CWE KIRKEE
Headquarters CWE Kirkee, Military Engineer Services, Range Hills Road, Kirkee, Pune-411003
REPAIR AND MAINTENANCE OF APFC PANEL HT EXTERNAL ELECTRIC SUPPLY DISTRIBUTION SYSTEM INCLUDING FILTRATION REPAIRS OF TRANSFORMER VCB RMU AND CONNECTED WORKS AT MILITARY HOSPITAL KIRKEE AND RANGE HILLS AREA UNDER GE (MH AND RH) KIRKEE
2021_MES_428535_2
CWE/KKE/TOKEN-70 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KIRKEE
As per tender documents
5 documents required · 5 mandatory
₹500
Yes
GE MH AND RH KIRKEE
₹82,000
Yes
Headquarters CWE Kirkee, Military Engineer Service
7 Jul 2021
16 Apr 2021
30 Apr 2021
16 Apr 2021
28 Apr 2021
16 Apr 2021
16 Apr 2021 - 19 Apr 2021
19 Apr 2021
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying UG cable not exceeding 1.5m in depth and getting out in hard/dense soil.
All as per item no. 1 above but for soft / loose soil
All as per item no. 1 above but for soft / disintegrated rock.
Returning, filling, including spreading leveling, watering and well ramming in layers not exceeding 25cm all as directed
Removing excavated material not exceeding 50m and depositing where as directed at a level not exceeding 1.5m above the starting point.
Supply and spread riddled earth as per IS for cable cushioning all as directed. Note:-Thickness of sand cushioning shall be measured after punning.
Supply and laying reinforced precast concrete cable cover class HV, type 1, flat size 300 mm x 180 mm x 40 mm size for cable protection all as specified and as directed.
Taking down unserviceable cable of any size and description all as directed and specified.
Supply, lay & testing XLPE insulated, PVC sheathed, bedded, galvanized steel strip or wire armoured electric aluminium conductor cable 11000 volts (earthed) grade of cross sectional area 95 Sqmm 3 core with DWC pipe of suitable dia for protection and including disconnecting and removing old unserviceable cable and bricks complete all as directed.
Disconnecting the faulty cable ends, removing the faulty cable joint and M & L for heat shrinkable HT 11 KV (earthed) indoor type joint suitable for aluminium conductor cable of size 3 core 95 Sqmm , jointing and testing, reconnecting the cable ends complete all as directed
All as per item No 10 above but for HT 11 KV (earthed) outdoor type cable joint of size 3 core 95 Sqmm complete all as directed
Disconnecting the faulty cable ends, removing the faulty cable joint and M & L for jointing with 11 KV (Earthed) straight through heat shrinkable type cable joint kit, testing and reconnecting the cable ends complete suitable for 3 core 95 Sqmm aluminum conductor all as specified and as directed.
Dismantling the broken / worn out cable route indicator S & F cable route indicator made out of PCC 1:3:6 of size 300x100mm, 450mm above ground level finished even and fair with 10mm thick plaster 1.6 embedded upto 600mm below ground level of size 300x300mm and marked/ written for HT 11KV including indicating direction with and including painting with two coats of synthetic enamel paint over a coat of primer to exposed surfaces complete all as specified and directed by the Engineer-in-charge.
Material and Labour for shifting of transformer of any capacity from one area to another area and placing in position and making all connections including removing and depositing the old transformer to store yard carefully and properly testing and commissioning transformer all as directed .
Disconnecting the transformer indoor/ out door from HT (11 KV) / LT(440 volt) side at site dismantling carefully and removing primary and secondary terminals, top cover with conservator tank, neutral earth strip and draining out transformer oil to the required level and storing carefully in cleaned containers, cleaning of terminals, inspection of core, supply and replacing 5 mm thick rubberised cork sheet gasket for tank top cover and reassembling the complete dismantled items, reconnecting the HT/ LT supply cable ends at the site for the following transformers complete all as directed by engineer in charge.
a) Transformer capacity 100KVA to 250 KVA
b) Transformer capacity 300KVA to 500 KVA
Filteration of transformer oil of transformer installed at various locations out door/in door transformer to achieve electric strength of 40 KV for 1 minute at 4mm gap as per relevant IS with portable filteration plant, testing of oil for di electric strength before and after filteration shall be conducted all as directed by the Engineer in Charge. Note : Test results after filteration shall be produced on completion.
Supply and topping up new transformer oil into the conservator tank/body tank of the transformer at various location complete all as directed by the Engineer-in-charge. (Make : Power Oil or its equivalent) Note : The transformer oil for topping up shall be with di-electric strength of 40KV
Material and Labour for insulating the defective coils of the transformer winding the with new insulation materials, bracings the terminals before placing into the transformer and assembling the HT / LT coil with new insulation between core and LT coil all as required and fitting the coils in the chamber, testing and commissioning the transformer after providing necessary connections complete including transportation to workshop all as directed.
a) Transformer capacity 100KVA to 250 KVA
b) Transformer capacity 300KVA to 500 KVA
Material and Labour for rewinding of HT /LT windings of transformer of capacity 200 KVA, winding the defective coils with approved quality copper wire as per IS of same gauge and existing size together with new insulation materials, bracings the terminals before placing into the transformer and assembling the HT / LT coil with new insulation between core and LT coil all as required and fitting the coils in the chamber, testing and commissioning the transformer after providing necessary connections complete including transportation to workshop all as directed.
a) Transformer capacity 100 KVA
b) Transformer capacity 200 KVA
M & L for Spray Painting of transformer of capacity up to 200 KVA with two coats of synthetic enamel paint and writing the MES / SM No in white color on black back ground all as specified and as directed.
All as per item No 20 above but for capacity up to 250 KVA to 1000 KVA all as specified and as directed.
Material & Labour for replacing silica gel breather for the following sizes of transformers:-
(a) 100 to 250 KVA
(b) 300 to 500 KVA
Taking out old unserviceable defective HT bushings from transformers and material and labour for new porcelain bushing with brass stud, nuts and washers, connecting to the winding testing and commissioning the transformer of capacity 100 to 250KVA complete all as directed
All as per item No 23 above but HT bush for 300 to 500 KVA
All as per item No 23 above but HT bush for capacity above 500 KVA upto 1000 KVA
All as per item No 23 above but LT bush for 100 to 250 KVA
All as per item No 23 above but LT bush for 300 to 500 KVA
All as per item No 23 above but LT bush for capacity above 500 KVA upto 1000 KVA
M&L for switch air-break gang operated horizontal/vertical type single break, 11000 volts grade, triple pole, mechanically operated mounted on 9 insulator and steel frame, with operating mechanism worked from ground level, for current rating 200 amps capacity including taking down old AB switch all as directed. ( Make: Pactil /Jaipuria Brothers / MEC Trivandrum)
M&L for Drop out fuse suitable for 11 KV current rating 25 to 50 Amps including taking down old HT Drop out fuse units complete all as directed ( Make: WSI / Jayshree / Mysore)
M&L for lightning arrester high tension expulsion type complete with all fittings transmission class, discharge capacity 30 Kilo amps suitable for 11000 Volts supply including taking down old lightning arresters complete all as directed ( Make: WSI / Jayshree / Mysore/Areva)
Supply and replacement of pin type porcelain vitreous white/ brown insulator of size 150 mm height, 150 mm dia 11000 volts grade incl one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut all as directed. (Make: Jayshree / Mysore porcelain / Jaipuria / BHEL / Southern insulator / WS insulators)
Supply and replacement of disc type porcelain vitreous 145 mm height and 255 mm dia ball and socket type white, brown or green for working pressure 11000 volts including mild steel straps of size 38 x 5 with 20mm dia bolts all as directed (Make: Jayshree /Mysore porcelain / Jaipuria / BHEL / Southern insulators / WS insulator)
M & L for earthing complete with GI earth plate electrode of size 600mm x600mmx 3.15 mm thick buried directly under ground vertically to a depth not less than 2.25meter below ground level with top edge of the plate at a depth not less than 1.5 m below ground level connected to and including GI strip 32 x 6 mm, by means of bolts, nuts, check nuts and washers made out of GI including protection pipe GI light grade 40 mm size and watering pipe 20 mm dia GI medium grade all as shown on plate No 3 of SSR Part-I, connecting to earthing test point, including necessary exacution and earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1 (using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work complete including necessary test on completion all as specified and as directed.
M & L for locating the HT 11 KV cable fault with cable fault locating kit, excavating the of soil and taking out the faulty cable, refilling the soil after jointing and testing of HT cable all as specified and directed by Engr-in-Charge. (Note: (i) Cable joint required size measured and paid separately (ii) The cost of hiring/transporting the cable fault locator to site is deemed to be included in the quoted rate.)
M&L for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small inequalities (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exceeding 50 meters away complete for the various sub station all as specified and as directed.
Supply and laying GI tubing light grade 80mm bore, including necessary fittings ISI marked, for cable protection.
M&L for road cutting and making good with PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) of 150mm X 100mm in respect of width and thickness complete all as directed by Engr -in- charge.
S & F in repair 08 windows announciator 24 V DC operated and with Buchholz trip, winding temperature high trip, oil temperature high trip, Buchhloz alarm, winding temperature high alarm, oil temperature high alarm, spare complete all as specified and directed.
S & F Push buttons ON/OFF suitable for 11 KV panel existing size and including removing old unserviceable (colour-Red/Green/Black) complete all as specified and directed.
Supply and fixing in repairs Hooter for announciator panel complete all as specified and directed.
Servicing/calibration to 11 KV HT VCB (SF-6 type) complete including the following:- a) Taking out 11 KV HT VCB/(SF 6 type) of 400 /800 Amps rating trolley from HT panel after switching off electric supply checking of mechanical system for proper functioning of upward/downward movement of HT VCB/SF 6 type trolley including opening the VCB/SF-6 type & checking the mechanical system. Cleaning & servicing the fixed/moving contact & blowing out dust and applying the proper lubrication/greasing and reassembling the VCB/SF-6 type including connection to HT panel (b) Taking out relay set ( 2 Nos over current & 01 No earth fault relay) of any make from HT 11 KV VCB / SF-6 type panel and cleaning the contact (NO+NC) by CTC solution and adjust the contact and calibrate the relay by relay testing kit & proper plug setting as per reqd load & time delay and fixing the relay set in HT panels complete all as specified and directed. Note for (a) & (b):- (i) Testing of above job to be carried out by engineers of authorised dealer/service centre of concerned OBC. (ii) Replacing new items shall be measured and paid separately as supply only. (iii) Contractor shall submit the connected document/graph for relay calibration duly authenticated by authorised dealer/service center.
Supply & Fixing shunt trip coil assembly suitable for HT, (SF -6 type)/VCB, operating on 30/110 volt system and testing complete all as specified and directed.
Supply & Fixing closing/tripping coil operated on 110 /30 volt system suitable for working of relay of HT (SF-6 type)/VCB complete all as specified and directed.
Supply and fixing in replacement of faulty oil temperature indicator with trip and alarm contacts complete all as specified and directed.
S & F of demand controller of model PN8740 of elmeasure and connecting to existing tripping system all as specified and as directed.
Supply and fix in repairs Auxiliary Relay type with Buchhloz alarm, winding temp alarm, oil alarm etc complete all as specified and directed.
Supply and fix in repairs Auxiliary Relay type with Buchhloz alarm, winding temp alarm, oil alarm etc complete all as specified and directed
S & F Ammeter digital type -/5A CTR of 95 x 95 mm including taking out of old unserviceable ammeter complete all as specified and directed.
S& F Voltmeter digital type 15 KV of 110 V PTR, size 95 x 95mm including taking out old unserviceable voltmeter complete all as specified and directed.
S& F Voltmeter digital type 25 KV of 110 V PTR, size 95 x 95mm including taking out old unserviceable voltmeter complete all as specified and directed.
S & F power factor meter digital type of 95 x 95 mm including taking out of old unserviceable PF meter complete all as specified and directed.
S & F indicator light (LED type) suitable to operate on 30 Volts DC / 110 V AC having two covers red/green/blue for HT VCB panel including taking down old complete all as specified and directed.
Supply, fixing and testing in repairs power pack units with maintenance free solid batteries in sheet metal enclosure with arrangements for mounting on the existing 11 KV VCBs panels with nuts and bolts and capable of providing 30 V DC current to the VCBs during power failure for a continuous period of not less than 12 hours, for functioning of relays, charging motor and other parameters complete all as specified and directed.
Opening the top cover of VCBs 11 KV and servicing of fixed and moving contacts, replacement of defective components of panel board like lamp indicators, calibration of digital meters, over load protection relay, time delay relay/ earth fault relay, charging spring etc. Cleaning the fixed and moving contact inside the VCBs properly, servicing and greasing all movable mechanism, replacement of defective fuses, wiring and reassembling and testing complete all as specified and directed
Note : The rates quoted by the contactor shall include cost of any other spare parts/relay not mentioned herein but essentially required for functioning of the system.
S & F the following spares for 11KV VCB of capacity 630/800 Amps all as specified and as directed.
Spring charging motor as per sample
Fixed contacts as per sample
Moving contacts as per sample
Epoxy coated brass spout
Vacuum interrupter bottle
Charging bottles suitable for 11 KV VCB trolley
Lever type tripping /closing switch suitable for 11 KV VCB
S & F in repair PVC insulated twin core copper conductor cable of size 2.5 Sqmm complete all as specified and directed.
S & F in repair PVC insulated twin core copper conductor cable of size 4.0 Sqmm complete all as specified and directed.
Supply and fixing Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M. S. clamps, bolts and nuts of approved size for 11/22kv High tension 20 x 25 cm complete all as specified and directed.
M&L for preparation of old painted surfaces above ground level of PCC pole 9 M long with two coats of cement based paint cleaning by scraping and applying two coats of aluminium paint over one coat of red oxide primer on cross arms, brackets, clamps etc and writing pole number in black paint (Size shall be 40 mm) complete all as directed by Engineer - In - Charge (Note: The quoted rate inclusive of two coats of cement based paint on exposed coping surface and painting Blue and White strips in alternate layers with synthetic enamel paint up to1Mtr height above coping of pole as directed).
M&L for preparation of old painted surfaces for steel tubular poles above ground level of PCC base of pole 9 M long pole with two coats of cement based paint on concrete base and coping, cleaning by scraping and applying and two coats of aluminium paint over one coat of red oxide primer on 9 M steel poles cross arms, brackets, clamps etc and writing pole number in black paint (Size shall be 40 mm) complete all as directed by Engineer - In - Charge (Note: The quoted rate inclusive of two coats of cement based paint on exposed coping surface and painting Blue and White strips in alternate layers with synthetic enamel paint up to1Mtr height above coping of pole as directed).
M&L for preparation of old painted surfaces for steel tubular poles above ground level of PCC base of pole 11 M long pole with two coats of cement based paint on concrete base and coping, cleaning by scraping and applying and two coats of aluminium paint over one coat of red oxide primer on 11 M steel poles cross arms, brackets, clamps etc and writing pole number in black paint (Size shall be 40 mm) complete all as directed by Engineer - In - Charge (Note: The quoted rate inclusive of two coats of cement based paint on exposed coping surface and painting Blue and White strips in alternate layers with synthetic enamel paint up to1Mtr height above coping of pole as directed).
M & L for preparation of old painted surface complete of 11 Mtr long 2 pole structure cleaning by scraping and applyingand two coats of aluminium paint over one coat of red oxide primer on cross arms, brackets, clamps etc and writing pole No in Black & white paint (Number size shall be 50 mm ) as specificed and as directed by Engineer in charge. (Note: The quoted rate inclusive of two coats of white wash on exposed coping surface and painting Blue and White strips in alternate layers with synthetic enamel paint up to1Mtr height above coping of pole as directed).
All as per item No 62 above but for 4 pole structure all as specified and as directed.
M & L for 32x6mm galvanised iron strip all as specified and as directed.
M & L for preparation of old painted surface complete for 11KV HT Panel by cleaning, scraping and applying and two coats of synthetic enamel paint over one coat of red oxide primer and writing the MES NO / SM No in white colour on black background all as specified and as directed.
Excavation in trenches exceeding 1.5 m wide and not exceeding 3.0 m in depth for foundation of poles and getting out in hard/dense soil all as specified and directed.
Taking down burnt bricks / PCC covers of any size and relaying the same after laying of cable all as directed and specified.
M/L for PCC 1:4:8 Type D2 with 40 mm graded aggregate for foundation of pole complete including necessary foam work all as directed.
M/L for PCC 1:3:6 Type C1 with 20 mm graded aggregate for coping of pole complete including necessary foam work all as directed.
Relaying the serviceable cable of any size obtained from item No 08 above all as specified and as directed.
M & L for GI pipe 100 mm dia light grade laid in trenches at road crossings / foot paths icluding taking out old unserviceable pipe complete all as directed
Supply, lay & testing XLPE insulated, PVC sheathed, bedded, galvanized steel strip or wire amoured electric aluminium conductor cable 22000 volts (earthed) grade of cross sectional area 95 Sqmm 3 core with DWC HDPE pipe of suitable dia for protection and including disconnecting and removing old unserviceable cable and bricks complete all as directed.
Disconnecting the faulty cable ends, removing the faulty cable joint and M & L for heat shrinkable HT 22 KV (earthed) indoor type joint suitable for aluminium conductor cable of size 3 core 95-150 Sqmm , jointing and testing,reconnecting the cable ends complete all as directed
All as per item No 74 above but for HT 22 KV (earthed) outdoor type cable joint of size 3 core 95 -150 Sqmm complete all as directed
Disconnecting the faulty cable ends, removing the faulty cable joint and M & L for jointing with 22 KV (Earthed) straight through heat shrinkable type cable joint kit, testing and reconnecting the cable ends complete suitable for 3 core 95-150 Sqmm aluminum conductor all as specified and as directed.
M&L for switch air-break gang operated horizontal/vertical type single break, 22000 volts grade, triple pole, mechanically operated mounted on 9 insulator and steel frame, with operating mechanism worked from ground level, for current rating 200 amps capacity including taking down old AB switch all as directed. ( Make: Pactil /Jaipuria Brothers / MEC Trivandrum)
M&L for Drop out fuse suitable for 22 KV , horn gap fuse type , current rating 25 to 50 Amps including taking down old HT Drop out fuse units complete all as directed ( Make: WSI / Jayshree / Mysore)
M&L for lightning arrester high tension expulsion type complete with all fittings transmission class, discharge capacity 30 Kilo amps suitable for 22kv /33kv supply including taking down old lightning arresters complete all as directed ( Make: WSI / Jayshree / Mysore/Areva)
Supply and replacement of pin type porcelain vitreous white/ brown insulator of size 150 mm height, 150 mm dia 22000 volts grade including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut all as directed. (Make: Jayshree / Mysore porceleain / Jaipuria / BHEL / Southern insulator / WS insulators)
Supply and replacement of disc type porcelain vitreous 145 mm height and 255 mm dia ball and socket type white, brown or green for working pressure 22000 volts including mild steel straps of size 38 x 5 with 20mm dia bolts all as directed (Make: Jayshree /Mysore porcelain / Jaipuria / BHEL / Southern insulators / WS insulator)
Dismantling U/S HT steel tubular / PCC poles and Supply and erect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 11.0 mtrs long all as specified and directed by Engr-in-Charge. Note: Excavation , PCC will be measured and paid separately
Removing existing u/s danger boards HT and S&F danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT 20 x 20 CM size.
Dismantling the unserviceable cross arms and M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint all as directed.
Taking down carefully and refixing the existing alluminium strip of size 25 x 3.15mm as roof conductors and down conductor fixed on bldgs above ground level all as specified and as directed by Engineer-in-Charge.( Note : Porcelain conductors required will be measured and paid separately)
S&F porcelain insulators with screws, bolt and nut for fixing the aluminium strip along with necessary fixing accessories as required all as specified and directed.
M & L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including, 3 Nos, 8mm dia 25mm long hex, head screw all as specified and directed.
Restringing only ACSR conductor of any type/ size on existing HT poles etc incl binding on insulator pin, shackle with aluminium binding wire all as directed. (Note : Single line conductor shall be measured as one unit)
Cutting and brooming and clearing tree branches/ plants/ bushes obstructing the LT/HT OH lines up to 3.0 mtrs on both sides including disposal of materials to a distance of 50 meters complete all as directed by Engineer - in - Charge
Disconnecting ACSR conductor any type and supply and fixing ACSR conductor of any size/ type for OH line on poles insulator for jumpering connection incl binding insulators with aluminium wire all as specified and directed
M & L for Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 4 mm dia
Serviceing/calibration to 22 KV HT POVCB complete including the following:- (a) Checking the 22 KV HT POVCB/(SF 6 type) of 1600 Amps rating HT panel after switching off electric supply checking of mechanical system for proper functioning of upward/downward movement of HT POVCB including servicing the CR Panel & checking the mechanical system. Cleaning & servicing the fixed/moving contact & blowing out dust and applying the proper lubrication/greasing the including replacing the control cables as required for connection to CR panel (b) Taking out relay set ( 2 Nos over current & 01 No earth fault relay) of any make from HT 22 KV CR panel and cleaning the contact (NO+NC) by CTC solution and adjust the contact and calibrate the relay by relay testing kit & proper plug setting as per reqd load & time delay and fixing the relay set in HT panels complete all as specified and directed. Note for (a) & (b):- (i) Testing of above job to be carried out by engineers of authorised dealer/service centre of concerned OBC. (ii) Replacing new items shall be measured and paid separately as supply only. (iii) Contractor shall submit the connected document/graph for relay calibration duly authenticated by authorised dealer/service center.
Supply and fix in repairs battery bank of capacity 24 volt consisting of ( 02 Nos each of 12 V maintenance free battery of 120 AH capacity) with replacement of battery bank of capacity 24 V, consisting of (12 Nos) of 02 Volts Each 120 AH maintenance free "Exide" make for system voltage 24 V, including disconnection of old U/S battery bank complete all as specified and directed.
M & L for servicing the battery bank by replacing the unserviceable spares, meters all as specified and as specified
Star Electrical
Rama Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .