Loading…
Loading…
Tender Value
₹14.7 L
EMD Value
₹29,500
Closing Date
21 Jul 2026, 11:00 amClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
45 days
Expenditure
Capital (Works)
Above/Below/Par
TECHNICAL
12 conditions · 1 needing a document upload
Tenderer must have to submit valid Electrical Contractor license as per Indian Electricity Rules for the respective category of works issued by Government Electrical License Board on or before the closing date of tender. Copy of the electrical contractor license should be submitted along with the tender offer, otherwise, the tender will be summarily rejected.
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
51 conditions · 5 needing a document upload
Whether the cost of earnest money deposited
Migration to GST regime - Special Tender Conditions: The rates should clearly indicate the rate of applicable duties and taxes included in the prices quoted by them. Any variation in tax structure/ rate due to introduction of GST, shall be dealt with under Statutory Variation Clause. It should be ensure that bidders/tenderers are GST compliant and quoted tax structure/rates are as per GST Law.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Contractor should submit the GSTIN number and same should be mentioned in the bills along with a copy of GSTIN registration certificate while submitting the bills to accounts for audit and payment, As GST is scheduled to implemented wef 01.07.2017. Without GSTN, no bill will be accepted w.e.f. 01.07.2017
From 01.07.2017 GST has been implemented but the detail guideline is still not clear. Hence, new tax structure on materials and labour will be applicable to both Railway & contractor after getting proper notification
Payment of Earnest Money deposit (EMD) , in respect of e- tendering,should be accepted through net banking or online payment gateway only
Provision of construction of RPF barrack at Chaparmukh(30 bedded capacity). (Electric portion)
EL-LM-26-27-10
EL-LM-26-27-10
Open
Works - General
90 Days
Hojai, Assam
₹0
₹29,500
21 Jul 2026
29 Jun 2026
7 Jul 2026
53 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 14,73,169.81 | ||
| — | 300.00 | — | — | ||
| Supply of materials and wiring of light point through concealed wiring by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch(with indicator type) to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes.(i.e thickness of mounting boxes of 3 mm and inside width of box should be 50 mm). All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. | — | — | — | 1,16,844 | |
| — | 50.00 | — | — | ||
| Supply of materials and wiring of fan point through concealed wiring by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch(with fan marking) and module type step fan regulator of 100 W to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes.(i.e thickness of mounting boxes of 3 mm and inside width of box should be 50 mm). All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. | — | — | — | 23,791.5 | |
| — | 80.00 | — | — | ||
| Supply of materials and wiring of 6 amps plug point through concealed wiring by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch(with indicator type) and 2 modular 6 Amps 5 Pin universal socket to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes.(i.e thickness of mounting boxes of 3 mm and inside width of box should be 50 mm). All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. | — | — | — | 19,782.4 | |
| — | 3.00 | — | — | ||
| Supply and wiring of geyser point by good quality accessories with proper connection complete with 15 amps plug point and 16 amps DP MCB overload protection, through concealed wiring by 4 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire: All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. | — | — | — | 1,846.41 | |
| — | 100.00 | — | — | ||
| Supply, fitting fixing of 18/20 watt Led indoor light | — | — | — | 32,284 | |
| — | 10.00 | — | — | ||
| Supply of materials and wiring of Exhaust fan point through concealed wiring by 1.5 sq mm single core PVC insulated flexible industrial unsheathed FRLSH copper wire through PVC concealed rigid conduit pipe with earth continuity by 1 sq mm single core PVC insulated unsheathed flexible copper wire and modular type 6 amps controlling switch(with fan marking) to be provided on good quality modular plate and frame of suitable sizes and mounting box of proper sizes.(ie thickness of mounting boxes of 3 mm and inside width of box should be 50 mm). All other necessary accessories i.e PVC Tee, Bend etc will be supplied by contractor. After concealed if needed than the concealed portion will be painted by contractor as per site colour of the surface. | — | — | — | 5,158 | |
| — | 1.00 | — | — | ||
| Supply, installation, connection, testing and commissioning of 8 way SPN (Single Pole & Neutral) distribution board, single door type, suitable for concealed wiring, complete with all necessary accessories and internal connections. The DB shall be equipped with the following protective devices: (i) 16 Amp SP MCB, C Curve - 2 Nos., (ii) 10 Amp SP MCB, C Curve - 2 Nos., (iii) 6 Amp SP MCB, C Curve - 2 Nos., and (iv) Over Voltage Release/MSU 275V AC - 1 No. The distribution board shall be complete with suitable enclosure, neutral link, earth bar, bus bar, terminals, mounting arrangements and all required hardware. The work shall include proper fixing, connection, testing and commissioning of the DB compatible with concealed wiring system as per manufacturer's specifications and direction of Engineer-in-Charge. | — | — | — | 4,903 | |
| — | 25.00 | — | — | ||
| Supply, fitting, fixing, testing, installation & commissioning of 45 Watt outdoor type LED street light fitting made up of pressure die cast aluminum housing with high power LED as lighting source and lens embedded PC cover having TOP Opening separate driver compartment with IP66 protection and impact resistance of IK07. The street light must be conforms to the technical specification i.e. attached in the tender document. The whole work shall be executed as per direction of Engineer in charge at site. | — | — | — | 1,11,649 | |
| — | 1.00 | — | — | ||
| Supply, installation, connection, testing and commissioning of 12 way LT Panel suitable for concealed wiring system, complete with suitable enclosure, bus bar arrangement, internal wiring, terminals, mounting accessories and all necessary hardware. The LT panel shall comprise of the following protective devices: (i) 250 Amp TPN MCCB, C Curve - 1 No., (ii) 100 Amp MCCB, C Curve - 2 Nos., (iii) 63 Amp, 4 Pole MCB, C Curve - 4 Nos., and (iv) Over Voltage Release - 4 Nos. The panel shall be complete with phase indication, neutral and earth arrangement, proper cable entry provisions, internal connections and all required accessories. The work shall include fixing, termination, testing and commissioning of the complete LT panel compatible with concealed wiring system as per applicable IS/IEC standards, manufacturer's specifications and direction of Engineer- in-Charge. | — | — | — | 1,62,475 | |
| — | 12.00 | — | — | ||
| Supply,erection, installation & commissioning of 6 Mtr long Octagonal pole hot dip galvanized minimum 65 micron zinc coating with sectional dia 70 mm (top),130 mm (bottom).overall sectional thickness 3 mm complete with base plate of size (220x220x12)mm, 4 nos 600 mm long foundation bolt of suitable dia along with pipe cap type pole bracket 1000 mm long double arm made with suitable cap pipe 48.3 mm,3.25 mm thick arms.Junction plate made of 6 mm thick Bakelite sheet with 10 amps SP MCB c curve & 4 nos end terminals to be mounted inside the base compartment of Octagonal pole.The work will also include supply and erection of PCC/RCC works for foundation of size 55 cm x 55 cm and depth 1 Mtr below GL and height 20 cm above GL in proportion 1:2:4 with stone chips of maximum aggregate size 20 mm and less including cement,sand & provision of 75 mm dia pvc pipe for cable entry with excavation of earth for foundation of all depth and all places,nature and condition of soil including de-watering,shoring, shuttering, batchning,mixing,placing,leveling,carrying,etc and refilling the pit after completion of foundation work from excavated earth or borrowed pit by contractors own arrangement for octagonal pole.(considering SBC of soil is 10 Ton/sq.Mtr) | — | — | — | 77,189.52 | |
| — | 800.00 | — | — | ||
| Making of cable trench dimension 300 mm wide and 1000mm deep by excavation of earth. The cable shall be protected by laying of brick in 3 sides with filling of sand as per the direction of Engineer in charge at site (Outside track crossing) and backfilling of earth/ ballast. The work to be executed as per enclosed specification | — | — | — | 38,416 | |
| — | 100.00 | — | — | ||
| Making of bore for putting the cable under the track/road (Inside track/road boring) by crossing it through requisite dia as per direction of Engineer in charge at site. | — | — | — | 17,833 | |
| — | 1800.00 | — | — | ||
| Supply and wiring of main line (concealed type) by 1.1 KV grade HRFR PVC insulated single core 10 mm2 multistrand flexible copper cable conforming to IS:694/1990 through 25 mm dia. PVC conduit pipe including earth continuity by HRFR PVC insulated singe core 10mm2 multi strand flexible copper wire as per direction of Engineer Incharge at site. | — | — | — | 4,06,260 | |
| — | 2000.00 | — | — | ||
| Supply and wiring of sub-main line (concealed type) by 1.1 KV grade HRFR PVC insulated single core 6 mm2 multistrand flexible copper cable conforming to IS:694/1990 through 25 mm dia. PVC conduit pipe including earth continuity by HRFR PVC insulated singe core 6 mm2 multiflexible stranded copper wire as per direction of Engineer In charge at site. | — | — | — | 2,70,220 | |
| — | 600.00 | — | — | ||
| Supply and wiring of sub-main line (concealed type) by 1.1 KV grade HRFRPVC insulated single core 4 sqmm multistrand flexible copper cable conforming to IS:694/1990 through 25 mm dia. PVC conduit pipe including earth continuity by HRFR PVC insulated singe core 4 mm2 multiflexible stranded copper wire as per direction of Engineer Incharge at site. | — | — | — | 61,158 | |
| — | 10.00 | — | — | ||
| Supply, fitting, fixing, connection & commissioning of 300 mm sweep heavy duty exhaust fan. All consumables regarding fixing arrangement will be supplied by the contractor as per the direction of engineer in charge at site. | — | — | — | 6,878.3 | |
| — | 3.00 | — | — | ||
| Supply, fitting, fixing, installation, testing and commissioning of 25 litres capacity electric storage water heater (geyser), suitable for 230V AC, 50 Hz single phase supply, complete with insulated storage tank, heating element, thermostat control, thermal cut-out, safety valve/pressure relief valve, wall mounting arrangement, necessary accessories, electrical connections, fittings and all required hardware. The work shall include transportation, installation, testing and commissioning of the geyser complete in all respects as per manufacturer's specifications and direction of Engineer-in-Charge. | — | — | — | 49,929 | |
| — | 30.00 | — | — | ||
| Fabrication, supply, installation, testing and commissioning of international glow trilingual signage board single sided of different size and 20 cm width of 20 SWG thick aluminum sheet powder coated box with different color font and back surface, details given below, base made of white penaflex sheeting duly stretched of 627 gram per sq mt. (18.5 ounce per sq yard) thickness 0.52 mm & colored translucent vinyl sheeting base, subject matter and logo in different size and in different color given below with 20w/10w LED tube fitting as required for suitable glow of the board . Panaflex sheet should of reputed make. As per site incharge instruction.(2'x1.5'x10=240 sq feet) | — | — | — | 4,438.2 | |
| — | 20.00 | — | — | ||
| Supply and erection of earthing by 50 mm dia 3.60 mm thick 3 mtr long GI pipe with (25x5) mm GI strip & GI nut/bolts/washers etc as per CEE/MLGs diagram CEE/STD/1. | — | — | — | 10,866.6 | |
| — | 400.00 | — | — | ||
| Supply and drawing of 2.5 sqmm single core multi strand copper cable. | — | — | — | 18,340 | |
| — | 14.00 | — | — | ||
| Carrying and Erection of tubular pole 10 mtr long including digging the pit 1/5th of the total length.The whole work shall be executed as per direction of Engineer in charge at site | — | — | — | 6,515.88 | |
| — | 2.14 | — | — | ||
| Supply and erection of PCC/RCC works for foundation of column,pillars,posts,struts etc. excluding the cost of cement shuttering and centering.(CC block will be 30 cm dia with height upto the pole depth below GL and 30 cm above GL and 10 cm below base plate including tie- muffinng of DP)-a)1:3:6 (M-10)-1 cement,3 sand,6 graded stone aggregate 20 mm nominal size | — | — | — | 4,493.19 | |
| — | 0.71 | — | — | ||
| Ordinary portland cement grade-53 frade | — | — | — | 3,666.97 | |
| — | 17.00 | — | — | ||
| Supply & fixing of GI channel of size 75x40x40x6mm bracket of following size clamped with above pole made by GI flat 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting .(2200 mm long ) | — | — | — | 14,564.92 | |
| — | 16.00 | — | — | ||
| Supply & fixing of GI channel of size 75x40x40x6mm bracket of following size clamped with above pole made by MS flat 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting .(300 mm long bracket) | — | — | — | 2,746.88 | |
| — | 44.00 | — | — | ||
| Supply and fixing of pin type insulator of size 80 x 105 mm complete with 50 x 5 mm MS 'D' clamp, suitable nuts, bolts and all required accessories. The work shall include proper fixing, alignment and securing of the insulator assembly on the supporting structure complete in all respects as per site requirement and direction of Engineer-in-Charge. | — | — | — | 920.04 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
EL-LM-26-27-10final.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .