| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.0 LAccepted-AOC | L1 | Accepted-AOC L1 Accepted | |
| 2 | L2₹8.1 L+₹1.1 L (16.1%)Rejected-Finance | L2 | Rejected-Finance Other than L1 after deducting Sch of Credit Rs 84,000.00 | |
| 3 | L3₹9.6 L+₹2.6 L (37.5%)Rejected-Finance | L3 | Rejected-Finance Other than L1 after deducting Sch of Credit Rs 84,000.00 |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
31 Dec 2021, 6:00 pmClosed
GE North Akhnoor
GE North Akhnoor C/O 56 APO
REPAIR MAINT OF DG SET AND CONNECTED DISTRIBUTION PANELS AND CONNECTED ITEMS UNDER GE NORTH AKHNOOR
2021_MES_491764_1
GE(N)/AKH-62/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Akhnoor
Class E cat b i
8 documents required · 8 mandatory
₹500
Yes
GE North Akhnoor
₹16,000
Yes
11 Feb 2022
3 Dec 2021
3 Jan 2022
3 Dec 2021
31 Dec 2021
17 Dec 2021
Amount
S & F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made main LT Panel. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel should be anti-acid & anti corrosive. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer shall share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. The manufacturer of panel SHALL submit a copy of CPRI TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits.The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960°C in accordance with 60695-2-11 [flame retardant and self-extinguishing. Make- Hensel/Schneider/ABB/L&T Incomer i. Main MCCB 400A 4Pole Breaking Capacity 36KA adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 No. ii. Digital VAF Meter with Volt,Amp, Frequency – 1 Nos iii. LED Indicator Lamp R,Y,B – 3 Nos iv. CT coils 400/5A – 3 Nos v. Control Fuse – 3 Nos
Outgoings i. MCCB 250A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos. ii. MCCB 125A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos. iii. MCCB 100A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos. iv.MCCB 63A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos.
S & F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made main LT Panel. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel should be anti-acid & anti corrosive. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer shall share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. The manufacturer of panel SHALL submit a copy of CPRI TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits.The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. Make- Hensel/Schneider/ABB/L&T
INCOMER Main MCCB 250A 4Pole Breaking Capacity 36KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 No.
Digital VAF Meter with Volt,Amp, Frequency – 1 No
LED Indicator Lamp R,Y,B – 3 Nos
CT coils 250/5A – 3 Nos
Control Fuse – 3 NoS
OUTGOINGS MCCB 160A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos.
MCCB 125A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos.
MCCB 100A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos.
MCCB 63A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos.
S & F in repairs, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made main LT Panel. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel should be anti-acid & anti corrosive. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer shall share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. The manufacturer of panel SHALL submit a copy of CPRI TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits.The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. Make- Hensel/Schneider/ABB/L&T
INCOMINGS Main MCCB 160A 4Pole Breaking Capacity 36KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 No.
Digital VAF Meter with Volt,Amp, Frequency – 1 No
LED Indicator Lamp R,Y,B – 3 Nos
CT coils 160/5A – 3 Nos
Control Fuse – 3 Nos
Outgoings
MCCB 125A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 1 Nos.
MCCB 100A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 2 Nos.
MCCB 63A 4Pole Breaking Capacity 36 KA Adj. Thermal and Magnetic Setting with Spreader Links & Extended Rotary Handle – 2 Nos.
Jiwan Singh
m/s vishkarma construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .