Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 LAccepted-Finance | L1 | Accepted-Finance Lowest | |
| 2 | L2₹3.5 L+₹2,739 (0.78%)Rejected-Finance | L2 | Rejected-Finance 2nd. Lowest | |
| 3 | L3₹3.6 L+₹8,448 (2.42%)Rejected-Finance | L3 | Rejected-Finance 3rd. Lowest |
| Sl No | Description | Qty | Unit | SKY DECORATIONS PRIVATE LIMITED L3 | HIMAYAN L2 | SUPER COOLING AGENCY L1 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing, and Commissioning of air-cooled Hi-Wall split type air conditioners of following capacities comprising Indoor and Outdoor Units with factory-charged Rotary/Scroll compressors (R-32/R-410A) including surface/concealed copper refrigerant piping insulated with closed-cell elastomeric nitrile rubber insulation and wrapping tape (up to 3 m), FRLS type copper power cable (up to 3.5 m) with suitable plug top, 3 meters of drain pipe, and wireless remote control with suitable battery. The system shall operate on 230V, 50Hz (±tolerance as per applicable standard), single-phase AC supply, providing cooling, dehumidification, and air circulation functions conforming to IS-1391 (Part-II ) with all amendments, and shall be capable of efficient performance at outdoor ambient temperatures up to 50°C, with a minimum 5 year OEM warranty on both the compressor and PCB. The system shall be installed with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC (Make: Mitsubishi Electric/O-General/Daikin) | ||||||
| 1.01 | Cooling Capacity- 5.2 kW (Minimum) , Air Flow Rate:600 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) | 1 | nos. | 48,900 ₹48,900 | 48,220 ₹48,220 | 47,700 ₹47,700 Lowest |
| 1.02 | Cooling Capacity- 6.1 kW (Minimum) , Air Flow Rate:800 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) | 4 | nos. | 63,000 ₹2,52,000 | 62,310 ₹2,49,240 | 61,700 ₹2,46,800 Lowest |
| 2.00Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : | ||||||
| 2.01 | 1/4" or 6.4 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 7 | mtrs. | 155 ₹1,085 | 155 ₹1,085 | 153 ₹1,071 Lowest |
| 2.02 | 3/8" or 9.5 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 20 | mtrs. | 210 ₹4,200 | 207 ₹4,140 | 204 ₹4,080 Lowest |
| 2.03 | 1/2" or 12.7 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 7 | mtrs. | 315 ₹2,205 | 310 ₹2,170 | 307 ₹2,149 Lowest |
| 2.04 | 5/8" or15.86 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 20 | mtrs. | 370 ₹7,400 | 365 ₹7,300 | 362 ₹7,240 Lowest |
| 3.00 | S&F of additional following items for length exceeding 3.5 mtr for complete installation and commissioning of aboove AC machines. i) 2.5 sqmm, 3/4 core copper cable (FRLS type) | 27 | mtrs. | 205 ₹5,535 | 130 ₹3,510 Lowest | 180 ₹4,860 |
| 4.00 | Supply & laying Soft Drawn PVC Drain Pipe 19mm dia with proper supports & brackets as per direction EIC. | 10 | mtrs. | 75 ₹750 | 75 ₹750 | 72 ₹720 Lowest |
Tender Value
Refer Docs
EMD Value
₹7,100
Closing Date
17 Jun 2026, 4:00 pmClosed
Assistant Engineer
West Bengal Legislative Assembly South Annex Building Gr Floor Kolkata 700 001
Conversion of attached toilet at Block-B of the Upper Lobby of the Debating Chamber, assembly House into server room and store room under assembly House electrical Sub. Divn. Part II Air-condition Work.
2026_WBPWD_5014923_1
eNIQ No. - 02 /WBPWD/AE/AHESD of 2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Assembly House
Please refer Tender documents.
6 documents required · 6 mandatory
₹7,100
Yes
9 Sept 2026
4 Jun 2026
22 Jun 2026
4 Jun 2026
17 Jun 2026
6 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing, and Commissioning of air-cooled Hi-Wall split type air conditioners of following capacities comprising Indoor and Outdoor Units with factory-charged Rotary/Scroll compressors (R-32/R-410A) including surface/concealed copper refrigerant piping insulated with closed-cell elastomeric nitrile rubber insulation and wrapping tape (up to 3 m), FRLS type copper power cable (up to 3.5 m) with suitable plug top, 3 meters of drain pipe, and wireless remote control with suitable battery. The system shall operate on 230V, 50Hz (±tolerance as per applicable standard), single-phase AC supply, providing cooling, dehumidification, and air circulation functions conforming to IS-1391 (Part-II ) with all amendments, and shall be capable of efficient performance at outdoor ambient temperatures up to 50°C, with a minimum 5 year OEM warranty on both the compressor and PCB. The system shall be installed with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC (Make: Mitsubishi Electric/O-General/Daikin) | |||||
| 1.01 | Cooling Capacity- 5.2 kW (Minimum) , Air Flow Rate:600 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) | 1 | nos. | - | - |
| 1.02 | Cooling Capacity- 6.1 kW (Minimum) , Air Flow Rate:800 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) | 4 | nos. | - | - |
| 2Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : | |||||
| 2.01 | 1/4" or 6.4 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 7 | mtrs. | - | - |
| 2.02 | 3/8" or 9.5 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 20 | mtrs. | - | - |
| 2.03 | 1/2" or 12.7 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 7 | mtrs. | - | - |
| 2.04 | 5/8" or15.86 mm dia (OD) (Soft drawn) as per standard BS864 or ASNISB 1622 | 20 | mtrs. | - | - |
| 3 | S&F of additional following items for length exceeding 3.5 mtr for complete installation and commissioning of aboove AC machines. i) 2.5 sqmm, 3/4 core copper cable (FRLS type) | 27 | mtrs. | - | - |
| 4 | Supply & laying Soft Drawn PVC Drain Pipe 19mm dia with proper supports & brackets as per direction EIC. | 10 | mtrs. | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.53 MB
Tendernotice_2.pdf
PDF • 0.62 MB
BOQ_5083361.xls
BOQ • 0.26 MB
Corrigendum.pdf
PDF • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .