Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹20.7 CrAdmitted-Finance | L1 | Admitted-Finance | ||
| 2 | L2₹22.9 Cr+₹2.2 Cr (10.6%)Admitted-Finance | L2 | Admitted-Finance |
Tender Value
₹25.8 Cr
EMD Value
₹51.7 L
Closing Date
3 Jun 2025, 6:00 pmClosed
se
BDA OFFICE
Work of internal electrification in S.P.Z scheme of Development Authority.
2025_UITBR_471184_2
online nit no. 06(2024-2025)10 Bharatpur Development Authority
Open Tender
Electrical Works
Percentage
bharatpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,500
Secretary, UIT
₹51.7 L
Yes
19 Jun 2025
23 May 2025
4 Jun 2025
23 May 2025
3 Jun 2025
23 May 2025
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | DISTRIBUTION SUBSTATION PACKAGE SUB STATION WITH APFC PANEL Supplying installation testing and commissioning of 11/0.4KV 500 KVA Package sub stations with APFC panel as details below:- PSS/RMU-1A/1 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 500 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1000 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 800A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
"
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU -1A/1 described as above. | 1 | Set | 31,53,500 | ₹31,53,500 |
| 2 | Supplying installation testing and commissioning of 11/0.4KV 315 KVA Package sub stations with APFC panel as details below:-
PSS/RMU-2A/4 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 500 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1000 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 800A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
Outgoing
i. 100A, 4 Pole , 25KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 2nos
ii. 200A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 2nos
iii. 250A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 1nos
iv. 320A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 1nos
v. 400A, 4 Pole ,36KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 165kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction.
"
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU -2A/4 described as above. | 1 | Set | 31,53,500 | ₹31,53,500 |
| 3 | PSS/RMU-1A/2 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 315 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 630 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
MCCB, 500A, 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
"
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-1A/2described as above. | 1 | Set | 26,47,800 | ₹26,47,800 |
| 4 | PSS/RMU-1A/3 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 315 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 630 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
MCCB, 500A, 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp& Multifunction meter
"
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-1A/3 described as above. | 1 | Set | 26,47,800 | ₹26,47,800 |
| 5 | Supplying installation testing and commissioning of 11/0.4KV 630 KVA Package sub stations with APFC panel as details below:-
PSS/RMU-2A/2 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 315 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 630 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
MCCB, 500A, 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp& Multifunction meter
Outgoing
i. 250A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 3nos
ii. 250A, 4 Pole ,36KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 105kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction.
"
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-2A/2 described as above. | 1 | Set | 26,47,800 | ₹26,47,800 |
| 6 | PSS/RMU-2A/1 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I , EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 630 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1250A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 1000A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
Outgoing
i. 63A, 4 Pole , 25KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 1nos
ii. 200A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 4nos
iii. 320A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-3nos
iv. 500A, 4 Pole ,36KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 200kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction."
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-2A/1 described as above. | 1 | Set | 44,86,300 | ₹44,86,300 |
| 7 | PSS/RMU-2A/3 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 630KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1250 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 1000A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
Outgoing
i. 250A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 2nos
ii 320A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 3nos
iii. 500A, 4 Pole ,35KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 200kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction."
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-2A/3 described as above. | 1 | Set | 43,79,200 | ₹43,79,200 |
| 8 | Supplying installation testing and commissioning of 11/0.4KV 500 KVA Package sub stations with APFC panel as details below:-
PSS/RMU-2A/5 (BLOCK-A)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I , EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 630KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fitting Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1250 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 1000A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
Outgoing
i. 250A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF- 2nos
ii 320A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-3nos
iii. 500A, 4 Pole ,36KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 200kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction."
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-2A/5 described as above. | 1 | Set | 42,36,400 | ₹42,36,400 |
| 9 | PSS/RMU-B1 (BLOCK-B)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 500 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fittings Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1000 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 800A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
Outgoing
i. 63A, 4 Pole, 25KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-1nos
ii. 100A, 4 Pole , 25KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-1nos
iii. 160A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-3nos
iv 200A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-2nos
v. 400A, 4 Pole ,36KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 165kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction."
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-B1 described as above. | 1 | Set | 38,97,300 | ₹38,97,300 |
| 10 | Supplying installation testing and commissioning of 11/0.4KV 315 KVA Package sub stations with APFC panel as details below:-
PSS/RMU-B2 (BLOCK-B)
HT Switchgear
Outdoor type package / Compact substation complete with RMU, Transformer & LT Breaker panel including interconnecting HT & LT Cables complete housed in weather proof housing (As per OEM Design) made out of CRCA Sheet with louvers etc. and to withstand internal arch withstand test of 20kA for one second with internal earthing with Al strips, pad locking, internal lighting complete as required.
"RMU-NON-Extensible (2 isolators (C), 1 Vacuum circuit breaker(T2), cu busbars,
C FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit.
1. Operation of LBS- Manual.
2. Cable Switch Rating- 12KV, 630A, 21 KA/3 sec.
3. Cable Bushing Rating- 630A,
4. Cable Cover:- As per our standard,
5. Fixed type Capacitive voltage indication,
6. On/Off/EARTH Switch via MIMIC,
7. Bottom Cable Termination- Suitable up to 300sq. mm. ,
T2 FUNCTION Type:- 3 position Disconnection (or equivalent as approved by the Deptt.) and Earthing switch equipped with separate drive unit. T2 equipped with over current time release for transformer protection.
1. Vacuum circuit breaker 12 kV, 630A, 21 KA/3 sec.
2 Operation of breaker – MANUAL
3 Self Powered Electronic numerical protection relay providing over-current & earth fault protection – relay.
4 Ring core protection current transformers.
5 Aux. contacts for VCB. ( 2 no + 2nc )
6 Capacitive voltage indication fixed type.
7 ON, OFF, TRIP indication on the front mimic of the panel.
8 Cable box for termination of cable up to 1 No. x 300 sq. mm.
9 Cable cover standard.
10 Emergency trip push button.
11 Shunt trip coil – 230 V AC."
Transformer
"TRANSFORMER (Manufactured as per IS 1180), Part-I, EEL-1
TYPE:- ONAN, Hermitically sealed.
1. Ratio- 11KV/433V,
2. Capacity:- 500 KVA,
3. Vector Group- DYn11,
4. Off Load Tapings-+/-5% in steps of 2.5%,
5. Winding- Double wound copper,
6. Class of Insulation- A,
7. Ambient Temperature- 50Deg C,
8. Temperature rise in winding over ambient- 50Deg C,
9. Temperature rise in oil over ambient- 40Deg C,
9. Max losses at 50% loading - 1700 watts
10. Max losses at 100% loading - 6800 watts 11. Impedance - 5% ( IS tol applicable)"
"Transformer Fittings Accessories
As per IS"
LT Switchboard
"LT BUSBARS- ALUMINIUM
Voltage Rating- 433V
Current Rating- 1000 A
R/Y/B indicating lamps"
"LT PANEL
Incomer
ACB, 800A, MDO 4 Pole , 50 KA, microprocessor based over current, short circuit and earth fault release .
On, OFF, RYB lamp & Multifunction meter
Outgoing
i. 125A, 4 Pole , 25KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-1nos
ii. 250A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-2nos
iii. 320A, 4 Pole , 36KA, MCCB, microprocessor based over current, short circuit and earth fault release with ON/OFF-2nos
iv. 400A, 4 Pole ,36KA, MCCB, microprocessor based over current, short circuit and earth fault release . 1 nos for 165kVAR capacitor bank with Stepped relay(APFCR) with 8 steps (each to be of 50/20/5 KVAR) for automatic power factor correction."
ENCLOSURE-
HV KIT
EARTHING - ALUMINIUM
TROLLEY
COPPER FLEXIBLE
With Oil type Transformer
PSS/RMU-B2 described as above. | 1 | Set | 38,37,800 | ₹38,37,800 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.43 MB
techbid10.pdf
Tender Documents • 15.35 MB
BOQ_845200.xls
BOQ • 0.77 MB
Tenderdocument.pdf
Tender Documents • 15.35 MB
BOQ.xls
BOQ • 0.79 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .