260 volts or 140 volts to 270 volts AC single phase .
S&F in replacement of auto transformer 6/12 volts output and 220 volt input suitable for 5 / 4/ 3 KVA voltage stabilizer complete all as specifeid and directed.
All as per item No:141 but voltage stablizer of capacity 0.5/ 1/ 2 KVA.
S&F in replacement electromagnetic relay 12 volts 25 Amp complete all as specified and directed.
All as per item No:143 but electromagnetic relay 12 volts 10 Amp
All as per item No:143 but electromagnetic relay 12 volts 5 Amp .
S&F in replacement printed circuit board for high low cut off & time delay circuit 12 volts 10 Amp for 2/ 3 KVA stabilizer complete all as specifeid and directed.
All as per item No:146 but high low cut off & time delay circuit 12 volts 25 Amp for 4/ 5 KVA stabilizer
S&F in replacement printed circuit board for control 12 volt system 5 Amps for 0.5 / 1 KVA stabilizer complete all as specifeid and directed.
All as per item No:148 but printed circuit board for control 12 volt system 10 Amps for 2/ 3 KVA stabilizer.
All as per item No:148 but printed circuit board for control 12 volt system 25 Amps for 4/ 5 KVA stabilizer.
S&F in replacement voltmeter 0 to 250 volts for voltage stabilizer complete all as specified and directed.
S&F in replacement digital voltmeter 0 to 250 Volt AC for voltage stabilizer complete all as specified and directed.
S&F in replacement indicator lamp (LED type) for voltage stabilizer complete all as specified and directed.
S&F in replacement toggle switch for voltage stabilizer as per existing size complete all as specified and directed.
S&F for sub main wiring with PVC insulated, unsheathed 2 single core cable 1100 volts grade with copper conductor of size 6 sq mm (Nominal area) multi stranded drawn into conduit (Existing / new) with and including 4 sqmm green stranded copper conductor as contineous earthwire with lugs complete all as specified and as directed. Note: New conduit and conduit accossories shall be measured separately.
S&F for sub main wiring with PVC insulated, unsheathed 2 single core cable 1100 volts grade with copper conductor of size 4 sq mm (Nominal area) multi stranded drawn into conduit (Existing / new) with and including 2.5 sqmm green stranded copper conductor as contineous earthwire with lugs complete all as specified and as directed. Note: New conduit and conduit accossories shall be measured separately.
S & F Regid non-metallic PVC conduit not less than 20 mm dia (external) ISI marked (on surface) incl of all accessories and all fittings such as Tees,bends, elbows, reducers, bell mouth, tube ends and fixing accossories such as couplers,lock nuts, saddles, pipe hook etc complete all as specified and as directed
SHRI HARI CONSTRUCTION
M/s Ravi Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .