| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 CrAdmitted-Finance A 249 1ST FLOOR TODAY BLOSSOM 1 SEC 47 GURUGRAM | GURUGRAM | GURUGRAM | HARYANA | ₹1.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.9 Cr+₹2.6 L (1.39%)Admitted-Finance | ₹1.9 Cr+₹2.6 L (1.39%) | L2 | Admitted-Finance |
| 3 | L3₹2.1 Cr+₹27.4 L (14.6%)Admitted-Finance | ₹2.1 Cr+₹27.4 L (14.6%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | GROVER APPLIANCES L2 | Rehman Builders Pvt. Ltd. L3 | JMD ELECTRICALS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Designing, Supply and erection of DG set of capacity 1050 KVA with noise controlled devices acoustic of suitable rating, testing and commissioning of diesel generating set, radiator cooled, 3 phase, 4 wire, 50 cycles 415 plus (-)1% volts AC alternator coupled directly through a set of flexible coupling on a common MS fabricated base frame with diesel engine complete with suitable size incoming cable from generator to change over/AMF panel, making 2nd incoming cable connection from transformer, outgoing cable connection from changeover/ standard panel, making second incoming cable connection from transformer, outgoing cable connection from changeover / STD panel to incomer of motor starter panel, fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. The rating should be at 1500 RPM.
a) Diesel Engine, b) Alternator c) Battery 24 V. d) Base Plate. e) suitable sq.mm suitable core copper cable upto 40 meters. f) Tools, standard panel g) Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT`s) h) Metering set 60/5A/110V (Amp. Meter, Volt Meter) i) Overload protection for DC-1 No. j) Battery Charger 24V DC k)Copper bus bar of suitable size l) KWH meter 96 sqmm size m) Starting fuse button and key switch9on/off) n) Indicating lamps for low lubricated oil pressure, high coolant temperature, set running, load on, Dc control and other required accessories complete in all respects to the satisfaction of Engineer-in-charge` | 1 | Each | 94,80,500 ₹94,80,500 | 88,40,000 ₹88,40,000 | 76,00,000 ₹76,00,000 Lowest |
| 2.00 | Designing, Supply and erection of DG set of capacity 750 KVA with noise controlled devices acoustic of suitable rating, testing and commissioning of diesel generating set, radiator cooled, 3 phase, 4 wire, 50 cycles 415 plus (-)1% volts AC alternator coupled directly through a set of flexible coupling on a common MS fabricated base frame with diesel engine complete with suitable size incoming cable from generator to change over/AMF panel, making 2nd incoming cable connection from transformer, outgoing cable connection from changeover/ standard panel, making second incoming cable connection from transformer, outgoing cable connection from changeover / STD panel to incomer of motor starter panel, fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. The rating should be at 1500 RPM.
a) Diesel Engine, b) Alternator c) Battery 24 V. d) Base Plate. e) suitable sqmm suitable core copper cable upto 40 meters. f) Tools, standard panel g) Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT`s) h) Metering set 60/5A/110V (Amp. Meter, Volt Meter) i) Overload protection for DC-1 No. j) Battery Charger 24V DC k)Copper bus bar of suitable size l) KWH meter 96 sqmm size m) Starting fuse button and key switch9on/off) n) Indicating lamps for low lubricated oil pressure, high coolant temperature, set running, load on, Dc control and other required accessories complete in all respects to the satisfaction of Engineer-in-charge` | 1 | Each | 67,54,500 ₹67,54,500 Lowest | 70,71,650 ₹70,71,650 | 68,00,000 ₹68,00,000 |
| 3.00 | Supply, erection, testing and commissioning of 2000 KVA 11 KV / 0.433 KV, 3 Phase, 50 Hz, Copper wound, off-load tap charging links on HV side including first filling of filtered Dehydrated oil including entire cable network from G.O. switch to H.T metering equipment and from H.T metering to Transformer from transformer to main to L.T panel, earthing, safety equipment, fenced enclosure for transformer, including incoming and outgoing VCB, required H.T./L.T. Cables, ACB 3200 Incomer, Bus Coupler and any other required equipment/work as per site condition complete in all respect as per approved make and directions of Engineer-in-charge complete to the entire satisfaction.
Make - Kirloskar / Crompton / Voltamp / Schneider | 1 | Each | 27,25,500 ₹27,25,500 Lowest | 55,25,000 ₹55,25,000 | 43,00,000 ₹43,00,000 |
Tender Value
₹1.6 Cr
EMD Value
₹3.2 L
Closing Date
15 Apr 2026, 11:00 amClosed
PARIK GARG
Division - Sewerage
Supply, erection, testing and commissioning at 100MLD STP
2026_HRY_512953_1
202652496631 36DB 4032 B2F7 D4FE76594506717001
Open Tender
Civil Works
Works
270 days
Gurugram
2 documents required · 2 mandatory
₹1,180
₹3.2 L
Yes
Plot No. 3 Sector-44, Gurugram
26 May 2026
4 Apr 2026
16 Apr 2026
4 Apr 2026
15 Apr 2026
4 Apr 2026
4 Apr 2026 - 6 Apr 2026
13 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Designing, Supply and erection of DG set of capacity 1050 KVA with noise controlled devices acoustic of suitable rating, testing and commissioning of diesel generating set, radiator cooled, 3 phase, 4 wire, 50 cycles 415 plus (-)1% volts AC alternator coupled directly through a set of flexible coupling on a common MS fabricated base frame with diesel engine complete with suitable size incoming cable from generator to change over/AMF panel, making 2nd incoming cable connection from transformer, outgoing cable connection from changeover/ standard panel, making second incoming cable connection from transformer, outgoing cable connection from changeover / STD panel to incomer of motor starter panel, fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. The rating should be at 1500 RPM.
a) Diesel Engine, b) Alternator c) Battery 24 V. d) Base Plate. e) suitable sq.mm suitable core copper cable upto 40 meters. f) Tools, standard panel g) Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT`s) h) Metering set 60/5A/110V (Amp. Meter, Volt Meter) i) Overload protection for DC-1 No. j) Battery Charger 24V DC k)Copper bus bar of suitable size l) KWH meter 96 sqmm size m) Starting fuse button and key switch9on/off) n) Indicating lamps for low lubricated oil pressure, high coolant temperature, set running, load on, Dc control and other required accessories complete in all respects to the satisfaction of Engineer-in-charge` | - | Each | - | - |
| 2 | Designing, Supply and erection of DG set of capacity 750 KVA with noise controlled devices acoustic of suitable rating, testing and commissioning of diesel generating set, radiator cooled, 3 phase, 4 wire, 50 cycles 415 plus (-)1% volts AC alternator coupled directly through a set of flexible coupling on a common MS fabricated base frame with diesel engine complete with suitable size incoming cable from generator to change over/AMF panel, making 2nd incoming cable connection from transformer, outgoing cable connection from changeover/ standard panel, making second incoming cable connection from transformer, outgoing cable connection from changeover / STD panel to incomer of motor starter panel, fenced enclosure with platform for DG sets complete as per following detailed scope and specifications and directions of Engineer-in-charge. The rating should be at 1500 RPM.
a) Diesel Engine, b) Alternator c) Battery 24 V. d) Base Plate. e) suitable sqmm suitable core copper cable upto 40 meters. f) Tools, standard panel g) Metering set 415 VAC-1 set (Amp. meter, Volt Meter, ASS, VSS, Phase Indicator, control fuse, frequency meter, CT`s) h) Metering set 60/5A/110V (Amp. Meter, Volt Meter) i) Overload protection for DC-1 No. j) Battery Charger 24V DC k)Copper bus bar of suitable size l) KWH meter 96 sqmm size m) Starting fuse button and key switch9on/off) n) Indicating lamps for low lubricated oil pressure, high coolant temperature, set running, load on, Dc control and other required accessories complete in all respects to the satisfaction of Engineer-in-charge` | - | Each | - | - |
| 3 | Supply, erection, testing and commissioning of 2000 KVA 11 KV / 0.433 KV, 3 Phase, 50 Hz, Copper wound, off-load tap charging links on HV side including first filling of filtered Dehydrated oil including entire cable network from G.O. switch to H.T metering equipment and from H.T metering to Transformer from transformer to main to L.T panel, earthing, safety equipment, fenced enclosure for transformer, including incoming and outgoing VCB, required H.T./L.T. Cables, ACB 3200 Incomer, Bus Coupler and any other required equipment/work as per site condition complete in all respect as per approved make and directions of Engineer-in-charge complete to the entire satisfaction.
Make - Kirloskar / Crompton / Voltamp / Schneider | - | Each | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.80 MB
BOQ_591771.xls
BOQ • 0.31 MB
777821Z156138.pdf
Additional Documents • 9.87 MB
OT0156138.pdf
Other Document • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .