Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹7.8 Cr 2 CORRIGENDUM ADDENDUM 01 DATED 11 01 2024 3 YOUR TENDER SUBMITTED ON 15 01 2024 ON E TENDER WEBSITE 4 CORRIGENDUM ADDENDUM 02 DATED 06 02 2024 5 YOUR PRICE BID OPENED ON 06 02 2024 ON E TENDER WEBSITE | ₹7.8 Cr |
Tender Value
₹10.2 Cr
EMD Value
₹10.2 L
Closing Date
12 May 2023, 11:00 amClosed
Supply, Installation, Testing & Commissioning of 2x20 MVA 33/11 KV Sub-Station at Nauroji Nagar, New Delhi
NBCCRBGRedevNauroji062023Date24042023
NBCCRBGRedevNauroji062023Date24042023
Open Tender-Domestic
Electrical Work
New Delhi, Delhi
₹11,800
₹10.2 L
24 Jul 2026
24 Apr 2023
12 May 2023
12 May 2023
8 Jun 2023
Providing and laying in position cement concrete of specified grade excluding the cost of
centering and shuttering - All work up to plinth level :
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone
aggregate 40 mm nominal size derived from natural sources) cum 70 6326.05 4,42,823.50
Providing and laying in position specified grade of reinforced cement concrete, excluding
the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :
1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone
aggregate 20 mm nominal size de rived from natural sources) cum 162 8364.20 13,55,000.40
1.4 5.9 Centering and shuttering including strutting, propping etc. and removal of form for
1.4.1 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete Sqm 98 307.95 30,179.10
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses
Steel reinforcement
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding all complete upto plinth level.
1.5.1 5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kG 9 000 89.65 8,06,850.00
Providing, hoisting and fixing above plinth level up to floor five level precast reinforced
cement concrete (Drain Covers) work in string courses, bands, copings, bed plates, anchor
blocks, plain window sills and the like, including the cost of required centering, shuttering
but, excluding cost of reinforcement with 1:1.5:3 (1 cement: 1.5 coarse sand (zone-III)
derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from
natural sources). cum 162 9673.50 15,67,107.00
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations
1.7 2.25 etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming
and watering, lead up to 50m and lift upto 1.5m. cum 230 253.95 58,408.50
2.0 FIRE RATED WALL
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in
superstructure above plinth level up to floor V level in all shapes and sizes in :
2.1.1 6.4.2 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 12 8288.35 99,460.20
2.2 13.1 12 mm cement plaster:
2.3 13.2 15 mm cement plaster
3.0 FENCING WALL
R.C.C. Standards post/ struts/ rails/ pales of mix 1:1.5:3 (1 cement : 1.5 coarses and : 3
graded stone aggregate 12.5 mm nominal size) with wooden plugs or 6mm bar nibs
wherever required as per direction of Engineer-in charge (cost of earth works in excavation,
concrete works in foundation to be paid separately) cum 1 28603.00 28,603.00
Fencing with R.C.C. post placed at required distance, embedded in cement concrete
blocks, every 15th post, last but one end post and corner post shall be strutted on both
sides and end post one side only, provided with horizontal lines and two diagonals of
3.2 16.17.1 barbed wire weighing 9.38 kg per 100 metres (minimum), between the two posts fitted and
fixed with G.I. staples on wooden plugs or G.I. binding wire tied to 6 mm bar nibs fixed while
casting the post (cost of R.C.C. posts, struts, earth work and concrete to be paid for
separately) :- Payment to be made per metre cost of total length of barbed wire used.
3.2.1 With G.I. barbed wire meter 60 12.45 747.00
4.0 Hot Dipped Galvanized Iron Cable Tray
4.1 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray
(galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc. as required.
4.1.1 4.6.4 300 mm width X 50 mm depth X 1.6 mm thickness Meter 100 963.00 96,300.00
4.1.2 4.6.6 450 mm width X 50 mm depth X 2.0 mm thickness Meter 10 1325.00 13,250.00
4.1.3 4.6.14 600 mm width X 75 mm depth X 2.0 mm thickness Meter 10 1955.00 19,550.00
Digitally signed by GOTETI
Ref (DSR(Civil)-2021
S.No. Description. Unit. Qty Rate Amount
and DSR(E&M)2022
4.2 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray
“bends” (galvanisation not less than 50 microns) withperforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc. as required
4.2.1 4.7.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 6 1852.00 11,112.00
4.2.2 4.7.6 450 mm width X 50 mm depth X 2.0 mm thickness Each 1 2683.00 2,683.00
4.2.3 4.7.14 600 mm width X 75 mm depth X 2.0 mm thickness Each 1 4131.00 4,131.00
4.3 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray
“Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc. as required
4.3.1 4.10.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 1 2823.00 2,823.00
4.3.2 4.10.6 450 mm width X 50 mm depth X 2.0 mm thickness Each 1 3721.00 3,721.00
5.0 HT CABLE LAYING
Laying of one number XLPE insulated power cable of 33 KV grade of following size in the
existing masonry open duct/ cable tray as required.
6.0 HT CABLE END TERMINATION
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete
6.1 10.7 with all accessories including lugs suitable for following size of single core, XLPE aluminium
conductor cable of 33 KV grade as required :
Supplying and making outdoor cable end termination with heat shrinkable jointing kit
6.2 10.8 complete with all accessories including lugs suitable for following size of single core, XLPE
aluminium conductor cable of 33 KV grade as required :
Earthing with copper earth plate 600 mm X 600 mm X 6 mm thick including accessories,
and providing masonry enclosure with cover plate having locking arrangement and watering
pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
Supplying and laying 50 mm X 5 mm copper strip at 0.50 Meter below ground as strip earth
electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.
(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer
spaced at 50mm) Meter 200 972 1,94,400.00
Providing and fixing 50 mm X 5 mm copper strip in 80 mm dia G.I. pipe from earth electrode
7.3 5.10 including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as
required. Meter 500 1551 7,75,500.00
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections
etc. as required. Meter 50 2113 1,05,650.00
Providing and fixing H.T. danger notice plate of 250 mm x 200 mm, made of mild steel, at
least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single
red Colour on front side as required as per specifications of this tender and directions of
Engineer-in-Charge. Each 3 292 876.00
Total of the Schedule items 73,05,047.00
Non-Schedule items
33KV SIX GIS HT PANEL (INDOOR)- TWO INCOMERS, ONE BUS COUPLER AND
THREE OUTGOINGS
Design, manufacture, supply, shop inspection, Installation , Testing & commissioning of 6
panel, 33 kV HT GIS switch board in the 33KV Switchgear room with following accessories:
1250A, 33KV, 31.5 KA for 3 Sec., TP, motorised spring charged closing mechanism, motor
voltage 230V AC, shunt tripping & closing coil voltage 50V DC, electrically operated, trip
free, dust & vermin proof, GIS panel with mechanical & Electrical OFF/ ON indicators &
provided with following:
Current transformers as detailed in technical specifications and SLDs
3‐phase Directional & Non-directional relay with IDMT, Definite time and Instantaneous
characteristics, as per technical specifications
Micro-processor based, communicable type line current differential relays
Anti Pumping Relay
Master Trip Relay
Trip circuit supervision relay
Voltage transformers as detailed in technical specifications and SLDs
6 Windows Annunciator with Hooter & Accept Button:
1 window for over current trip
1 window for earth fault trip
1 window for master trip relay
1 window for emergency stop push button
2 windows spare
Digitally signed by GOTETI
Ref (DSR(Civil)-2021
S.No. Description. Unit. Qty Rate Amount
and DSR(E&M)2022
Digital Multifunction meter with MDI, communicable type (V, A, Hz PF, KVA, KVARH, KWH,
KVAR, KVAH, KW).
Voltmeter with selector switch.
Ammeter with selector switch.
A set of breaker ON/ OFF/ Trip/ DC control supply healthy/ Trip circuit healthy/ Spring
Charged & R,Y,B Phase Indication Lamps.
Emergency stop push button
6 NO/ 6 NC breaker auxiliary contacts
Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement,
pistol grip type.
Surge arrestor as per technical specifications and SLD
All control wiring with protection & test terminal block as required.
Strip heater with thermostat for moisture absorption.
Suitable for connection to 33 KV, 2R x 3C x 400 Sqmm XLPE armoured, aluminium
conductor cable for incoming and outgoing feeders.
Cable box for 33 KV, 2R x 3C x 400 Sqmm XLPE armoured, aluminium conductor cable.
HT Danger Plate
Each Incoming as described above.
1600A, 33kV, 31.5KA for 3 Sec., 3 phase, Electrolytic grade copper bus bars.
1250A, 33kV, 31.5KA for 3 Sec., TP, motorised spring charged closing mechanism, motor
voltage 230V AC, shunt tripping & closing coil voltage 50V DC electrically operated, trip
free, dust and vermin proof, GIS panel with mechanical & Electrical OFF/ ON indicators &
provided with following:
Current transformers as per SLDs
3‐phase Non-directional relay with IDMT, Definite time and Instantaneous characteristics,
as per technical specifications
Window annunciator (window as per alarm/trip annunciation requirement)
A set of breaker ON/ OFF/ Trip/ DC control supply healthy/ Trip circuit healthy/ Spring
Charged indication lamp.
Emergency stop push button
6 NO/ 6 NC breaker auxiliary contacts
Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement,
pistol grip type.
All control wiring with protection & test terminal block as required.
Strip heater with thermostat for moisture absorption.
1250A, 33kV, 31.5KA for 3 Sec., TP, motorised spring charged closing mechanism, motor
voltage 230V AC, shunt tripping & closing coil voltage 50V DC electrically operated, trip
free, dust & vermin proof, GIS panel with mechanical & Electrical OFF/ ON indicators &
provided with following:
Current transformers as detailed in technical specifications and SLDs
Ammeter with selector switch
3‐phase Non-directional relay with IDMT, Definite time and Instantaneous characteristics,
as per technical specifications
Micro-processor based Transformer differential and 11KV side REF protection relay
Anti Pumping Relay
Master Trip Relay
Trip circuit supervision relay
A set of breaker ON/ OFF/ Trip/ DC control supply healthy/ Trip circuit healthy/ Spring
Charged indication lamp.
Digitally signed by GOTETI
Ref (DSR(Civil)-2021
S.No. Description. Unit. Qty Rate Amount
and DSR(E&M)2022
Auxiliary relays for transformer faults as per specifications
window annunciator as required with Hooter & Accept Button:
Emergency stop push button
6 NO/ 6 NC breaker auxiliary contacts
Control:-T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement,
pistol grip type.
Surge arrestor as per technical specifications and SLD
All control wiring with protection & test terminal block as required.
Strip heater with thermostat for moisture absorption.
Cable box for 33 KV, 2R x 3C x 400 Sqmm XLPE armoured, aluminium conductor cable.
HT Danger Plate
Each Outgoing as described above.
Important Note :
1. Both the incomers breakers & the Bus coupler breaker shall be Electrically &
Mechanically interlocked to ensure only two breakers are 'ON' at a time.
2. Supply, laying and termination of the cables from 11kV incomers CTs and neutral CT of
transformer to the transformer feeders for 11kV side REF protection plus the cables for aux.
AC supply to the GIS panels from existing distribution board are also included in the above
SIX PANEL 33kV GIS HT PANEL AS DESCRIBED ABOVE set 1 2,12,23,070.86 2,12,23,070.86
10 POWER TRANSFORMER (OIL FILLED TYPE)
Design, manufacture, supply, shop inspection, assembly at site, installation, testing and
commissioning of 20 MVA Power Transformer as per IS:2026 with percentage impedance
10.24% (without negative tolerance),33 KV/11 KV, 3 phase, 50 Hz delta/ star connected,
Vector Group Dy 11, out door, oil filled, copper wound, KNAN cooled transformer,
temperature rise (Oil/ Winding -50/55 deg C) complete with all fittings such as ON Load
Tap Changer + 5 % to –15% tapping at the step of 1.25%, RTCC panels, bi-directional
roller, diagrams & rating plate & Winding temperature indicator, lifting lugs, termination of
cable on 33 KV/ 11 KV side with bottom entry. Losses at rated voltage and frequency will
be No Load- 13 KW and Full Load- 120 KW (Approximate), Fitting and accessories as
per the technical specifications will be provided (Supply, laying and termination of the
control cables and cables for auxiliary power supply from respective transformer feeders to
the transformer M.B. cubicle and RTCC panels is also included).
10.1 MR 20 MVA Power Transformer as mentioned above. Nos 2 3,42,77,255.52 6,85,54,511.04
11.0 HT CABLE SUPPLY
Supply of following sizes of 33 KV grade Stranded Compact Circular Aluminium Conductor,
Conductor screen with extruded semi conducting compound, XLPE Insulated, insulation
11.1 screening with extruded semi conducting compound in combination with Copper Tape, Al
flat strip and overall PVC sheathed cable conforming to IS 7098(Part II) 1985 with latest
ammendments as required.
11.1.1 MR 3C X 400 sq. mm Aluminium Conductor Meters 300 3585.27 10,75,582.22
Supply, Installation, Testing & Commissioning of NDMC Metering Panel (with Trivector
energy meter for each incoming panel) in the exisiting metering room. Panels shall be
completely metal enclosed and shall be dust moisture and vermin proof. Panel enclosures
12.0 MR shall provide a degree of protection not less than IP31 as per IS:2147 with latest
amendments thereof (Note: Supply, laying and termination of the CT/PT cables in the
exsting cable trench from incomers of GIS panels to metering panel, located in the existing
metering room as per technical specifications is also included).
Design, supplying, installation, testing and commissioning of Nitrogen Injection Fire
13.0 MR Protection System (NIFPS) for 20 MVA transformer as per latest CEA notifications and
technical specifications Nos. 2 14,31,679.55 28,63,359.09
Design, manufacture, assembly, supply, erection, testing & commissioning of 50 VDC, 30
Amp float cum boost battery charger for trickle/ boost charging alongwith DCDB for 230 V, 1-
phase, 50 Hz AC input supply with indications, protection and instrumentation complete as
per detailed technical specifications.
Design, manufacture, assembly, supply erection, testing & commissioning of 50V DC, 200
AH Battery bank having VRLA batteries, duly charged complete with connecting lead
15.00 MR mounting stand etc. as required, suitable for control supply to 33 KV board (Note: Supply,
laying and termination of cables pertaining to battery and battery charger and cables to GIS
panels for auxilary DC supply is also included in the prices).
Ladder Type Cable Trays
Digitally signed by GOTETI
Ref (DSR(Civil)-2021
S.No. Description. Unit. Qty Rate Amount
and DSR(E&M)2022
`16.0 Supply & installation of prefabricated hot dip galvanized steel ladder type cable trays,
(galvanisation not less than 50 microns) including bends, tees & reducers fabricated out of
hot rolled sheet steel with rigid welded construction with a rung as per standard and
specifications, of approved make and cable tray fittings, including all labour and materials,
as per approved drawings, specifications of this tender and directions of Engineer-in-
750 mm wide (Runners 25 x 75 x 25 x 2.5 mm and Rungs 20 x 30 x 20 x 2.5 mm 250 mm
center to center.) Meter 100 1876.18 1,87,617.92
600 mm wide (Runners 25 x 75 x 25 x 2.5 mm and Rungs 20 x 30 x 20 x 2.5 mm 250 mm
center to center.) Meter 150 1686.19 2,52,928.09
450 mm wide (Runners 25 x 75 x 25 x 2.5 mm and Rungs 20 x 30 x 20 x 2.5 mm 250 mm
center to center.) Meter 20 1527.06 30,541.29
17.0 MR SAFETY ITEMS
Supplying and fixing of standard shock restoration chart in heavy wooden frame with 3mm
thick plain glass as per specifications of this tender and directions of Engineer-in-Charge.
Supplying and fixing of 11 KV grade nominal 2.5 mm +/- 10% thick insulated Synthetic Mat
conforming to IS 15652: 2006 and meeting the requirements of IS 5216 (Part1, 2 & 3), IS
17.2 8437, IEC-479 Pub-1, along-with suitable adhesive/ chemibound, Pu resin, waterproofing
compound and sealing material as per in service recommendation as per specifications of
this tender and directions of Engineer-in-Charge.
Supplying and fixing of 33 KV grade Class C nominal 3.0 mm +/- 10% thick insulated
Synthetic Mat conforming to IS 15652: 2006 and meeting the requirements of IS 5216
17.3 (Part1, 2&3), IS 8437, IEC-479 Pub-1, along-with suitable adhesive/ chemibound, Pu resin,
waterproofing compound and sealing material as per in service recommendation as per
specifications of this tender and directions of Engineer-in-Charge.
Supply and fixing safety instruction chart in word duly framed with 5mm thick glass required
as per specifications of this tender and directions of Engineer-in-Charge. Nos. 2 459.58 919.16
Supply of Rubber hand gloves suitable for 33 KV as per specifications of this tender and
directions of Engineer-in-Charge. Pair 4 937.15 3,748.62
Providing & fixing of set of 4 Nos 9.0 Litre capacity GI bucket painted in post office red
Colour with prior coat of red - oxide paint and written with white paint 'Fire' and mounted on
MS angle iron frame with bracket of appropriate size and capacity including filling sand etc
as per specifications of this tender and directions of Engineer-in-Charge.
Supply of First Aid box as approved by St. John Ambulance Brigade/ Indian red Cross
17.7 conforming to IS 2217 -1963 as per specifications of this tender and directions of Engineer-
Liaison and coordination with NDMC, Chief Electrical Inspectorate, Govt. of NCT of Delhi
18.00 and other statutory bodies for approvals regarding the substation energization and other
necessary clearances/ NOCs are also deemed to be included in the quoted prices.
The statutory fees/ charges as applicable in this regard shall be payable to the contractor
separately upon production of challan/ receipt of deposit/ payments made to the relevant
statutory body/ authority in this regard.
Total of the Non-Schedule items 9,50,82,563.02
Total Estimated cost (Including GST) 10,23,87,610.02
Say, Total Estimated cost (Including GST) 10,23,87,610.00
Digitally signed by GOTETI
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
GCCPMC2022inclamendment1to3.pdf
Tender Document
Technicalspecifications.pdf
Tender Document
ListofApprovedMakes.pdf
Tender Document
BoQ.pdf
Tender Document
Drawings1Schematicfor 3KV Substation.pdf
Tender Document
Drawinbs2Substation layout.pdf
Tender Document
SCC.pdf
Tender Document
IntegrityPact.pdf
Tender Document
corrigendum-1567-corrigendum 1.pdf
pdf • 1.21 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .