Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.7 LAccepted-AOC | L1 | Accepted-AOC Being 1st Lowest | |
| 2 | L2₹46.3 L+₹2.3 L (5.22%)Rejected-Finance | L2 | Rejected-Finance Being 2nd Lowest | |
| 3 | L3₹47.5 L+₹3.5 L (7.99%)Rejected-Finance SHOP NO 12 KHOPKAR APARTMENT KUMBHARAWADA URAN DISTT RAIGAD 400 702 | URAN | RAIGAD | MAHARASHTRA | 400702 | L3 | Rejected-Finance Being 3rd Lowest | |
| 4 | L4₹47.7 L+₹3.7 L (8.45%)Rejected-Finance FLAT NO 201 GREEN VALLEY CHS PLOT NO 26 SECTOR 19 NERUL EAST NAVI MUMBAI 400 706 | THANE | MAHARASHTRA | 400706 | L4 | Rejected-Finance Being 4th Lowest | |
| 5 | L5₹48.1 L+₹4.0 L (9.14%)Rejected-Finance 203 NIVAAN LAXMI SOCIETY PLOT NO 169 SECTOR 19 KHARGAHAR NAVI MUMBAI 410210 | RAIGAD | MAHARASHTRA | 410210 | L5 | Rejected-Finance Being 5th Lowest |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
26 Sept 2023, 6:00 pmClosed
CWE KARANJA
CWE KARANJA NAVAL STATION KARANJA URAN RAIGAD - 400704
PERIODICAL AND COMPREHENSIVE MAINTENANCE TO CENTRAL AC PLANTS COMPRISING THE VARIOUS EQUIPMENTS INCLUDING QUARTERLY INSPECTION AND SERVICING AND OVERHAULING OF CHILLER UNIT AT NAD AREA AT NAVAL STATION KARANJA
2023_MES_617692_1
84244-K/E8
Open Tender
Miscellaneous Works
Item Rate
240 days
NAVAL STATION KARANJA
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (NW) KARANJA
₹1 L
17 Nov 2023
7 Sept 2023
28 Sept 2023
7 Sept 2023
26 Sept 2023
21 Sept 2023
Amount
Quaterly inspection and servicing of the complete central AC plant of capacity 2 x 37 TR, model No WCDS037DP MN3x1 - 2 Nos, alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at DBM 15 of Make: Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 2 x 10 TR, model No ACWCDS 011DP MN 2x1 - 2 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at SBM (old) of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 52 TR, Model No XWC54052 AR2 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at TAL of Make : Blue star complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 81 TR, Model No WCDSO81 DPMN 3x2 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at PCB Workshop of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 4 x 13 TR, Model NoWCDSO12DP MN 1 x 1- 4 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at LWT Store of Make : Blue star complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 81 TR, WCDSO81 DP MN 3 x 2 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at Kasthan workshop of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 26 TR, Model No WCUSO 28 DMN - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at Barrack workshop of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 26 TR, Model No WCDSO 25 DPMN 2x1 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM(Original Equipement Manufacturer) and carring out preventive maintenance as per standard practice to maintain & keep the central AC plant functional regularly complete, Replacement of defective component/ Equipemement under the respective item of schedule of at SM 39 of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 40 TR, Model No AWC-45 052 AR2 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at Tech store of Make : Blue Star complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 37 TR, Model No WC DSO 40 DPMN 3 x 1 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at EMR Workshop of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 37 TR, Model No WC DSO 40DP MN 3x1 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at RT Workshop of Make : Voltas complete all as specified and directed by Engr-in-charge.
Quaterly inspection and servicing of the complete central AC plant of capacity 3 x 120 TR, Model No AGEGWFXR1201MLB2 - 3 Nos alongwith all equipement, electrical connections to inspect the operation of plant by the representative of OEM (Original Equipement Manufacturer) and carring out preventive maintenance to maintain & keep the central AC plant functional at EKM Workshop of Make : Voltas complete all as specified and directed by Engr-in-charge.
SCOPE OF WORK FOR ITEM NO. 01 TO 12 : (i) Inspecting the plant/system and carry out preventive maintenance as per standard practice four times in a year or as required. (ii) Checking the refrigeration system, motor and starters and ensuring healthy condition of the plant . (iii) Checking the system for any for leakage and rectification of leakage by holding nitrogen gas for 24 hrs into the closed system complete. (iv) Checking the system Attending to any number of breakdown calls during normal working hours on working days (v) Quarterly inspection of belts adjusting the tension. (vi) Checking the microprocessor controler for its proper functioning with all sensors. (vii) Periodic report shall be submitted to department on each visit of the OEM at site. (vii) Checking the refrigerantion system,motors, starters and ensuring healthy condition of plant (ix) Checking the functioning of compressor and its accessories (x) Lubricating the bearings of motors,fans when found necessary.
Notes for item No. 1 to 12: (i) Service Maintenance of above make central chilled type AC plants installed at the given location to be carried out from authorised service engineer from OEM. On quatertly basis or whenever called by GE/Engineer-in-charge/JE E/M during break down. The contractor shall submit the license/agreement obtained form the service provider of OEM at the time. (ii) The inspection and servicing shall be carried out by OEM only. Contractor has to submit necessary AMC documents to Engineer-in-charge with in 15 days of accetance of tender. (iii) The rates quoted shall also include the attending of emergency breakdowns in AC plants. If such breakdowns are not attended in time. The following compensation shall be leived from the contractors dues:- (a) Attending breakdown with in 48 hours - Rs Nil. (b) Attending breakdown with in 3 to 7 days - Rs 5000.00 per breakdown (c) Attending breakdown after 7 days - Rs 10000.00 per breakdown (d) Spares parts required shall be measured and paid separately under relevent items based on their consumption on ground.
Material and labour for overhauling of compressors SMC 4-65 Make compressor complete all as per manufacturer's instruction by authorised dealers /workshop for improved performance and designed parameter including the following complete all as specified and directed by Engr-in-charge. (i) Replacement of crank shaft of suitable size including dismantling transporting to authorised approved work shop and back including refixing after repair and testing. (ii) Complete dismantling of each part of compressors cleaning each part of compressors carrying out preventive work like oiling, greasing, replacing defective parts reassembling compressors complete with vaccum test and pressure test at specified pressure to detect leak and again same tests after leak repair to ensure leakage in the complete system. Notes: (a) New spare parts of compressors as required shall be measured and paid seperately as supply only and cost of labour and T&P shall be deemed to include in the quoted rate of this item. (b) Unit rate quoted shall include for the necessary elelctrical check i.e checking of panel wiring to run the compressor smoothly. (c) Before opening of compressor the freon gas to be taken in empty cylinder by the help ice or as directed by Engr-in-charge. (d) Unit rate quoted shall also be included for testing the whole system for any leakage using nitrogen gas by vaccumising the system and filling the system with pressurise nitrogen to test the leakage including nitrogen gas as required and top up repaired compressor and whole system with refrigerant gas R-22 and compressor oil after confirmation of no leakage. (e) Unit rate quoted shall also be inclusive of charging of compressor oil and refrigerant of sufficient quantity or as directed by Engr-in-charge. (f) Minor items required for smooth functioning of compressor is included in the quoted rate of the item. Location: DBM 14
Supply only following parts of make SMC 4-65 model Accel compressor complete all as specified and directed by Engr-in-charge.
Bushing with collar
Half section of bearing
Rocker for unloading mechanism
Connecting rod assembly
Shaft seal assembly including 10 AG
Bushing for piston pin
Piston with pin and Rings
Cylinder liner with suction valve assembly
Oil pressure valve
Compressor safety valve
Suction valve ring plate
Suction valve retaining plate
Discharge valve ring
Discharge valve retaining plate
Suction strainer for SMC 4-65
Oil strainer and filter
Castle Nuts
Split pins
Scraper Ring
Seeger Ring
Cup washer
Crank shaft for SMC 4-65
Set of gasket for SMC 4-65
Set of neoprene 'O' ring SMC 4-65
Sealing ring set SMC 4-65
Dowty ring set SMC 4-65
Set of aluminium gasket SMC 4-65
Suction stop valve assembly
Discharge stop valve assembly
Material and labour for overhauling of receprocating compressors chiller unit Make Voltas Model No WCURO17MNT complete all as per manufacturer's instruction by authorised dealers /workshop for improved performance and designed parameter including the following complete all as specified and directed by Engr-in-charge. (i) Replacement of crank shaft of suitable size including dismantling transporting to authorised approved work shop and back including refixing after repair and testing. (ii) Complete dismantling of each part of compressors cleaning each part of compressors carrying out preventive work like oiling, greasing, replacing defective parts reassembling compressors complete with vaccum test and pressure test at specified pressure to detect leak and again same tests after leak repair to ensure leakage in the complete system. Notes: (a) New spare parts of compressors as required shall be measured and paid seperately as supply only and cost of labour and T&P shall be deemed to include in the quoted rate of this item. (b) Unit rate quoted shall include for the necessary elelctrical check i.e checking of panel wiring to run the compressor smoothly. (c) Before opening of compressor the freon gas to be taken in empty cylinder by the help ice or as directed by Engr-in-charge. (d) Unit rate quoted shall also be included for testing the whole system for any leakage using nitrogen gas by vaccumising the system and filling the system with pressurise nitrogen to test the leakage including nitrogen gas as required and top up repaired compressor and whole system with refrigerant gas R-22 and compressor oil after confirmation of no leakage. (e) Unit rate quoted shall also be inclusive of charging of compressor oil and refrigerant of sufficient quantity or as directed by Engr-in-charge. (f) Minor items required for smooth functioning of compressor is included in the quoted rate of the item. Location: DBM 16
Supply only following parts of receprocating compressor chiller unit Make Voltas Model No WCURO17MNT complete all as specified and as directed by Engr-in-charge.
Bushing with collar
Half section of bearing
Rocker for unloading mechanism
Connecting rod assembly
Shaft seal assembly including
Bushing for piston pin
Piston with pin and Rings
Cylinder liner with suction valve assembly
Oil pressure valve
Compressor safety valve
Suction valve ring plate
Suction valve retaining plate
Discharge valve ring
Discharge valve retaining plate
Suction strainer
Oil strainer and filter
Castle Nuts
Split pins
Scraper Ring
Seeger Ring
Cup washer
Crank shaft
Set of gasket
Set of neoprene 'O' ring
Sealing ring set
Dowty ring set
Set of aluminium gasket
Suction stop valve assembly
Discharge stop valve assembly
Supply and fix in repairs cooling tower fan assembly with low speed fan with noise level not exceeding 75 dBa made out of propeller type light weight solid/ hollow FRP rust resistant with statically and dynamically balanced blades suitable for 61 to 120 TR capacity AC plants complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs cooling tower fan assembly with low speed fan with noise level not exceeding 75 dBa made out of propeller type light weight solid/ hollow FRP rust resistant with statically and dynamically balanced blades suitable for upto 60 TR capacity AC plants complete all as specified and directed by Engr-in-charge. Notes for Item No. 17 to 18: (i) Fan speed shall not exceed 60 MPS. Outlet velocity of air shall not be less than 610 mtrs/ min. (ii) Fan shall be protected by a fan guard and bird screen of galvanised steel construction. (iii) G SS/ SS 304 fan guard shall be provided over the fan motor for protection against rain water.
Material and labour for taking out all old unserviceable PVC fills from cooling tower of capacity upto 100 TR and supply anf fix in replacement of eliminator of cooling tower uptp 100 TR complete all as specified and directed by Engr-in-charge.
Material and labour for taking out all old unserviceable PVC fills from cooling tower of capacity 100 TR to 200 TR and supply anf fix in replacement of eliminator of cooling tower101 TR to 200 TR complete all as specified and directed by Engr-in-charge.
Dismantling and removing old unserviceable compressor sealed unit of scroll type compressor carefully and supply, installation, testing new sealed compresor unit of capacity 12.5 TR Model No SZ185S4RC of Make Blue Star/ Danfoss or equivalent complete with all standard accessories as per existing model installed at AC plant complete all as specified and directed by Engr-in-charge. Notes:- (i) Sealed unit shall be purchased from authorised dealers/agents (ii) Cost of labour, fixing & T & P shall be deemed to include in the quoted rate of this item. (iii) Unit rate quoted shall include for the necessary elelctrical check i.e checking of panel wiring to run the compressor smoothly. (iv) Before opening/ dismantling the compressor the freon gas to be taken in empty cylinder by the help Ice or as directed by Engineer-in-Charge.
Supply and fix in replacement of wall mounting /hanging type LED digital type temperature /relative humidity indicator with 2" large size display and minimum size (445x130x115mm) with following specifications complete all as specified and directed by Engr-in-charge. Display : 2" Red LED x 2 Display Accuracy : + 0.5% Resolution : 0.1 deg C, 0.1 % RH Input : 4-20mA Enclousure : Powder coated metal case Operating Voltage : 230V AC
Material and labour for laying, jointing, connecting and testing in repairs sensor cable 3 core 2.5 sqmm PVC insulated and sheathed with bare annealed copper conductor as per IS 694:1990 for connecting RH+T sensor to RH+T indicators complete all as specified and directed by Engr-in-charge.
Material and labour for laying, jointing, connecting and testing in repairs indicator cable 2 core 1.5 sqmm PVC insulated and sheathed with bare annealed copper conductor complete all as specified and directed by Engr-in-charge.
Material and labour for rewinding of induction motor 2900 RPM, 3 phase, 50 Hz, 415 volt of compressor motor and AHU blower, chiller, condenser motor comprising of the following activities for induction motor of following capacities complete all as specified and as directed by Engr-in-charge. (i) Disconnecting and removing the electric motor from installed position and loading unloading, transporting to authorised/approved work shop. (ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, bearing cover slieving , necessary replacement of cooling fan, nut-bolt etc (iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric conection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-Charge all as specified and directed. (iv) Material and labour for replacement of 02 Nos of suitable size of ball bearing of existing size of the following type and capacity of induction motor.
Induction Motor of Capacity 15 HP
Induction Motor of Capacity 10 HP
Induction Motor of Capacity 7.5 HP
Induction Motor of Capacity 5 HP
Induction Motor of Capacity 3 HP
Induction Motor of Capacity 2 HP
Supply and fix in replacement power contactor 3 pole, type ML-1.5 with 2 NO + 2 NC aux contracts with standard coil voltage 415 volts, rating 25 Amp complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement power contactor 3 pole, type ML-2 with 2 NO + 2 NC aux contracts with standard coil voltage 415 volts, rating 32 Amp complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement power contactor 3 pole, type ML-3 with 2 NO + 2 NC aux contracts with standard coil voltage 415 volts, rating 40 Amp acomplete all as specified and directed by Engr-in-charge.
Supply and fix in replacement bimetal overload relay type MN-02 of relay range, 4.5 to 7.5 Amp with single phasing protection complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement bimetal overload relay type MN-02 of relay range, 9 to 15 Amp with single phasing protection complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement bimetal overload relay type MN-02 of relay range, 14 to 23 Amp with single phasing protection complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement electronic timer 800SQA Make M/s Selec/GIC/Siemens/ M/s Havells working voltage 240V 50 Hz complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement air break contactor Model No 3TS3500-0A with Auxiliary 3TX400--2A 1 NC 415 V, 50 Hz, AC complete all as specified and directed by Engr-in-charge.
Supply and fix for MCB SP 5 To 32 amp rating 240V, 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
Supply and fix for MCB SPN 32 AMP rating 240V, 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
Supply and fix for MCB SPN 40 to 63 AMP rating 240V, 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
Supply and fix for MCB TP 40 To 63 AMP 415V 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
Supply and fix for MCB TPN 16 to 32 AMP 415V 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
Supply and fix for MCB TPN 40 to 100 AMP 415V 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement MCCB 3 Pole, 415 V, fixed type, 25 to 400 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement MCCB 4 Pole, 415 V, adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement MCCB 4 Pole, 415 V, adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement power contactor 3 pole, type MNX 12, 1NO + 1 NC aux contracts with standard coil voltage 240 volts, rating 30 Amp complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement power contactor 3 pole, type MNX 18, 1NO + 1 NC aux contracts with standard coil voltage 240 volts, rating 30 Amp complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement power contactor 3 pole, type MNX 22, 1NO + 1 NC aux contracts with standard coil voltage 240 volts, rating 30 Amp complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement power contactor 3 pole, type MNX 32, 1NO + 1 NC aux contracts with standard coil voltage 240 volts, rating 30 Amp complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs sprinkler assembly complete with header nozzles made out of galvanised iron suitable to fix in cooling towers of 71 TR and above capacity AC plant complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs sprinkler assembly complete with header nozzles made out of galvanised iron suitable to fix in cooling towers of 61 to 70 TR capacity AC plants complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs sprinkler assembly complete with header nozzles made out of galvanised iron suitable to fix in cooling towers of 51 to 60 TR capacity AC plants complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs sprinkler assembly complete with header nozzles made out of galvanised iron suitable to fix in cooling towers of 31 to 50 TR capacity AC plants complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs sprinkler assembly complete with header nozzles made out of galvanised iron suitable to fix in cooling towers of below 30 TR capacity AC plants complete all as specified and directed by Engr-in-charge.
Supply, assembly and erection in repair of GI sheet with C & SS rectangular/square duct made out of L shapped hollow profile, duly factory boxed, incl all accessories such as corner, cleat, carraige bolt, gasket and appropriate sealant on longitudinal joint etc complete of size 24 gauge complete all as specified and as directed by Engr-in-charge.
Material and labour in repair for duct insulation with resin bonded fibre glass wool roll of density 24 Kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation 50mm including the following complete all as specified and as directed by Engr-in-charge. (a) Cleaning the duct surface (to be insulated) by scrapping carefully with wire brush etc. to make the surface completely free of milllscale, dirt, dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) Applying rubber based adhesive CPRX compound. (c) Sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50mm wide, to make the insulation leakproof. (d) Securing the insulation with and including mechanically fastened nylon/ steel straps of size 12mm/ 50mm at maximum intervals of 1.2m.
Material and labour in repair for duct insulation with resin bonded fibre glass wool roll of density 24 Kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation 40mm including the following complete all as specified and as directed by Engr-in-charge. (a) Cleaning the duct surface (to be insulated) by scrapping carefully with wire brush etc. to make the surface completely free of milllscale, dirt, dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) Applying rubber based adhesive CPRX compound. (c) Sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50mm wide, to make the insulation leakproof. (d) Securing the insulation with and including mechanically fastened nylon/ steel straps of size 12mm/ 50mm at maximum intervals of 1.2m.
Material and labour in replacement for aluminium cladding of insulated duct using 0.5 mm thick aluminium sheet and make good to the existing insulation complete all as specified and as directed by Engr-in-charge.
Charging only of refrigerant gas R- 407c/ R134/R22 in sealed cylinder after making system leak proof and complete vaccume complete all as specified and as directed by Engr-in-charge.
Supply and fix for filter drier for chiller as per existing make and model complete all as specified and as directed by Engr-in-charge.
Supply and fix for air terminals of supply / return / exhaust air grilles /of powder coated aluminium with aluminium volume control dampers with anti smudge ring and removable core complete all as specified and as directed by Engr-in-charge.
Servicing of cooling coils and air filters of AHUs intalled at air conditioning plant by removing air filters and fixing ack after cleaning with air blower and water and cleaning agent, cleaning of cooling coil with wire brush and air blower and water spray pump after spraying scale gun or equivalant chemical suitable for aluminium fins and straighting the fins of cooling coil by using suitable brush for capacity upto 10000 CFM complete all as specified and as directed by Engr-in-charge.
Servicing of cooling coils and air filters of AHUs intalled at air conditioning plant by removing air filters and fixing ack after cleaning with air blower and water and cleaning agent, cleaning of cooling coil with wire brush and air blower and water spray pump after spraying scale gun or equivalant chemical suitable for aluminium fins and straighting the fins of cooling coil by using suitable brush for capacity 10000 CFM to 20000 CFM complete all as specified and as directed by Engr-in-charge.
Material and labour for repairs to condenser of AC plant by blocking the damaged/ corroded tubes involving following activities:- (i) Disconnecting the side covers of the condenser from their existing positions. (ii) Leakage testing of the condenser using pressurised nitrogen gas and finding the leaked tubes. (iii) Blocking the damaged /leaked tubes by brass plugs. (iv) Re-fixing the side covers of the condenser and the condenser valves from their existing positions with new nuts, bolts, rubber gasket and washers etc., and painting the surface with approved shade of synthetic enamel paints for following capacities of condenser complete all as specified and as directed by Engr-in-charge.
Upto 25 TR Capacity
26 to 50 TR capacity
51 to 130TR capacity
Supply and fix for regenerable coarse type AHU filter of size 60cm x 60 cm x5 cm complete all as specified and as directed by Engr-in-charge.
Supply and fix for regenerable coarse type AHU filter of size 60cm x 50 cm x 5 cm complete all as specified and as directed by Engr-in-charge.
Supply and fix for regenerable coarse type AHU filter of size 60cm x 40 cm x 5 cm complete all as specified and as directed by Engr-in-charge.
Supply and fix for regenerable coarse type AHU filter of size 60cm x 30 cm x 5 cm complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs auto capacity regulator solenoid valve including connecting of interlock wiring, nuts, bolts, wahsers etc., complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs coil for solenoid vlave connecting into liquid line including interlock wiring, nuts, bolts, washers etc., complete all as specified and as directed by Engr-in-charge.
Material and labour for descaling of complete condenser units for central/ package type AC plants of following capacities by means of adding descaling chemical solution (HCL) or equivalent into the cooling tower sump as per requirements, and running the plant pump continuously till all the scale of pipes/shell are removed including removing side covers of condenser and cleaning the water tubes by means of nylon brushes till the scaling is removed and re fixing of covers including replacement of neoprene rubber gasket and refixing pipe connection etc., complete all as specified and as directed by Engr-in-charge.
Condenser unit of AC plant up to 60 TR
Condenser unit of AC plant 60 TR to 120 TR
Supply and fix in repairs of Motor and Voltage protective device as per existing make and type complete all as specified and as directed by Engr-in-charge.
MVPD EC 5-30 A
MVPD EC 30-220A
Micro VPD (Split) 360-500V AC
Supply and fix microprocessor scroll controller for compressor of 11-20 TR capacity including removing unserviceable of microprocessor complete all as specified and as directed by Engr-in-charge.
Supply and fix microprocessor scroll controller for compressor of 21-30 TR capacity including removing unserviceable of microprocessor complete all as specified and as directed by Engr-in-charge.
Supply and fix microprocessor scroll controller for compressor of 31-40 TR capacity including removing unserviceable of microprocessor complete all as specified and as directed by Engr-in-charge.
Supply and fix microprocessor scroll controller for compressor of 41-78 TR capacity including removing unserviceable of microprocessor complete all as specified and as directed by Engr-in-charge.
Supply and fix microprocessor scroll controller for compressor of 79-100 TR capacity including removing unserviceable of microprocessor complete all as specified and as directed by Engr-in-charge.
Supply and fix microprocessor scroll controller for compressor of 100-120 TR capacity including removing unserviceable of microprocessor complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of single phase preventor type SPP VSP3 3 phase, 415 Volts, 50 Hz AC complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of CVT for chiller controller power supply 3 phase, 415 Volts, 50 Hz AC complete all as specified and as directed by Engr-in-charge.
Supply and fix for connector in HVAC panel 6 Amp to 35 Amps complete all as specified and as directed by Engr-in-charge.
Material and labour for repair of condenser pump/ chiller pump any type including replacement of impeler and bearings both side, replacement of main saft, outer body of the pump of following capacities complete all as specified and as directed by Engr-in-charge.
Chiller/condenser pump of Capacity 10 HP
Chiller/condenser pump of Capacity 7.5 HP
Chiller/condenser pump of Capacity 5 HP
Supply and fix in replacement MS ERW tubing medium grade 80mm dia for condenser water circulation pipes complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement MS ERW tubing medium grade 100mm dia for condenser water circulation pipes complete all as specified and as directed by Engr-in-charge.
Material and labour for nitrogen leak test entire system of the AC plant of Capacity upto 150 TR with Nitrogen gas. If found any leakage or reduction in the scale of pressure shall located and arrest the leakage immediately by soldering or an appropriate measure are to be taken to top the leakage permanently complete all as specified and as directed by Engr-in-charge.
Cleaning the cooling tower by applying wire brush, washing powder and other solvent by removing the deposited impurities sush as silt, dust particles mud/ sand inside the dume and around the fins,cleaning of base tray and grills, pot stainer, main shaft etc., and other connected items, servicing of fan motor including changing of bearings and greasing refixing the fan, frill and top cover including testing commissioning after reassembling complete including painting complete all as specified and as directed by Engr-in-charge.
Cooling tower of capacity up to 35 TR
Cooling tower of capacity 35 TR to 65 TR
Cooling tower of capacity 66 TR to 250 TR
Supply and fix in replacement of butter fly valve of 65 mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of butter fly valve of 80mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of butter fly valve of 100 mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of gun metal gate or globe valve of 15mm dia with iron wheel head screwed both ends for iron pipes complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of gun metal gate or globe valve of 20mm dia with iron wheel head screwed both ends for iron pipes complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of 15mm dia ball brass valve, high pressure, with polythene float and fly nuts complete, screw for iron pipe or brass ferrule and mixed complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of 20mm dia ball brass valve, high pressure, with polythene float and fly nuts complete, screw for iron pipe or brass ferrule and mixed complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs of chilled water sensor as per existing make and type complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement of flow switch as per existing make and model complete all as specified and as directed by Engr-in-charge.
Material and labour in repairs strip heater finned 2 inch wide alluminised steel fins of 415 volt 1.5 to 3 KW capacity to match with the existing complete all as specified and as directed by Engr-in-charge.
Material and labour for thermal insulation to chilled water line, ducts, chillers, suction pipe with one coat of bituminous paint, polythelyne sheet, fiber glass wool insulation upto 50mm thick, wiremesh and cover with 24 SWG aluminium clading complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs pressure gauge of range -30-150 complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs pressure gauge of range 0-200 complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs pressure gauge of range 0-300 complete all as specified and as directed by Engr-in-charge.
Supply and fix in repairs on-off push button pendants with elements red/green/orange complete all as specified and as directed by Engr-in-charge.
Supply and fix in replacement V Belt complete all as specified and as directed by Engr-in-charge.
V Belt A-58
V Belt A-28
V Belt A-48
V Belt A-79
V Belt A-62
V Belt A-56
V Belt B-58
V Belt B-73
V Belt B-68
V Belt B-61
somnath engineering corporation
ENJOY
M.K Enterprises
BALAJI TRADERS
AIRDOT ENGINEERING
cooltech engineering services
ECOBUILD
Sagar Electricals
Shree Ayyappa Engineering
M/S SOMANATH ENTERPRISES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .